![Theben theRonda S360-100 UP WH Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/theben/theronda-s360-100-up-wh/theronda-s360-100-up-wh_manual_1101213005.webp)
5
Factory settings
The theRonda S360-100 UP presence detector is delivered
with the following parameter values:
Parameter
Value
Brightness setpoint value A
300 lux
Time delay A
10 min
Short presence A
On
Configuration type
auto
Control input S
auto
Detection sensitivity (PIR)
Increment 3
Group address
I
LED display motion
Off
9. Start-up
Switch-on behaviour
Every time the power supply is switched on, the presence
detector runs through two phases that are shown by an LED:
1. Start-up phase (30 s)
•
The red LED flashes at one second intervals, both switch
contacts are closed (light on).
•
The detector does not respond to push button com-
mands and remote control commands.
•
When no one is present, the contact open after 30 s.
2. Operation
The detector is ready for operation (LED off).
Presence test
Presence test mode is used to test presence detection and
wiring. Presence test mode can be activated with "SendoPro
868-A" management remote control, with "theSenda B" app
remote control (with "theSenda Plug" app) and with "the-
Senda P" installation remote control.
Setting the presence test mode via remote control
The detector goes directly into test mode when the test mode
is set via the remote control:
Every movement is indicated by the LED.
•
When movement occurs, the light switch contact close.
¾
y
When no one is present, the light switch contact opens
after 10 s.
¾
y
Brightness measurement deactivated, detector does
not react to brightness.
¾
y
The detector reacts as in configuration type fully auto
-
matic device, even if semi-automatic is set.
¾
y
Teach-in cannot be activated in test mode.
•
Test mode ends automatically after 10 min. The detector
restarts itself (see switch-on behaviour).
10. Technical data
Operating voltage
110–230 V AC +10%/–15%
Frequency
50–60 Hz
Upstream protection device:
13 A
Power consumption
approx. 0.1 W
Type of installation
Ceiling installation; flush/surface
mounted or ceiling installation
Recommended installation height
2.0–3.0 m/max. 4 m
Minimum height
> 1.7 m
Detection area
horizontal
360°
Maximum range
Ø 4 m (Mh. 3 m)/13 m² seated
Ø 4 m (Mh. 3 m)/13 m² radially
moving
Ø 8m (Mh. 3m)/50 m² tangentially
moving
Setting range brightness setpoint
value
30–3000 lux
Light time delay
10 s–60 min/pulse
Presence time delay
10 s–120 min
Switch-on delay "Presence"
0 s–10 min
Channel A light
Relay 230 V/10 A, µ-contact
Max. switching capacity
cos
j
1 resistive
2300 W (max 10 A)
Max. switching capacity
cos
j
0.5
1150 VA
Max. switching capacity LED
LED lamp < 2 W
LED lamp > 2 W
see manufacturer concerning cos
j
60 W
180 W
Guidance values max. switch-on
current
800 A/200 µs
Maximum number EBs T5/T8
16x 54/58 W, 24x 35/36 W
8x 2x 54/58 W
12x 2x 35/36 W
Connection type
Screw terminals
Max. cable cross-section
Max. 2 x 2.5 mm²
Size of flush-mounted box
Size 1, Ø 55 mm (NIS, PMI)
Protection rating
IP 20 (IP 54 installed)
Ambient temperature
–15 °C ... +50 °C
CE Declaration of Conformity
This device conforms to the safety
regulations of the EMC directive
2014/30/EU and of directive
2014/35/EU.
Product overview
Type of
installa-
tion
Channel Operating
voltage
Colour
Type
Item
number
Ceiling
installa-
tion
Light
110–
230 V AC
White
theRonda
S360-100 UP WH
2080520
Grey
theRonda
S360-100 UP GR
2080521
Special colour
in accordance
with customer
information
theRonda
S360-100 UP SF
2080523