MIX 2 series RMG 4 U / RME 4 U actuators
Continuation:
Designation
Values
Description
Parameter for threshold object
Counter value 0..255
Lower threshold
1..254
Default value = 127
Desired threshold.
Example of
NO contact
with response
as
switch object = 1
:
Switches on when:
Object value > threshold
Switches off when:
Object value < threshold - hysteresis
Hysteresis
1..254
Default value = 5
The hysteresis prevents frequent change
overs after small fluctuations in
readings.
Parameter for threshold object
Counter value 0..65535
Lower threshold
1..65534
Default value = 1000
Desired threshold.
Example of
NO contact
with response
as
switch object = 1
:
Switches on when:
Object value > threshold
Switches off when:
Object value < threshold - hysteresis
Hysteresis
1..65534
Default value = 5
The hysteresis prevents frequent change
overs after small fluctuations in
readings.
Parameter for threshold object
EIS5 (e.g. CO
2
, brightness…)
Lower threshold
Format (-)0.00..99999
0.00..99999
Default value = 20
Desired threshold.
Example of
NO contact
with response
as
switch object = 1
:
Switches on when:
Object value > threshold
Switches off when:
Object value < threshold - hysteresis
Hysteresis
0.00..9999
0.00..9999
Default value = 1
The hysteresis prevents frequent change
overs after small fluctuations in
readings.
Updated: Apr-15 (Subject to changes) Page 31 of 50