Quest 185 Cool 

Installation, Operation and Maintenance Instructions

21

www.QuestHydro.com

[email protected]

Low dehumidification capacity (evaporator is frosted continuously). Dehumidification is being called for.
1.  Defrost thermostat loose or defective.
2. Low refrigerant charge.
3.  Dirty air filter(s) or air flow restricted.
4.  Excessively restrictive ducting connected to unit.
No ventilation. Ventilation is being called for.
1.  Loose connection in ventilation control circuit.
2.  Loose connection in damper power circuit.
3.  Defective fresh air damper.
Dehumidifier removes some water, but not as much as expected.

 

1.  Air temperature and/or humidity have dropped. 
2.  Humidity meter and or thermometer used are out of calibration.
3.  Unit has entered defrost cycle. 
4.  Dirty air filter(s) or air flow is restricted. 
5.  Defective defrost thermostat. 
6. Low refrigerant charge. 
7.  Air leak such as loose cover or ducting leaks. 
8. Defective compressor. 
9. Restrictive ducting.

Troubleshooting Procedure for Control Related Issues.

This method of diagnosis will test the 3 main components of the control circuit individually to indicate any potential 

problems. This is to be used when the control will not activate the main unit.
1.  Detach field control wiring connections from the pigtails on the main unit.
2.  Connect the yellow and green wire pigtails  

together; only the fan should run. Disconnect the wires.

3.  Connect the yellow and blue wires pigtails together; fan and compressor should run.  

Disconnect the wires.

4.  If this test works, the main unit is working  

correctly from a control standpoint. 

5.  Reconnect field control wiring to the pigtails on the main unit.
6.  Remove the control panel cover and detach the field wiring from the control connections. 
7.  Connect the yellow and green wires together; only the fan should run. Disconnect the wires.
8.  Connect the yellow and blue wires together; fan and compressor should run. Disconnect the wires.
9.  If this test works, then the field control wiring is ok.
10.  If the problem persists, then the control is most likely faulty.

  

Содержание 4037391

Страница 1: ...is provided to acquaint you with the dehumidifier so that installation operation and maintenance can proceed successfully Ultimate satisfaction depends on the quality of installation and a thorough u...

Страница 2: ...Set Installation 9 5 4 Brazing the Line Set 11 5 5 Leak Test Line Set and Dehumidifier 13 5 6 Evacuating the Line Set and the Dehumidifier 14 5 7 Charging the System 15 6 Control Options 16 6 1 On Bo...

Страница 3: ...outlet that is a GROUND FAULT INTERRUPT protected circuit DO NOT use the device as a bench or table DO NOT place the device directly on structural members Provide vibration isolation in order to mini...

Страница 4: ...ifier Quest 185 Cool Condensing Unit Quest 185 Cool Installation Instructions Quest 185 Cool Leveling Feet 4 Specifications 80 F 60 RH Dehumidifier 4037391 Power Watts 160 Supply voltage 110 120 VAC 1...

Страница 5: ...5 Cool Dehumidifier as a bench or table DO NOT place the Quest 185 Cool Dehumidifier directly on structural members Provide vibration isolation in order to minimize operational vibration and or noise...

Страница 6: ...ontact or be connected to a high voltage circuit The control terminals and remote control are labeled and numbered to prevent confusion Be sure to consult the electrical schematic in this manual or in...

Страница 7: ...e the condensing unit at least 1 above ground level Place the condensing unit as close as possible to the dehumidifier to minimize the length of the connecting lines The maximum line set length is 50...

Страница 8: ...ensing unit The power wiring must have a Minimum Circuit Ampacity of 20A and be run within a rain tight conduit The con densing unit must be grounded as required by applicable code s Field Wiring the...

Страница 9: ...ER WALL STUD STRAP LIQUID LINE TO VAPOR LINE LIQUID LINE VAPOR LINE WRAPPED IN ARMAFLEX NON CORROSIVE METAL SLEEVE VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE CALK PVC PIPE FIBERGLASS INSULATION OUTS...

Страница 10: ...ine to prevent water condensation on the gas line Flush the lines with an inert gas before and or during brazing to prevent oxidation inside the lines Release the inert gas holding charge and remove t...

Страница 11: ...re tightening Allow braze joint to cool before removing the wet rag from service valve Temperatures above 250 can damage seals Use silver alloy brazing rods with 5 minimum silver alloy for copper to c...

Страница 12: ...ttings included with the condensing unit onto the line set if necessary 3 Swage the liquid and gas lines if necessary to fit onto the line stubs with the flare fittings 4 Remove service valve caps and...

Страница 13: ...le of sensing HFC refrigerant WARNING Refrigerant can be harmful if it is inhaled Refrigerant must be used and recovered responsibly Failure to follow this warning may result in personal injury or dea...

Страница 14: ...e side of the manifold gage set to the liquid line stub service port 6 Connect a vacuum pump to the center port on the manifold gage set 7 Open the valve core removal tool valves 8 Open the high and l...

Страница 15: ...ired 2 Connect a cylinder of HFC 410A refrigerant to the center port of the manifold gage set Position the HF C410A refrigerant cylinder to deliver liquid only 3 Open the valve on the HFC 410A cylinde...

Страница 16: ...ports of the liquid and gas line stubs finger tight then tighten an additional 1 6 turn Check the service port caps for leakage reinstall if necessary 6 Control Options The Quest 185 Cool Dehumidifier...

Страница 17: ...sformer neutral side common with red On board dehumidistat must be set to off otherwise the dehumidifier will run at the lowest setpoint between the dehumidistat and external control Between the COM D...

Страница 18: ...lean Filter non compliance invalidates the product warranty COM FAN 24V DEHU DMPR COM FAN 24V DEHU DMPR 24VAC COMP FAN ONEYWELL REMOTE HUMIDISTAT WIRING DIAGRAM QUEST DEH 3000R CONTROL WIRING DIAGRAM...

Страница 19: ...unit read it before any repair is initiated If a warranty repair is required call the factory first at 1 877 420 1330 for warranty claim authorization and technical assistance 8 2 Refrigerant Chargin...

Страница 20: ...or control wiring 4 Defective compressor relay 5 Defective control transformer Compressor is not running Dehumidification is being called for Fan is running 1 Defective compressor run capacitor 2 Loos...

Страница 21: ...ctive compressor 9 Restrictive ducting Troubleshooting Procedure for Control Related Issues This method of diagnosis will test the 3 main components of the control circuit individually to indicate any...

Страница 22: ...If compressor is running and continues to run after about 15 minutes you should feel a slight increase in air tem perature being discharged out of the discharge air side of the unit 6 If so depending...

Страница 23: ...DEHU RELAY COIL BLOWER RELAY COIL DEFROST T STAT L PRESS SWITCH RUN CAP 24VAC SIGNAL FROM DEHU NC NO YEL 6 BLU 7 GRN 5 PNK 3 WHT 4 RED 1 YEL 2 BLK 9 BLK 8 BLK BLK BLK 3 WHT 5 BLK 2 BLU 2 115V 24V COM...

Страница 24: ...lation Operation and Maintenance Instructions 24 www QuestHydro com info QuestHydro com 10 Optional Accessories PART NO DESCRIPTION 4028531 DEH 3000R Control with remote 4021475 MERV 11 Filter 16 x20...

Страница 25: ...warranty does not cover any costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by...

Отзывы: