6
switches at presence/absence.
Deactivation of the brightness measurement: set the poten-
tiometer to „on“.
The lux scale applies for rooms with average room design. It
is recommended that the room correction factor be adjusted
with the management remote control according to the instal-
lation location, light incidence, reflection characteristics of the
room and the furniture.
Potentiometer lighting time delay
The following guidance values have proved themselves in
practice and are recommended as settings:
•
Transit zones (no work area
approx. 5 min
•
Classroom
approx. 10 min
•
Work areas (office, living room)
approx. 10 min
•
When settings are between 2 - 30 mins the time delay
varies within this range in a self-learning way.
Setting values ≤ 2 min or ≥ 30 min remain fixed. Only
active with the setting "eco".
•
"Pulse": Control staircase light timer switch (0.5 s "on"
/ 10 s "off")
DIP switch fully/semi-automatic (auto/man)
Description of the function semi-automatic or fully automatic,
see function description:
•
"auto": fully automatic: the lighting switches on and off
automatically.
•
"man": semi-automatic: switching on always has to be
completed manually. Switching off occurs automatically.
DIP switch staircase light function (room/corridor)
For description of the staircase light function, see function
description:
•
"room" : manual switching on and off possible
•
“corridor”: detector is used as staircase light timer
switch. Manual switch off is no longer possible
DIP switch energy saving behaviour (eco/eco plus)
Selection of “eco” for optimal switching behaviour or “eco
plus” for maximum energy saving.
•
“eco”: The time delay adapts to the user behaviour in a
self-learning way.
It does not drop below the set value.
•
“eco plus” : The set time delay remains unchanged (no
self-learning effect). Faster response to brightness
detection than with „eco“.
DIP switch short-term presence (On/Off)
For description of short-term presence, see function
description:
•
„2 min“ short-term presence is switched on
•
„
“ Short-term presence is switched off.
Settings of switch contact presence
Potentiometer presence time delay
The contact closes if people are present and opens when the
room is vacated after the time delay expires. The set values
remain unchanged (no self-learning effect).
Potentiometer presence switch-on delay
•
The contact only closes when someone is present after
expiry of the switch-on delay
•
0 = contact closes immediately if people are present
•
"Room monitoring": contact closes only when a sig-
nificant movement occurs (high false alarm safety).
The switch-on delay is deactivated.
Parameters and control commands via remote
control
The following parameters can be queried or changed via
the remote control for support during installation as well as
servicing: