8
We recommend the following procedure:
•
Place the lux meter on the work surface below the sensor
and note down the measured lux value.
•
Query „brightness actual value A“ with the «SendoPro
868-A» management remote control.
•
Calculating the room correction factor: „brightness actual
value A“ / lux value of lux meter.
•
Enter „room correction factor A“ with the «SendoPro
868-A» management remote control. Values between 0.05
and 2.0 are permitted. Entered values outside the permit-
ted range will automatically be set to the appropriate limit
value. The entered room correction factor will be applied
immediately.
!
The standard value is 0.3 and is suitable for most
applications.
Changes are only sensible in strongly deviating
situations.
Selection light measurement wide/spot
The light measurement can be switched over with the «Sen-
doPro 868-A» management remote control. „Wide“ and „spot“
can be selected. Description, see brightness measurement
section.
Time delay A
Value range
Adjustable values with "SendoPro 868-A" manage-
ment remote control
In the "theSenda P" installation remote control, the
following values are available
10 s - 60 min
10 s, 30 s, 60 s, 2
min, 10 min, 20 min,
60 min
Control for staircase light timer switch (0.5 s "on"
/ 10 s "off")
"SendoPro 868-A"
"theSenda P"
Pulse
Button
1
Short-term presence
The time delay of Channel A light can be switched off sooner
if a room is occupied only for a short time. (In fully automatic
device and semi-automatic device configuration type)
The time delay is applied according to the set time delay.
Off
If someone enters an unoccupied room and it is only occupied for
up to 30 seconds, the light will be switched off prematurely after
2 minutes.
On
Time delay H
The presence channel always switches, regardless of whether
configuration type is set to fully automatic device or semi-au-
tomatic. The set values remain unchanged. The relay contact
opens once the room is vacated after the set time delay
expires.
Value range
Adjustable values "SendoPro 868-A"
10 s ... 120 min
Adjustable values "theSenda P"
10 s, 30 s, 60 s, 2
min, 10 min, 20 min,
120 min
Switch-on delay H
The presence channel always switches, regardless of whether
configuration type is set to fully automatic device or semi-au-
tomatic. The relay contact only closes when someone is
present after expiry of the set switch-on delay.
Value range
Adjustable values
0 s, 30 s, 1 ...10 min
No switch-on delay (relay contact closes immedia-
tely when someone is present)
0 s
Adjustment possible only with "SendoPro 868-A".
Assignment channel A (relay operating mode)
With the parameter „Assignment channel A “ the operating
mode and behaviour of the light and presence relay can be
defined.
Assignment
channel A
Light relay
Presence relay
Functionality
L‘
Light channel A Presence channel
H
Light and presence
separately
L‘ + H
Light channel A Light channel A
Presence relay switches
as lighting channel
H
no function
Light channel A
Light relay deactivated,
presence relay switches
as lighting channel
The parameter „Assignment channel A“ can only be set with
the «SendoPro 868-A» management remote control. Factory
setting of „Assignment channel A“ is L‘.
Observe the performance specifications of the presence
relay.
Energy saving mode eco/eco plus
With the «SendoPro 868-A» management remote control, the
energy-saving behaviour can be set very simply. The selection
of “eco” stands for optimum switching behaviour, while “eco
plus” stands for maximum energy saving.
•
“eco”: The time delay adapts to the user behaviour in a
self-learning way. It does not drop below the set value.
•
“eco plus” : The set time delay remains unchanged (no
self-learning effect). Faster response to brightness detec-
tion than with "eco".
Configuration type
Fully automatic device: The lighting switches on and off auto-
matically. (due to presence/no presence and brightness)
auto
Semi-automatic: Switch on must always occur manually. Switch
off occurs automatically by the presence detector. (due to pre-
sence or brightness)
man
Control input S
Control input S for manual switch on/off of Channel A light
automatically detects push buttons or switches.
Several push buttons can be connected to control input S
Use light push button only with neutral conductor connector