7.3 Refrigerant Charging

If the refrigerant charge is lost due to service or a leak, a
new charge must be accurately weighed in. If any of the old
charge is left in the system, it must be recovered before
weighing in the new charge. Refer to the unit nameplate for
the correct charge weight and refrigerant type.

7.4 Impeller Fan Replacement

The motorized impeller fan is a unitary assembly consisting
of the motor and impeller fan. If defective, the complete
assembly must be replaced.

1.  Unplug the power cord
2.  Remove the cabinet access panel
3.  Disconnect the impeller's blue, black, brown leads,

which are attached to the capacitors as well as the
green/yellow ground lead.

4.  Remove the impeller access plate, which is the

D-shaped plate mounted to the supply/exhaust panel
of the UA-135H. The impeller should be attached to
this D-shaped plate. Pull the leads through the black 
plastic scroll housing inside, as you remove the
impeller access plate.

5.  Remove the two cable clamps securing the impeller

cord to the access plate.

6.  Remove the defective impeller from the access plate
7.  Reassemble the new impeller fan by reversing the

above procedure.  Note:  Make sure that the new
impeller cord is secured tightly to the impeller access
plate utilizing the two cable clamps given with the unit.
Make sure to reconnect all leads in their correct posi-
tions.

7.5 Compressor/Capacitor Replacement

This compressor is equipped with a two terminal external
overload and a run capacitor, but no start capacitor or relay. 

CAUTION-ELECTRICAL SHOCK HAZARD: Electrical power
must be present to perform some tests. These tests should
be performed by a qualified service person.

7.6 Replacing a Compressor, Nonburn Out

Remove the refrigerant from the system. Replace the 
compressor and liquid line filter/drier. Charge the system 
to 50 PSIG and check for leaks. Remove the charge and
weigh in the refrigerant quantity listed on the nameplate.
Operate the system to verify performance.

7.7 Electric Ventilation Damper

The electric ventilation damper is controlled by the ventilation
timer. The damper will open when the ventilation timer is
activated to allow fresh air into the structure through the 6”
diameter fresh air inlet duct. The electric ventilation damper
will remain closed when the ventilation timer is not activated
to prevent over-ventilating the structure when the unit is
dehumidifying or recirculating the indoor air.

The electric ventilation timer operates on 24 Vac from the
control circuit. DO NOT connect high voltage to the damper
motor or damage to the motor may result. DO NOT force the
blade of the damper by hand or damage to the damper
motor may result.

The damper opens in one direction only. The damper rotates
very slowly, allow sufficient time for the damper to cycle. The
damper will take approximately 1 minute to cycle from closed
to open or from open to closed.

If the electric ventilation damper fails to operate:

1. Check that the wiring is correct and that voltage 

is present at the damper motor.

2. Check for any obstruction inside the damper. If the

electric ventilation damper fails to operate after 
performing these checks, it must be replaced.

7.8 Condensate Pump Kit

An optional condensate pump kit is available from the factory
for use with the UA-135H. Condensate is automatically
pumped to a remote location when the water level in the
pump's reservoir rises to close the float switch. The pump
also contains a safety float switch. The white leads from this
switch extend from beneath the pump cover. This switch
should be installed in series with the field wire that connects
the blue (#5) lead from the UA-135H to the blue (#5) lead on
the control panel. If the pump fails, this switch opens the
compressor control circuit and stops water production before
the reservoir overflows. The UA-135H will continue to venti-
late or circulate air as normal, but will not dehumidify until
this switch closes.

Figure 2:

Condensate pump.

CAUTION

Содержание FOCUS Ultra-Aire 135H

Страница 1: ...midification The highly efficient Ultra Aire APD UA 135H dehumidifier utilizes refrigeration to cool the incoming air stream below its dew point This cooled and drier air is used to pre cool the incoming air stream resulting in up to a 200 percent increase in overall efficiency After the pre cooling stage the processed air is reheated by passing through the condenser coil The heat removed by the e...

Страница 2: ... room The ductwork of the existing heating system can be used to supply air to the home 2 Registrations The Ultra Aire 135H P N 4025080 conforms to UL STD 1995 Certified to CAN CSA STD C22 2 No 236 3 Specifications Model UA 135H Air Purifying Dehumidifier Electrical 110 120 VAC 12 Amps 60 Hz grounded Capacity 135 pints day 80 F 60 RH Operating Temp 55 F min 100 F max Air Flow 355 CFM without exter...

Страница 3: ...troller WITHOUT Fresh Air Refer to Sections 5 through Section 5 2G only 4 2 Humidity Control Adjustment Set the humidity control to the desired humidity level for the home Turning the knob clockwise results in a drier setting See the back of the control panel cover for set points The dehumidifier will run continuously until the relative humidity RH is reduced to the humidity control dial setting S...

Страница 4: ... Now with the ventilation start time set press the I O button The word OFF should appear to the right of the time and the number 1 should remain in the lower right hand corner of the display The 1 and OFF signify the turn off time for the first program Set the turn off time using the 1 7 h and m buttons in the same way as described above and continue on to the second through sixth programs When se...

Страница 5: ...r time 3 Push CLOCK button again The day display will flash Use the buttons to select the proper day 4 Push CLOCK button again The AM PM display will flash Verify AM PM setting is correct 5 Push CLOCK button again or wait a few seconds for the display to stop flashing The time is now set 5 2E Setting Relative Humidity Setpoint The relative humidity setpoint operates the dehumidifier function of th...

Страница 6: ... will be open and the fan of the system will be operating in order to introduce fresh air into the space Use this mode for continuous fresh air ventilation The fan is always on when the damper is open When in off mode the damper will not open and the sys tem will not ventilate When in the program mode the control will operate the damper and fan ventilate according to the programmed ventilation sch...

Страница 7: ...t exchange coils inside the unit could become clogged and require disassembly to clean Filter non compliance invalidates the product warranty 6 2 High Efficiency Air Filter An optional high efficiency pleated microglass paper filter is available for the UA 135H This filter is rated as 90 95 efficient by the ASHRAE Dust Spot test method 52 76 The high efficiency pleated microglass paper filter shou...

Страница 8: ...mpeller fan does not run with ventilation timer activated 1 Defective ventilation timer 2 Time not correct on ventilation timer 3 Ventilation timer set to manual switched OFF 4 Defective fan switch Evaporator coil frosted continuously low dehumidifying capacity 1 Defrost thermostat loose or defective 2 Low refrigerant charge 3 Dirty air filter s or airflow restricted 4 Excessively restrictive duct...

Страница 9: ...move the charge and weigh in the refrigerant quantity listed on the nameplate Operate the system to verify performance 7 7 Electric Ventilation Damper The electric ventilation damper is controlled by the ventilation timer The damper will open when the ventilation timer is activated to allow fresh air into the structure through the 6 diameter fresh air inlet duct The electric ventilation damper wil...

Страница 10: ...care and proper return packaging LIMITATIONS AND EXCLUSIONS This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC s reasonable control If any Ultra Aire 135H part is repaired or replaced the new...

Страница 11: ...n 3 4024539 DEH 2000 Digital Controller 4 4025287 Filter Box 5 4022220 Condensate Pump Kit External 6 4024377 Optional External Insulation Kit not shown 7 4024369 2 x20 x24 Filter not shown 8 4024370 4 x20 x24 Filter not shown 9 4020646 10 Backdraft Damper not shown 10 4025463 Stand Kit not shown Figure 1 Ventilation Timer Humidity Control Figure 2 Humidity Fan Control Figure 5 Condensate Pump Fig...

Страница 12: ...22 1447 Web www thermastor com Email sales thermastor com Information in this document is subject to change without notice No part of this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2004 Therma Stor LLC All rights reserved ...

Отзывы: