4. Installation
4.1 Location
The Quest Dual Dehumidifier can be installed in a variety of locations to meet the owner’s needs as listed below. In all
cases keep the following cautions in mind:
• It is designed to be installed INDOORS IN A SPACE THAT IS PROTECTED FROM RAIN AND FLOODING.
• Install the unit with space to access the back and side panels for maintenance and service and also to allow easy
access to the filter cover panel. DO NOT INSTALL UNIT WITH THE FRONT PANEL OR FILTER COVER
PANEL INACCESSIBLE.
• Avoid discharging the air directly at people, or over the water in pool areas.
• Be certain there is NO chance the unit could fall into water or be splashed and that it is plugged into a GROUND
FAULT INTERRUPTER.
• DO NOT use the Quest Dual Dehumidifier as a bench or table.
• DO NOT place the Quest Dual Dehumidifier directly on structural members. Provide vibration isolation in order to
minimize operational vibration and/or noise.
• A drain pan MUST be placed under the unit if installed above an area where water leakage could cause damage.
• Maintain a minimum 1ft. (.3m) clearance to avoid obstructing the air return and supply.
• Place the Quest Dual Dehumidifier on supports that raise the base of the unit 2.5” above the drain pan to a P-trap
can be installed. See Section 4.3.
• The Quest Dual Dehumidifier may be suspended with steel hanger, straps, or a suitable alternative from structural
members, unit must be supported from underneath. Don’t hang from sides or ends. See section 4.4
4.2 Electrical Requirements
The Quest Dual Dehumidifier plugs into NEMA rated Receptacles. The amp draws for each unit under normal operating
conditions are listed on page 4. A ground fault interrupter protected circuit is required.
CAUTION! For proper drainage, the unit must be mounted so the drain outlet is at least 4”
above the floor drain, and must be fully supported under the base.