background image

1

thePassa P360-101 UP WH

2010300

thePassa P360-101 UP GR 

2010301

307385

1103092701

Presence detectors

EN

1.  Product characteristics

 

Passive infrared presence detector for ceiling installation

 

Rectangular detection area of 360°, up to  
30 m x 5 m (150 m

2

)  

 

2 separate detection zones

 

Restriction of detection area with cover clips

 

Automatic presence- and brightness-dependent control 
for lighting and HVAC

 

Mixed light measurement suitable for fluorescent lamps 

(FL/PL/ESL), halogen/incandescent lamps and LEDs

 

Channel A light: relay, 230 V

 

Fully or semi-automatic operation, switchable

 

Brightness setpoint adjustable, teach-in function

 

Reduction of time delay when present briefly (short-term 

presence)

 

Connection option for push buttons or switches for 
manual switching with automatic detection of push 
button/switch

 

Staircase light function

 

Pulse function for staircase light timer switch

 

Channel H, presence: relay, floating e.g. for HVAC control

 

Switch-on delay and time delay configurable

 

Detection sensitivity configurable

 

Ready for immediate use due to factory presetting

 

Test mode for checking function and detection area

 

Extension of detection area via Master/Slave or Master/
Master switching, a maximum of 10 detectors can be 
switched in parallel with each other

 

Ceiling installation in flush-mounted box

 

Surface mounting on ceilings possible with back box 
(option)

 

User remote control “theSenda S” (option)

 

Management remote control "SendoPro" (option)

 

Installation remote control "theSenda P" (option)

 

App remote control "theSenda B" (option) and corres-
ponding app "theSenda Plug" (iOS/Android)

2.  Safety

Danger of death through electric shock or fire!

¾

¾

Installation should only be carried out by a 

qualified electrician!

WARNING

 

Work on electrical systems may only be carried out by 

qualified electricians or by instructed persons under the 
guidance and supervision of a qualified electrician in 

accordance with the technical regulations applying to 

electricity! 

 

Comply with the country-specific safety regulations for 
work on electrical systems! Ensure absence of voltage in 
the cable before installation!

 

The device is maintenance-free. If the device is opened 
or penetrated, the guarantee lapses.

3.  Proper use

The presence detector is intended for indoor installation. The 

presence detector is exclusively intended for the use as con-

tractually agreed between the manufacturer and the user. Any 

other use is considered to be unacceptable. The manufacturer 

does not accept liability for any resulting damages.

4.  Function

The presence detector is primarily used in passage areas, 

staircases, garages, basements and warehouses for conveni-

ent and energy-efficient control of lighting as well as HVAC. 

The switch contact "light" switches lighting on with presence 

and insufficient brightness, and off with absence or sufficient 

brightness. The light can also be switched on/off manually 

using push buttons or switches.

The "Presence" switch contact controls heating, ventilation 

and air conditioning systems. The contact closes when some

-

one is present, a switch-on delay permits delayed switch on.

Function description

 Mixed light measurement 

 Presence detection

 Artificial light

 Push button for manual lighting control

 Incident daylight

Содержание thePassa P360-101 UP WH

Страница 1: ... control theSenda B option and corres ponding app theSenda Plug iOS Android 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qualified electrician in accordance with the techni...

Страница 2: ...ple are present or it is dark Channel H presence Channel H presence is used for HVAC control The switching response of the floating contact is influenced only by pre sence and not by brightness If the contact is closed the time delay will be restarted at every movement Push buttons or switches do not influence the contact Switch on delay The switch on delay prevents instantaneous switching on The ...

Страница 3: ...ighting directly below the detector If the brightness measurement is deactivated chan nel A light only switches depending on presence brightness setpoint value set to on via potentiometer or set to mea surement off via remote control 1 8 m Suitable lamps The presence detector is designed for the operation of fluore scent compact fluorescent halogen and incandescent lamps as well as LEDs The maximu...

Страница 4: ... L Light measurement only with the Master Parameters are only set on the Master Switch up to 10 detectors in parallel Use the phase with the same phase for all detectors Master thePassa P360 101 UP Slave thePassa P360 Slave UP Master Master parallel switching for several lighting groups Several Masters can be used in a parallel switching Each Master controls its lighting group according to its own...

Страница 5: ... only closes when someone is present after expiry of the switch on delay 0 contact closes immediately if people are present Parameters and control commands via remote control The following parameters can be checked or changed via the remote control for support during start up as well as servicing Parameter Description Can be que ried by SendoPro 868 A theSenda B app Can be chan ged by SendoPro 868...

Страница 6: ... the furniture With the room correction factor the brightness measurement value of lighting channel A is adjusted to the conditions in the room and in this way can be matched to the lux meter value measured at the surface beneath the presence detector Room correction factor Brightness value at the ceiling brightness value at the working surface Using management SendoPro 868 A remote control and lu...

Страница 7: ...stable values 0 s no switch on delay 30 s 1 10 min Configuration type Fully automatic device The lighting is switched on and off automatically Due to presence absence and brightness SendoPro 868 A theSenda B app auto theSenda P Button A Semi automatic Lights must always be switched on manually Switching off occurs automatically by the presence detector due to absence or brightness SendoPro 868 A t...

Страница 8: ...ment occurs the light and presence switch contacts close y y When no one is present the light switch contact opens after 10 s y y Brightness measurement deactivated detector does not react to brightness y y The detector reacts as in configuration type fully auto matic device even if semi automatic is set y y Teach in cannot be activated in test mode y y Test mode ends automatically after 10 min Th...

Страница 9: ...e Flickering for 2 s The command sent from the remote control via infrared was accepted by the presence detector Lighting up briefly The command sent from the remote control via infrared was rejected by the presence detector The command is not valid Check the selected detector type or parameters on the SendoPro or in the app Fast flashing Error flashing The presence detector has found an error Fli...

Страница 10: ...Details www theben de en theSenda B Item no 9070985 Details www theben de en theSenda S Item no 9070911 Details www theben de en 12 Contact Theben HTS AG Im Langhag 7b 8307 Effretikon SWITZERLAND Phone 41 52 355 17 00 Fax 41 52 355 17 01 Hotline Phone 41 52 355 17 27 hotline theben hts ch www theben hts ch All countries except Switzerland Theben AG Hohenbergstraße 32 72401 Haigerloch GERMANY Tel 4...