background image

1

theRonda P360-100 M UP WH

2080020

theRonda P360-100 M UP GR 

2080021

307245

1103105201

Presence detector

EN

1.  Product characteristics

 

Passive infrared presence detector for ceiling installation

 

Circular detection area 360° to Ø 24 m (452 m

2

 

Restriction of detection area with cover clips

 

Automatic presence- and brightness-dependent control 
for lighting

 

Mixed light measurement suitable for fluorescent lamps 

(FL/PL/ESL), halogen/incandescent lamps and LEDs 

 

Channel A light: relay, 230 V

 

Choice of fully or semi-automatic operation

 

Brightness switching value configurable, teach-in 

function

 

Reduction of time delay when briefly present (short-term 

presence)

 

Connection option for push buttons or switches for 
manual switching with automatic detection of push 
button/switch

 

Pulse function for staircase light time switch

 

Time delay configurable

 

Detection sensitivity configurable

 

Ready for immediate use due to factory presetting

 

Test mode for checking function and detection area

 

Extension of detection area via master/slave or master/
master switching, a maximum of 10 detectors can be 
switched in parallel with each other

 

Ceiling installation in flush-mounted box

 

Ceiling installation possible with back box (optional)

 

User remote control theSenda S (optional)

 

Management remote control SendoPro (optional)

 

Installation remote control theSenda P (optional)

2.  Safety

Danger of death through electric shock or fire!

 Installation should only be carried out by a pro- 

    fessional electrician!

WARNING

 

Work on electrical systems may only be carried out by 
electricians or by instructed persons under the leader-
ship and supervision of an electrician in accordance with 
the technical regulations applying to electricity! 

 

Comply with the country-specific safety regulations for 

work on electrical systems! Ensure absence of voltage in 
the cable before installation!

 

The device is maintenance-free. If the device is opened 
or penetrated with any objects the guarantee lapses.

3.  Intended use

The presence detector is intended for interior installation. The 

presence detector is exclusively intended for the use as con-

tractually agreed between the manufacturer and the user. Any 

other use is considered to be unacceptable. The manufacturer 

does not accept liability for any resulting damages.

4.  Function

The presence detector is primarily used in entrance halls, 

garages, store rooms, offices and schools, as well as in homes, 

for easy and energy-efficient control of lighting. The switch 

contact „light“ switches lighting on with presence and insuf-

ficient brightness, and off with absence or sufficient bright

-

ness. The light can also be switched on/off manually using 

push buttons or switches.

Functional description

 Mixed light measurement 

 Presence detection

 Artificial light

 Push button for manual lighting control

 Incident daylight

Settings on theRonda P360-100

 Brightness set point value (lux)

 Lighting time delay 

 Mechanical safety lock

Light channel A 

Switching response is controlled by presence and brightness. 

The switch contact closes during darkness and when some-

one is present. It opens with a delay when there is brightness 

or when no one is present. 

Time delay

The time delay enables delayed switching off of lighting after 

the room is vacated. The time delay is adjustable in a range 

of 10 s to 60 min. If someone goes into an unoccupied room 

only briefly and leaves it within 30 seconds, then the light 

shuts off prematurely after 2 minutes (short-term presence).

Содержание theRonda P360-100 M UP WH

Страница 1: ...lectrician in accordance with the technical regulations applying to electricity Comply with the country specific safety regulations for work on electrical systems Ensure absence of voltage in the cabl...

Страница 2: ...reduced as temperatures increase Seated persons The details relate to smallest movements at table height approx 0 80 m Moving persons At installation heights of between 5 and 10 m the extent and dist...

Страница 3: ...ave parallel switching If the detection area covered by one presence detector is insufficient larger rooms then up to 10 detectors can be operated in parallel by connecting P terminals In the process...

Страница 4: ...min Classroom approx 10 min Work areas office meeting room approx 10 min Pulse Control staircase light time switch 0 5 s on 10 s off Parameters and control commands via remote control The following pa...

Страница 5: ...theSenda P man Button Control input S Control input S for manual switch on off of channel A light automatically detects push buttons or switches Several push buttons can be connected to control input...

Страница 6: ...AC 10 15 Frequency 50 60 Hz Upstream protection device 13 A Power consumption approx 0 1 W Type of installation Ceiling installation Flush surface mounted or ceiling installation Installation height...

Страница 7: ...test mode or LED display movement is activated The LED displays detection of movement Guarantee Theben HTS presence detectors are manufactured with the utmost care and using state of the art technolog...

Страница 8: ...act Theben HTS AG Im Langhag 7b 8307 Effretikon SWITZERLAND Phone 41 52 355 17 00 Fax 41 52 355 17 01 Hotline Phone 41 52 355 17 27 hotline theben hts ch www theben hts ch All countries except Switzer...

Отзывы: