Surface-mounted installation

A back box 110 A is available for surface mounted installation 

(see accessories).

7.  Switching

The motion detectors can be operated as a master in indivi-

dual switching. With parallel switching of the light outputs (L‘), 

it must be ensured that all detectors connected in parallel are 

connected to the same phase.

Individual switching

In individual switching, the presence detector, as Master, 

detects presence and brightness and controls lighting.

L’

8.  Settings

The presence detector theRonda S does not have a potentio-

meter. The presence detectors are supplied with basic settings 

ready for operation. The specifi cations are guidance values. 

Management remote control "SendoPro 868-A", service 

remote control "theSenda P" and app remote control "the-

Senda B" (with "theSenda Plug" app) are available for start-

up. They allow the remote adjustment of the setting values.

Parameters and control commands via remote 

control

The following parameters can be checked or changed via 

the remote control for support during start-up as well as 

servicing:

Parameter

Description

Can be 

queried by 

SendoPro

868-A/

theSenda B 

(app)

Can be 

changed by 

SendoPro

868-A/

theSenda B 

(app)

Can be 

changed by 

theSenda P

Brightness set-

point value A

Value range in lux

x

x

x

Measurement off

x

x

x

Time delay A

Value ranges in 

seconds/minutes

x

x

Pulse

x

x

Short presence A On/Off

x

Confi guration 

type

auto/man

x

x

x

Control input S

Auto/switch/push 

button S/push 

button O

x

Detection 

sensitivity (PIR)

Value range in 

increments

x

x

Group address

All/I/II/III

x

x

LED display 

motion

Off/On

x

The parameters are sent to the presence detector via infra-

red by using the "SendoPro 868-A" management remote con-

trol, the "theSenda P" service remote control, or "theSenda B" 

app remote control (with "theSenda Plug" app). Changed 

parameters are immediately applied and used by the detector.

With the "SendoPro 868-A" management remote control, as 

well as with "theSenda B" app remote control (with "the-

Senda Plug" app), parameters can be queried by sending 

values level-by-level to the detector. If the sent value is below 

the set parameter, the LED illuminates briefl y. If the sent value 

is equal to or above the set parameter, the LED fl ickers for 2 

seconds.

The following control commands can be triggered 

with the remote control:

Control 

command

Description

Can be trig-

gered by 

SendoPro

868-A/

theSenda B 

(app)

Can be 

trigge-

red by 

the-

Senda P

Teach-in channel 

A

Activation

x

x

Switching light

Lighting group can be switched 

on and off.

x

x

Presence test 

On/Off

x

x

Restart

Restart detector

x

x

Factory settings

Set all parameters and settings 

to factory setting.

x

Brightness setpoint channel A light

Brightness setpoint A defi nes the minimum desired bright-

ness. The currently prevailing brightness is measured under-

neath the presence detector. If the prevailing brightness is 

below the setpoint value, the light is switched on when a 

presence is detected (in confi guration type fully automatic 

device).

Value range

Adjustable values "SendoPro 868-A"/"theSenda B" (app) 30–3000 lux

Adjustable values "theSenda P"

30, 300, 500, 

800 lux

Содержание theRonda S360-100 UP WH

Страница 1: ...ation The presence detector is exclusively intended for the use as con tractually agreed between the manufacturer and the user Any other use is considered to be unacceptable The manufacturer does not...

Страница 2: ...m 50 m2 4 0 m 13 m2 4 0 m 13 m2 3 5 m 8 0 m 50 m2 4 0 m 13 m2 4 0 m 9 0 m 64 m2 4 0 m 13 m2 All figures are guidance values Brightness measurement The presence detector measures artificial light and...

Страница 3: ...S push button O x Detection sensitivity PIR Value range in increments x x Group address All I II III x x LED display motion Off On x The parameters are sent to the presence detector via infra red by...

Страница 4: ...nected to control input S Use light push button only with neutral conductor connector Value range Automatic detection of push button or switch A signal that is present for less than 0 7 s is detected...

Страница 5: ...set y y Teach in cannot be activated in test mode Test mode ends automatically after 10 min The detector restarts itself see switch on behaviour 10 Technical data Operating voltage 110 230 V AC 10 15...

Страница 6: ...ence detector The command is not valid Check the selected detector type or parameters on the SendoPro or in the app Fast flashing Error flashing The presence detector has found an error Lights up or f...

Страница 7: ...de en theSenda S Item no 9070911 Details www theben de en 11 Contact Theben HTS AG Im Langhag 7b 8307 Effretikon SWITZERLAND Phone 41 52 355 17 00 Fax 41 52 355 17 01 Hotline Phone 41 52 355 17 27 hot...

Отзывы: