Theben theRonda S360-100 UP WH Скачать руководство пользователя страница 5

5

Factory settings

The theRonda S360-100 UP presence detector is delivered 

with the following parameter values:

Parameter

Value

Brightness setpoint value A

300 lux

Time delay A

10 min

Short presence A

On

Configuration type

auto

Control input S

auto

Detection sensitivity (PIR)

Increment 3

Group address

I

LED display motion

Off

9.  Start-up

Switch-on behaviour

Every time the power supply is switched on, the presence 

detector runs through two phases that are shown by an LED:

1.  Start-up phase (30 s)

 

The red LED flashes at one second intervals, both switch 

contacts are closed (light on).

 

The detector does not respond to push button com-
mands and remote control commands.

 

When no one is present, the contact open after 30 s.

2.  Operation

The detector is ready for operation (LED off).

Presence test 

Presence test mode is used to test presence detection and 

wiring. Presence test mode can be activated with "SendoPro 

868-A" management remote control, with "theSenda B" app 

remote control (with "theSenda Plug" app) and with "the-

Senda P" installation remote control.

Setting the presence test mode via remote control

The detector goes directly into test mode when the test mode 

is set via the remote control:

Every movement is indicated by the LED.

 

When movement occurs, the light switch contact close.

¾

y

When no one is present, the light switch contact opens 

after 10 s.

¾

y

Brightness measurement deactivated, detector does 

not react to brightness.

¾

y

The detector reacts as in configuration type fully auto

-

matic device, even if semi-automatic is set.

¾

y

Teach-in cannot be activated in test mode. 

 

Test mode ends automatically after 10 min. The detector 
restarts itself (see switch-on behaviour).

10. Technical data

Operating voltage

110–230 V AC +10%/–15%

Frequency

50–60 Hz

Upstream protection device:

13 A

Power consumption

approx. 0.1 W

Type of installation

Ceiling installation; flush/surface 

mounted or ceiling installation

Recommended installation height

2.0–3.0 m/max. 4 m

Minimum height

> 1.7 m

Detection area 

horizontal

360°

Maximum range

Ø 4 m (Mh. 3 m)/13 m² seated

Ø 4 m (Mh. 3 m)/13 m² radially 

moving

Ø 8m (Mh. 3m)/50 m² tangentially 

moving

Setting range brightness setpoint 

value

30–3000 lux

Light time delay

10 s–60 min/pulse

Presence time delay

10 s–120 min

Switch-on delay "Presence"

0 s–10 min

Channel A light

Relay 230 V/10 A, µ-contact

Max. switching capacity  

cos 

j

 1 resistive

2300 W    (max 10 A)

Max. switching capacity 

cos 

j

 0.5

1150 VA   

Max. switching capacity LED

LED lamp < 2 W

LED lamp > 2 W

see manufacturer concerning cos 

60 W

180 W

Guidance values max. switch-on 

current

800 A/200 µs

Maximum number EBs T5/T8

16x 54/58 W, 24x 35/36 W

8x 2x 54/58 W

12x 2x 35/36 W 

Connection type

Screw terminals

Max. cable cross-section

Max. 2 x 2.5 mm²

Size of flush-mounted box

Size 1, Ø 55 mm (NIS, PMI)

Protection rating

IP 20 (IP 54 installed)

Ambient temperature

–15 °C ... +50 °C

CE Declaration of Conformity

This device conforms to the safety 

regulations of the EMC directive 

2014/30/EU and of directive 

2014/35/EU. 

Product overview

Type of 

installa-

tion

Channel Operating 

voltage

Colour

Type

Item 

number

Ceiling 

installa-

tion

Light 

110–

230 V AC

White

theRonda  

S360-100 UP WH

2080520

Grey

theRonda  

S360-100 UP GR

2080521

Special colour 

in accordance 

with customer 

information

theRonda  

S360-100 UP SF

2080523

Содержание theRonda S360-100 UP WH

Страница 1: ...ation The presence detector is exclusively intended for the use as con tractually agreed between the manufacturer and the user Any other use is considered to be unacceptable The manufacturer does not...

Страница 2: ...m 50 m2 4 0 m 13 m2 4 0 m 13 m2 3 5 m 8 0 m 50 m2 4 0 m 13 m2 4 0 m 9 0 m 64 m2 4 0 m 13 m2 All figures are guidance values Brightness measurement The presence detector measures artificial light and...

Страница 3: ...S push button O x Detection sensitivity PIR Value range in increments x x Group address All I II III x x LED display motion Off On x The parameters are sent to the presence detector via infra red by...

Страница 4: ...nected to control input S Use light push button only with neutral conductor connector Value range Automatic detection of push button or switch A signal that is present for less than 0 7 s is detected...

Страница 5: ...set y y Teach in cannot be activated in test mode Test mode ends automatically after 10 min The detector restarts itself see switch on behaviour 10 Technical data Operating voltage 110 230 V AC 10 15...

Страница 6: ...ence detector The command is not valid Check the selected detector type or parameters on the SendoPro or in the app Fast flashing Error flashing The presence detector has found an error Lights up or f...

Страница 7: ...de en theSenda S Item no 9070911 Details www theben de en 11 Contact Theben HTS AG Im Langhag 7b 8307 Effretikon SWITZERLAND Phone 41 52 355 17 00 Fax 41 52 355 17 01 Hotline Phone 41 52 355 17 27 hot...

Отзывы: