Ultra-Aire 135H Air Purifying Dehumidifier Owners Manual

The mixture of gas and liquid refrigerant enter the accumulator
after leaving the evaporator coil. The accumulator prevents
any liquid refrigerant from reaching the compressor. The 
compressor evacuates the cool refrigerant gas from the
accumulator and compresses it to a high pressure and 
temperature

7.2 Troubleshooting

No dehumidification, neither impeller fan nor compressor 
run with fan switch and ventilation timer OFF.

1. Unit unplugged or no power to outlet.
2. Humidity control set too high or defective.
3. Loose connection in internal or control wiring.
4. Defective Compressor relay.
5. Defective control transformer.
6. Low pressure Control open.
7. Optional Condensate Pump Safety Switch open.

No dehumidification, compressor does not run but impeller
fan runs with fan switch and ventilation timer OFF and
humidity control turned to ON.

1. Defective compressor run capacitor.
2. Bad connection in compressor circuit.
3. Defective compressor overload.
4. Defective compressor.
5. Defrost thermostat open.

Impeller fan runs with fan switch and ventilation timer OFF,
but compressor cycles on & off.

1. Low ambient temperature and/or humidity causing

unit to cycle through defrost mode.

2. Defective compressor overload.
3. Defective compressor.
4. Defrost thermostat defective.
5. Dirty air filter(s) or airflow restricted.
6. Low refrigerant charge, causing defrost control 

to cycle.

7. Bad connection in compressor circuit. Impeller fan

does not run with fan switch in either position.

Impeller fan does not run with ventilation timer activated.
Compressor runs briefly but cycles on & off with humidity
control turned to ON.

1. Loose connection in impeller fan circuit.
2. Obstruction prevents impeller fan rotation.
3. Defective impeller fan.
4. Defective impeller fan relay.
5. Defective impeller fan capacitor.

Impeller fan runs with fan switch ON. Impeller fan does not
run with ventilation timer activated.

1. Defective ventilation timer.
2. Time not correct on ventilation timer.
3. Ventilation timer set to manual & switched OFF.
4. Defective fan switch.

Evaporator coil frosted continuously, low dehumidifying
capacity.

1. Defrost thermostat loose or defective.
2. Low refrigerant charge
3. Dirty air filter(s) or airflow restricted.
4. Excessively restrictive ducting connected to unit. 

Unit not providing ventilation. Ventilation timer not operating
correctly.

1. If timer is not functioning correctly reset timer and

reprogram.

2. Check control wire connections (check connections at

fresh air damper also).

3. Defective fresh air damper.
4. Defective fan switch.

Unit removes some water, but not as much as expected.

1. Air temperature and/or humidity have dropped.
2. Humidity meter and or thermometer used are 

out of calibration.

3. Unit has entered defrost cycle.
4. Air filter dirty.
5. Defective defrost thermostat.
6. Low refrigerant charge.
7. Air leak such as loose cover or ducting leaks.
8. Defective compressor.
9. Restrictive ducting.
10. Optional Condensate Pump Safety Switch open.

Unit Test to determine problem:

1. Detach field control wiring connections from main unit.
2. Connect the yellow and green pigtails from the main

unit together; only the impeller fan should run.
Disconnect the wires.

3. Connect the yellow and blue pigtails from the main

unit together; the compressor and impeller fan 
should run.

4. If these tests work, the main unit is working properly.

You should check the control panel and field control
wiring for problems next.

5. Remove the control panel from the mounting box and

detach it from the field installed control wiring.
Connect the blue, yellow, and green wires from the
control panel directly to the corresponding colored pig-
tails on the main unit. Leave the violet, white and red
wires disconnected!

6. Turn on the fan switch; the impeller fan should run.

Turn off the fan switch.

7. Turn on the humidity control; the compressor and

impeller fan should run.

8. If these tests work, the problem is most likely in the

field control wiring.

Содержание FOCUS Ultra-Aire 135H

Страница 1: ...midification The highly efficient Ultra Aire APD UA 135H dehumidifier utilizes refrigeration to cool the incoming air stream below its dew point This cooled and drier air is used to pre cool the incoming air stream resulting in up to a 200 percent increase in overall efficiency After the pre cooling stage the processed air is reheated by passing through the condenser coil The heat removed by the e...

Страница 2: ... room The ductwork of the existing heating system can be used to supply air to the home 2 Registrations The Ultra Aire 135H P N 4025080 conforms to UL STD 1995 Certified to CAN CSA STD C22 2 No 236 3 Specifications Model UA 135H Air Purifying Dehumidifier Electrical 110 120 VAC 12 Amps 60 Hz grounded Capacity 135 pints day 80 F 60 RH Operating Temp 55 F min 100 F max Air Flow 355 CFM without exter...

Страница 3: ...troller WITHOUT Fresh Air Refer to Sections 5 through Section 5 2G only 4 2 Humidity Control Adjustment Set the humidity control to the desired humidity level for the home Turning the knob clockwise results in a drier setting See the back of the control panel cover for set points The dehumidifier will run continuously until the relative humidity RH is reduced to the humidity control dial setting S...

Страница 4: ... Now with the ventilation start time set press the I O button The word OFF should appear to the right of the time and the number 1 should remain in the lower right hand corner of the display The 1 and OFF signify the turn off time for the first program Set the turn off time using the 1 7 h and m buttons in the same way as described above and continue on to the second through sixth programs When se...

Страница 5: ...r time 3 Push CLOCK button again The day display will flash Use the buttons to select the proper day 4 Push CLOCK button again The AM PM display will flash Verify AM PM setting is correct 5 Push CLOCK button again or wait a few seconds for the display to stop flashing The time is now set 5 2E Setting Relative Humidity Setpoint The relative humidity setpoint operates the dehumidifier function of th...

Страница 6: ... will be open and the fan of the system will be operating in order to introduce fresh air into the space Use this mode for continuous fresh air ventilation The fan is always on when the damper is open When in off mode the damper will not open and the sys tem will not ventilate When in the program mode the control will operate the damper and fan ventilate according to the programmed ventilation sch...

Страница 7: ...t exchange coils inside the unit could become clogged and require disassembly to clean Filter non compliance invalidates the product warranty 6 2 High Efficiency Air Filter An optional high efficiency pleated microglass paper filter is available for the UA 135H This filter is rated as 90 95 efficient by the ASHRAE Dust Spot test method 52 76 The high efficiency pleated microglass paper filter shou...

Страница 8: ...mpeller fan does not run with ventilation timer activated 1 Defective ventilation timer 2 Time not correct on ventilation timer 3 Ventilation timer set to manual switched OFF 4 Defective fan switch Evaporator coil frosted continuously low dehumidifying capacity 1 Defrost thermostat loose or defective 2 Low refrigerant charge 3 Dirty air filter s or airflow restricted 4 Excessively restrictive duct...

Страница 9: ...move the charge and weigh in the refrigerant quantity listed on the nameplate Operate the system to verify performance 7 7 Electric Ventilation Damper The electric ventilation damper is controlled by the ventilation timer The damper will open when the ventilation timer is activated to allow fresh air into the structure through the 6 diameter fresh air inlet duct The electric ventilation damper wil...

Страница 10: ...care and proper return packaging LIMITATIONS AND EXCLUSIONS This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC s reasonable control If any Ultra Aire 135H part is repaired or replaced the new...

Страница 11: ...n 3 4024539 DEH 2000 Digital Controller 4 4025287 Filter Box 5 4022220 Condensate Pump Kit External 6 4024377 Optional External Insulation Kit not shown 7 4024369 2 x20 x24 Filter not shown 8 4024370 4 x20 x24 Filter not shown 9 4020646 10 Backdraft Damper not shown 10 4025463 Stand Kit not shown Figure 1 Ventilation Timer Humidity Control Figure 2 Humidity Fan Control Figure 5 Condensate Pump Fig...

Страница 12: ...22 1447 Web www thermastor com Email sales thermastor com Information in this document is subject to change without notice No part of this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2004 Therma Stor LLC All rights reserved ...

Отзывы: