MIX 2 series RMG 4 U / RME 4 U actuators
5.3.2.2
The "RMG 4 U basic module" parameter page
Designation
Values
Description
Relay switch delay
This parameter sets the minimum delay
between switching on 2 relays if several
are activated at the same time.
The shortest delay is achieved by using
the central switch object (object 242).
When switching on via individual
telegrams (1 telegram per channel), the
bus running times and the sequential
processing of commands cause an
additional delay.
This can help avoid high current peaks
when devices are switched on
simultaneously (e.g. with a number of
lighting strips).
None
There is no added delay.
60 ms
100 ms
200 ms
When a relay switches on, the next one
can only switch on after the set delay is
completed.
The switch-on delay between the first
and last relay is calculated according to
the following formula:
(Number of channels – 1) x delay
Example:
RMG 4 U and 60 ms:
= (4 channels – 1) * 60 ms = 180 ms
Channel C4 switches 180 ms after
C1.
Updated: Apr-15 (Subject to changes) Page 23 of 50