1
theRonda P360-100 M UP WH
2080020
theRonda P360-100 M UP GR
2080021
307245
1103105201
Presence detector
EN
1. Product characteristics
•
Passive infrared presence detector for ceiling installation
•
Circular detection area 360° to Ø 24 m (452 m
2
)
•
Restriction of detection area with cover clips
•
Automatic presence- and brightness-dependent control
for lighting
•
Mixed light measurement suitable for fluorescent lamps
(FL/PL/ESL), halogen/incandescent lamps and LEDs
•
Channel A light: relay, 230 V
•
Choice of fully or semi-automatic operation
•
Brightness switching value configurable, teach-in
function
•
Reduction of time delay when briefly present (short-term
presence)
•
Connection option for push buttons or switches for
manual switching with automatic detection of push
button/switch
•
Pulse function for staircase light time switch
•
Time delay configurable
•
Detection sensitivity configurable
•
Ready for immediate use due to factory presetting
•
Test mode for checking function and detection area
•
Extension of detection area via master/slave or master/
master switching, a maximum of 10 detectors can be
switched in parallel with each other
•
Ceiling installation in flush-mounted box
•
Ceiling installation possible with back box (optional)
•
User remote control theSenda S (optional)
•
Management remote control SendoPro (optional)
•
Installation remote control theSenda P (optional)
2. Safety
Danger of death through electric shock or fire!
Installation should only be carried out by a pro-
fessional electrician!
WARNING
•
Work on electrical systems may only be carried out by
electricians or by instructed persons under the leader-
ship and supervision of an electrician in accordance with
the technical regulations applying to electricity!
•
Comply with the country-specific safety regulations for
work on electrical systems! Ensure absence of voltage in
the cable before installation!
•
The device is maintenance-free. If the device is opened
or penetrated with any objects the guarantee lapses.
3. Intended use
The presence detector is intended for interior installation. The
presence detector is exclusively intended for the use as con-
tractually agreed between the manufacturer and the user. Any
other use is considered to be unacceptable. The manufacturer
does not accept liability for any resulting damages.
4. Function
The presence detector is primarily used in entrance halls,
garages, store rooms, offices and schools, as well as in homes,
for easy and energy-efficient control of lighting. The switch
contact „light“ switches lighting on with presence and insuf-
ficient brightness, and off with absence or sufficient bright
-
ness. The light can also be switched on/off manually using
push buttons or switches.
Functional description
Mixed light measurement
Presence detection
Artificial light
Push button for manual lighting control
Incident daylight
Settings on theRonda P360-100
Brightness set point value (lux)
Lighting time delay
Mechanical safety lock
Light channel A
Switching response is controlled by presence and brightness.
The switch contact closes during darkness and when some-
one is present. It opens with a delay when there is brightness
or when no one is present.
Time delay
The time delay enables delayed switching off of lighting after
the room is vacated. The time delay is adjustable in a range
of 10 s to 60 min. If someone goes into an unoccupied room
only briefly and leaves it within 30 seconds, then the light
shuts off prematurely after 2 minutes (short-term presence).