Ultra-Aire 135H Air Purifying Dehumidifier Owners Manual

one-minute time increments of the ventilation timer allow you
to program the ventilation of your home to fit your schedule.

The ventilation timer allows six programs with each program
having one "on" and one "off" event. A program allows the
user to turn the ventilation on at a certain day and time, then
it allows them to turn the ventilation off at a certain day and
time. Each of these programs can be repeated daily or week-
ly or during a specified block of days. All six of the programs
operate independently of each other. If the timer fails to oper-
ate or operates erratically, check that the control panel
receives 24Vac from the UA-135H. If 24Vac is present at the
control panel, reset the timer by pressing the reset button at
the bottom center of the timer face. The reset button is the
small recessed button with an R beneath it located below the
1...7 and h buttons. Depress the reset button until the dis-
play clears. Release the reset button. The display will reap-
pear as 00:00. Resetting the timer will clear the time and all
program settings. After resetting the timer follow the instruc-
tions below to set the correct time and ventilation programs.

4.5 Setting the Time

First, set the correct time on the timer by sliding the switch in
the upper right hand corner of the timer to the clock symbol.
and pressing the 1...7 (DAY), h (HOUR), and m (MINUTE) 
buttons. Remember this timer operates on a 24-hour (military
time) clock. 

4.6 Ventilation Schedule

Slide the switch in the upper right hand corner to the program
symbol P. "ON" will appear to the right of the time and the
number "1" will appear in the lower right hand corner of the
display. The "1" and "ON" signify the turn on time for the first
program. Press the 1...7, h and m button to choose the days
of the week for this program. You can choose Mon.-Sun,
Mon.-Fri., Sat-Sun, or any single day of the week. The days
chosen are shown along the top of the display on the ventila-
tion timer. Next press the h button to set the hour for the
start of the ventilation period. Remember this timer operates
on a 24-hour clock (military time). Then press the m button to
set the minutes past the hour to start the ventilation. Now,
with the ventilation start time set; press the I/O button. The
word "OFF" should appear to the right of the time and the
number "1" should remain in the lower right hand corner of
the display. The "1" and "OFF" signify the turn off time for the
first program. Set the turn off time using the 1...7, h and m
buttons in the same way as described above and continue 
on to the second through sixth programs. When setting the
ventilation programs, you can return to the current time 
display by sliding the switch in the upper right corner of the
timer to RUN. The slide switch must be set to RUN for the
timer to operate its scheduled programs.

4.7 Automatic or Manual Mode

The slide switch in the upper left of the timer is used to
choose between automatic and manual operation. When the
slide switch is set to AUTO mode, the UA-135H will ventilate

when the scheduled programs call for ventilation. When the
slide switch is set to manual (set to hand symbol on the
right), the operation of the timer is controlled by the I/O 
button only. Pressing the I/O button will switch the ventilation
timer between ON (detent) and OFF (detent). As you press the
I/O button, "ON" or "OFF" will be displayed to the right of the
time. The "ON" or "OFF" indicates if the ventilation timer is on
or off. The I/O button will manually override scheduled pro-
grams if the timer is in AUTO mode.

4.8 Low Pressure Control

If the low side refrigerant pressure drops to 15 PSIG, the 
low-pressure control opens and shuts off the compressor and
impeller fan. It is automatically reset when the pressure rises
to 35 PSIG. Its primary function is to prevent damage to the
compressor. It may also open if the unit is A) installed in a
cool area (below 50°F) or B) installed where it is below 40°F
and then started. Under these conditions, the unit will restart
within several minutes. Until the unit warms up, it may repeat
the cycle several times.

5 (DEH 2000) Digital Control

DEH 2000 Digital Ventilation Timer/Humidity/Fan Control
Installation & Operation Instructions

5.1 Specifications

Model: 4024539
Electrical: 24 

VAC

Humidity Range: 

20 – 90% RH

Humidity Accuracy: 

+/- 4%

Output: 

3 Amps 24 VAC

5.2 Operation

5.2A Display

When there is power to the control, the control display
sequence will alternately show the clock, humidity,
temperature, fan status, and fresh air damper status.
The display sequence repeats continually, and is referred to
as “home state”.

Figure 1:

DEH 2000 Digital Display

Содержание FOCUS Ultra-Aire 135H

Страница 1: ...midification The highly efficient Ultra Aire APD UA 135H dehumidifier utilizes refrigeration to cool the incoming air stream below its dew point This cooled and drier air is used to pre cool the incoming air stream resulting in up to a 200 percent increase in overall efficiency After the pre cooling stage the processed air is reheated by passing through the condenser coil The heat removed by the e...

Страница 2: ... room The ductwork of the existing heating system can be used to supply air to the home 2 Registrations The Ultra Aire 135H P N 4025080 conforms to UL STD 1995 Certified to CAN CSA STD C22 2 No 236 3 Specifications Model UA 135H Air Purifying Dehumidifier Electrical 110 120 VAC 12 Amps 60 Hz grounded Capacity 135 pints day 80 F 60 RH Operating Temp 55 F min 100 F max Air Flow 355 CFM without exter...

Страница 3: ...troller WITHOUT Fresh Air Refer to Sections 5 through Section 5 2G only 4 2 Humidity Control Adjustment Set the humidity control to the desired humidity level for the home Turning the knob clockwise results in a drier setting See the back of the control panel cover for set points The dehumidifier will run continuously until the relative humidity RH is reduced to the humidity control dial setting S...

Страница 4: ... Now with the ventilation start time set press the I O button The word OFF should appear to the right of the time and the number 1 should remain in the lower right hand corner of the display The 1 and OFF signify the turn off time for the first program Set the turn off time using the 1 7 h and m buttons in the same way as described above and continue on to the second through sixth programs When se...

Страница 5: ...r time 3 Push CLOCK button again The day display will flash Use the buttons to select the proper day 4 Push CLOCK button again The AM PM display will flash Verify AM PM setting is correct 5 Push CLOCK button again or wait a few seconds for the display to stop flashing The time is now set 5 2E Setting Relative Humidity Setpoint The relative humidity setpoint operates the dehumidifier function of th...

Страница 6: ... will be open and the fan of the system will be operating in order to introduce fresh air into the space Use this mode for continuous fresh air ventilation The fan is always on when the damper is open When in off mode the damper will not open and the sys tem will not ventilate When in the program mode the control will operate the damper and fan ventilate according to the programmed ventilation sch...

Страница 7: ...t exchange coils inside the unit could become clogged and require disassembly to clean Filter non compliance invalidates the product warranty 6 2 High Efficiency Air Filter An optional high efficiency pleated microglass paper filter is available for the UA 135H This filter is rated as 90 95 efficient by the ASHRAE Dust Spot test method 52 76 The high efficiency pleated microglass paper filter shou...

Страница 8: ...mpeller fan does not run with ventilation timer activated 1 Defective ventilation timer 2 Time not correct on ventilation timer 3 Ventilation timer set to manual switched OFF 4 Defective fan switch Evaporator coil frosted continuously low dehumidifying capacity 1 Defrost thermostat loose or defective 2 Low refrigerant charge 3 Dirty air filter s or airflow restricted 4 Excessively restrictive duct...

Страница 9: ...move the charge and weigh in the refrigerant quantity listed on the nameplate Operate the system to verify performance 7 7 Electric Ventilation Damper The electric ventilation damper is controlled by the ventilation timer The damper will open when the ventilation timer is activated to allow fresh air into the structure through the 6 diameter fresh air inlet duct The electric ventilation damper wil...

Страница 10: ...care and proper return packaging LIMITATIONS AND EXCLUSIONS This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC s reasonable control If any Ultra Aire 135H part is repaired or replaced the new...

Страница 11: ...n 3 4024539 DEH 2000 Digital Controller 4 4025287 Filter Box 5 4022220 Condensate Pump Kit External 6 4024377 Optional External Insulation Kit not shown 7 4024369 2 x20 x24 Filter not shown 8 4024370 4 x20 x24 Filter not shown 9 4020646 10 Backdraft Damper not shown 10 4025463 Stand Kit not shown Figure 1 Ventilation Timer Humidity Control Figure 2 Humidity Fan Control Figure 5 Condensate Pump Fig...

Страница 12: ...22 1447 Web www thermastor com Email sales thermastor com Information in this document is subject to change without notice No part of this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2004 Therma Stor LLC All rights reserved ...

Отзывы: