7
Parameter
Description
Can be
queried
SendoPro
868-A
Can be
changed
SendoPro
868-A
Can be
changed
theSenda
P
Brightness
switching
value A
Value range in lux
x
x
x
Measurement off
x
x
x
Room correc-
tion factor A
Room correction
factor
x
Brightness
actual value A
Query brightness
actual value
x
Light
measurement
Selection: wide / spot x
x
Time delay A
Value ranges in
seconds / minutes
x
x
Pulse
x
x
Short presence
A
Short-term presence:
On/Off
x
Time delay H
Value ranges in
seconds / minutes
x
x
Switch-on
delay H
Value ranges in
seconds / minutes
x
Assignment
channel A
Assignment function
relay H: L‘ / L‘ + H / H
x
Energy saving
mode
Selection: eco / eco
plus
x
x
Configuration
type
Selection: auto / man x
x
x
Staircase light
function
Selection: Off / On
x
Control input S
Auto / switch / push
button S / push
button O
x
Detection
sensitivity
Detection
Sensitivity
(PIR): value range in
Increments
x
x
Monitoring
sensitivity
reduction
Room monitoring
sensitivity: value
range in
Increments
x
Group address
Selection: I / II / III
/ all
x
Scene 1
Off / On
x
Scene 2
Off / On
x
LED display
motion
Off / On
x
The parameters are sent to the presence detector with the
"SendoPro 868-A" management remote control or with "the-
Senda P" installation remote control via infra-red. Changed
parameters are immediately applied and used by the detector.
With the "SendoPro 868-A" management remote control,
parameters can be queried by sending values level-by-level
to the detector. If the sent value is below the set parameter,
the LED illuminates briefly. If the sent value is equal or above
the set parameter, the LED flickers for 2 seconds.
The following control commands can be triggered
with the remote control:
Control
command
Description
Can be
triggered
SendoPro
868-A
Can be
trigge-
red the-
Senda P
Teach-in chan-
nel A
Activation
x
x
Switching light
Lighting group can be switched
on and off.
x
x
Control
command
Description
Can be
triggered
SendoPro
868-A
Can be
trigge-
red the-
Senda P
Presence test
Off / On
x
x
Light test
Off / On
x
Restart
Restart detector
x
x
Local settings
Detector assumes the set-
tings of the DIP switch and all
potentiometers
x
Factory
settings
Set all parameters and settings
to factory setting.
x
Brightness switching value A
The brightness switching value defines the minimum desired
brightness. The currently prevailing brightness is measured
below the presence detector. If the prevailing brightness
is below the switching value, the light switches on when a
presence is detected (in configuration type fully automatic
device).
Value range
Lux values with "SendoPro 868-A" management remote
control
In the installation remote control "theSenda P", the
following values are available
(The currently measured brightness value (Lux) can
be adopted with the "SendoPro 868-A" management
remote control, with the teach-in control command or
with the “theSenda P” installation remote control via the
teach-in button.)
Values outside the permitted range will automatically be
set to the appropriate limit value.
5 - 3000 lux
5, 10, 15, 300,
500, 800 lux
- Deactivating the brightness measurement (the bright-
ness has no influence)
- The light channels only switch according to presence/
absence.
Possible with "SendoPro 868-A" management remote
control or "theSenda P" installation remote control.
Measurement
off
Button
Room correction factor A
The room correction factor is a measurement for the diffe-
rence of the brightness measurement on the ceiling and the
work area. The brightness measurement value at the ceiling
is influenced by the installation location, incidence of light,
position of the sun, weather conditions, the reflection proper-
ties of the room, and the furniture.
With the room correction factor, the measured brightness
value of light channel A is adjusted to the conditions in the
room and in this way can be matched to the lux meter value
measured at the surface beneath the presence detector.
Room correction factor = Brightness value at the ceiling /
brightness value at the working surface