background image

MIX 2 series RMG 4 U / RME 4 U actuators

                                                                                                                               

 

 

 
Continuation: 

Designation 

Values 

Description 

Function of manual 
button (MIX2 series, 
order no. 493...) 

applies for 24 hours or until 

reset via object 

blocked 

applies until reset via object 

applies for 30 minutes or until 

reset via object 

applies for 1 hour or until reset 

via object 

applies for 2 hours or until reset 

via object 

applies for 4 hours or until reset 

via object 

applies for 8 hours or until reset 

via object 

applies for 12 hours or until 

reset via object 

Determines how long the device works 
manually and how this is ended. 
 
In manual mode, the channels can only 
be switched on and off via the buttons 
on the device. 
See also: object_78 
 
This parameter is used exclusively for 
MIX2 series devices. 

Manual operation of 
channels  
(MIX2 series, order no. 
493...) 

unblocked 

 

The channels can be operated via the 
buttons on the device. 

blocked 

No manual operation, the buttons on the 
device are blocked.. 

 

Updated: Apr-15 (Subject to changes)                                                                                                Page 22 of 50 

Содержание MIX 2 Series

Страница 1: ...MIX 2 series RMG 4 U RME 4 U actuators MIX 2 series actuators RMG 4 U RME 4 U RMG 4 U 4930223 RME 4 U 4930228 Updated Apr 15 Subject to changes Page 1 of 50 ...

Страница 2: ...e 27 5 3 2 6 The Pulse function parameter page 27 5 3 2 7 The Staircase light with forewarning function parameter page 28 5 3 2 8 The Flashing parameter page 29 5 3 2 9 The Threshold parameter page 30 5 3 2 10 The Block function parameter page 32 5 3 2 11 The Scenes parameter page 33 5 3 2 12 The Feedback parameter page 36 5 3 2 13 The Hour counter and service parameter page 37 5 3 2 14 The Link p...

Страница 3: ... Important parameter settings 46 7 Appendix 47 7 1 The scenes 47 7 1 1 Principle 47 7 1 2 Call up or save scenes 48 7 1 3 Teach in scenes without telegrams MIX2 devices ONLY 50 7 2 Conversion of percentages to hexadecimal and decimal values 50 Updated Apr 15 Subject to changes Page 3 of 50 ...

Страница 4: ...tuators is also possible without KNX bus module LED switching status indicator for each channel Manual operation on device even without bus voltage Adjustable features e g switching delayed switching pulse function Links type of contact NC contact NO contact and participation in central commands such as permanent On permanent Off central switching and save call up scene Switch functions e g On Off...

Страница 5: ...ble 1 Device type Ord No Designation Can be used with basic module in the MIX series in the MIX2 series MIX2 basic modules 493 RMG 4 I RMG 4 U RMG 8 S RMG 8 T DMG 2 T JMG 4 T HMG 6 T JMG 4 T 24V BMG 6 T MIX2 extensions 493 RME 4 I RME 4 U RME 8 S RME 8 T DME 2 T JME 4 T HME 6 T JME 4 T 24V BME 6 T no Yes MIX basic modules 491 BMG 6 DMG 2 S HMG 4 JMG 4 S RMG 4 S RMG 4 C load SMG 2 S MIX extensions ...

Страница 6: ...e A status LED displays the current switching status All bus telegrams are ignored with manual operation switched on manual button and the channels are exclusively to be operated via the buttons Mains voltage is required for the functioning of the buttons and LEDs bus voltage or bus module are not required Updated Apr 15 Subject to changes Page 6 of 50 ...

Страница 7: ...e output 240 V AC Switch output Floating Switching of different phases Possible Type of contact 16 A 3 A NO contact Resistive load 3680 W Incandescent and halogen lamp load 2000 W Fluorescent lamp load KVG parallel corrected 1300 W 140 μF Fluorescent lamp load KVG not corrected 2000 VA Fluorescent lamp load EB 1200 W Energy saving lamps 300 W LED lamps 2 W 55 W or 2 W 8 W 180 W Suitable for SELV Y...

Страница 8: ...anufacturer Theben AG Product family Output Product type RMG 4 U Program name MIX2 V1 8 The ETS database can be found on our downloads page www theben de en downloads_en Table 2 Number of communication objects 254 Number of group addresses 254 Number of associations 255 Updated Apr 15 Subject to changes Page 8 of 50 ...

Страница 9: ...Threshold 0 65535 2 byte 7 001 1 RMG 4 U channel C1 Logic input in AND gate 1 bit 1 001 Logic input in OR gate 1 bit 1 001 Logic input in XOR gate 1 bit 1 001 2 RMG 4 U channel C1 Block 1 bit 1 003 3 RMG 4 U channel C1 Call up save scenes 1 byte 18 001 4 RMG 4 U channel C1 Block scenes 1 1 bit 1 003 Enable scenes 1 5 RMG 4 U channel C1 Feedback On Off 1 bit 1 001 6 RMG 4 U channel C1 Time to next ...

Страница 10: ... Function Type DPT Flags C R W T 8 RMG 4 U channel C1 Switching with priority 2 bit 2 001 Reset service 1 bit 1 001 Reset operating hours 1 bit 1 001 9 Not used 10 198 Channels C2 C4 and extension modules See next table Updated Apr 15 Subject to changes Page 10 of 50 ...

Страница 11: ...7 37 8 18 28 38 1st EXTENSION RME 4 U C1 C2 C3 C4 80 90 100 110 81 91 101 111 82 92 102 112 83 93 103 113 84 94 104 114 85 95 105 115 86 96 106 116 87 97 107 117 88 98 108 118 2nd EXTENSION RME 4 U C1 C2 C3 C4 160 170 180 190 161 171 181 191 162 172 182 192 163 173 183 193 164 174 184 194 165 175 185 195 166 176 186 196 167 177 187 197 168 178 188 198 Updated Apr 15 Subject to changes Page 11 of 5...

Страница 12: ...001 243 Call up save central scenes RMG4x 8x DMG E2x JMG E4x SME2S 1 byte 18 001 244 Central safety 1 For JME 4 S 1 bit 1 001 245 Central safety 2 For JME 4 S 1 bit 1 001 246 Central safety 3 For JME 4 S 1 bit 1 001 247 Central up down For JME 4 S 1 bit 1 008 248 Central safety rain For JMG 4 T 1 bit 1 002 249 Central safety frost For JMG 4 T 1 bit 1 002 250 Version of bus coupling unit transmit 1...

Страница 13: ...ing the threshold Object type Percent DPT 5 001 Exceeding percentage value Object type Counter value 0 255 DPT 5 010 Any value in given numerical range Object type Counter value 0 65535 DPT 7 001 Object type EIS5 e g CO2 brightness DPT 9 xxx 2 byte floating point number Object 1 Logic input in AND gate in OR gate in XOR gate Only available if Link is activated Configuration options parameter page ...

Страница 14: ...he configuration As long as it is blocked scenes cannot be saved or called up Object 5 On Off feedback Reports the current channel status The status can also be fed back inverted depending on configuration Object 6 Time to next service operating hours feedback Only available if the hour counter function has been activated Configuration options parameter page Reports depending on selected Type of h...

Страница 15: ...ject 8 Channel status 0 as set by object 0 1 2 OFF 3 ON Depending on configuration Objects 78 158 238 Manual Only available for devices in the MIX2 series order number 493 Puts the relevant module in manual mode or sends the status of the manual operation Telegram Meaning Explanation 0 Auto All channels can be operated via the bus as well as via the buttons 1 Manual The channels can only be operat...

Страница 16: ...I RMG 8 S RME 8 S RMG 8 T RME 8 T RME 4 S C load DMG 2 T DME 2 S T SME 2 S Object 241 Central permanent OFF Central switch off function Enables simultaneous switch off of all channels basic and extension modules with a single telegram 0 No function 1 Permanent OFF Participation in this object can be set individually for each channel Configuration options parameter page IMPORTANT This object has th...

Страница 17: ...t object i e obj 0 10 20 etc were receiving a switch command Works on the following devices RMG 4 U RME 4 U RMG 4 I RME 4 I RMG 8 S RME 8 S RMG 8 T RME 8 T RME 4 S C load DMG 2 T DME 2 S T SME 2 S Object 243 Call up save central scenes Central object for using scenes This object can be used to save and subsequently call up scenes Works on the following devices RMG 4 I RME 4 I RMG 4 U RME 4 U RMG 8...

Страница 18: ...application version 1 8 Hardware version 25 Firmware version 25 Object 251 Version of basic module For diagnostic purposes only Only for basic modules in the MIX2 series order number 493 Sends the software version firmware of the basic module after reset or download Can also be read out via the ETS The version is issued as an ASCII character string Format Mxx Hyy Vzzz Code Meaning xx 01 FF Module ...

Страница 19: ...17 RMG 4 U 18 BMG 6 T 92 Object 252 Version of 1st extension module Telegram format See above object 251 Possible module codes as of 03 2015 Module Code Module or mains voltage are unavailable 00 RME 8 S 11 RME 4 I 12 DME 2 T 13 JME 4 T JME 4 T 24V 14 HME 6 T 15 RME 8 T 17 RME 4 U 18 BME 6 T 92 Object 253 Version of 2nd extension module See above object 252 Updated Apr 15 Subject to changes Page 1...

Страница 20: ...tivation of additional functions scenes links etc Contact characteristics Type of contact and status after download bus failure etc Threshold Settings for triggering channel function through exceeding threshold Block function Type of block telegram and response to blocking Scenarios Selection of scene numbers relevant to the channel Feedback Status of feedback object etc Hour counter and service T...

Страница 21: ... T 24V HME 6 T RME 4 S RME 4 C load DME 2 SME 2 BME 6 JME 4 S HME 4 Selection of 1st extension module if available MIX or MIX2 series Type of 2nd extension module not available inactive RME 8 S RME 8 T RME 4 I RME 4 U DME 2 T JME 4 T JME 4 T 24V HME 6 T RME 4 S RME 4 C load DME 2 SME 2 BME 6 JME 4 S HME 4 Selection of 2nd extension module if available MIX or MIX2 series Time for cycl sending of fe...

Страница 22: ...til reset via object applies for 8 hours or until reset via object applies for 12 hours or until reset via object Determines how long the device works manually and how this is ended In manual mode the channels can only be switched on and off via the buttons on the device See also object_78 This parameter is used exclusively for MIX2 series devices Manual operation of channels MIX2 series order no ...

Страница 23: ...ing times and the sequential processing of commands cause an additional delay This can help avoid high current peaks when devices are switched on simultaneously e g with a number of lighting strips None There is no added delay 60 ms 100 ms 200 ms When a relay switches on the next one can only switch on after the set delay is completed The switch on delay between the first and last relay is calcula...

Страница 24: ...Channel function Switching On Off On off time delay Pulse function Staircase light timer switch with forewarning function Flashing Determines the basic functionality of the channel Activation of function via Switch object The channel is operated via a 1 bit object Exceeding the threshold The channel is operated through exceeding a 1 or 2 byte threshold See below The Threshold parameter page Adjust...

Страница 25: ... permanent On and permanent OFF Which central objects are to be taken into account Central objects enable the simultaneous switching on and off of several channels with one single object Adjust feedback Yes The feedback function can be individually adjusted The relevant parameter page is shown no The Feedback function works with the standard parameters not inverted do not transmit cyclically Activ...

Страница 26: ... on command is issued Status with download and bus failure After download or with loss of bus voltage OFF the relay remains switched off ON the relay switches on unchanged the relay remains in the same state as before Status after restoration of the mains supply or bus supply After return of mains or bus voltage OFF the relay remains switched off ON the relay switches on Same as before failure the...

Страница 27: ...onds 0 255 0 255 Input of desired switch off delay in seconds 5 3 2 6 The Pulse function parameter page This parameter page appears if Pulse function is chosen as the Channel function Table 11 Designation Values Description hours 0 3 0 3 Input of desired pulse duration in hours minutes 0 60 0 60 Input of desired pulse duration in minutes seconds 0 255 0 255 Input of desired pulse duration in secon...

Страница 28: ... the staircase light time can be extended restarted by pressing the button again Duration of 1st forewarning in s 0 60 0 The light switches off immediately once the staircase light time is completed 1 60 Default value 10 Once the staircase light time is completed the light should briefly flash and then stay on for the duration of the forewarning Duration of 2nd forewarning in s 0 60 0 No 2nd forew...

Страница 29: ...nutes seconds 0 255 0 255 Input of desired pulse time in seconds OFF phase of flash pulse hours 0 3 0 3 Input of desired length of break tp in hours minutes 0 60 0 60 Input of desired length of break in minutes seconds 0 255 0 255 Input of desired length of break in seconds How often should it flash Until it switches off The channel flashes until a switch off telegram is received 1 x 2 x 3 x 4 x 5...

Страница 30: ...he set type of contact must be taken into account here As switch object 0 NO contact The relay switches off if threshold is exceeded NC contact The relay switches on if threshold is exceeded As switch object 1 NO contact The relay switches on if threshold is exceeded NC contact the relay switches off if threshold is exceeded Parameter for Percent threshold object Threshold 1 99 Default value 50 De...

Страница 31: ...1000 Desired threshold Example of NO contact with response as switch object 1 Switches on when Object value threshold Switches off when Object value threshold hysteresis Hysteresis 1 65534 Default value 5 The hysteresis prevents frequent change overs after small fluctuations in readings Parameter for threshold object EIS5 e g CO2 brightness Lower threshold Format 0 00 99999 0 00 99999 Default valu...

Страница 32: ...n Block telegram Block with ON telegram 0 Enable 1 Block Block with OFF telegram 0 Block 1 Enable Note The block is always deactivated after reset Response when setting the block OFF Switch off ON Switch on unchanged No response Response when cancelling the block OFF Switch off ON Switch on Unchanged No response update Restore normal operation and switch relay accordingly Updated Apr 15 Subject to...

Страница 33: ...el assumes the configured Status after download see below See appendix Teach in scenes without telegrams Unchanged after download All previously taught in scenes are saved However the scene numbers the channel should react to can be changed see below Channel reacts to Participation in central scene object No yes Should the device react to the central scene object Channel reacts to No scene number ...

Страница 34: ... download Off On See above Permit teach in No Yes See above Channel reacts to No scene number Scene number1 Scene number 4 Scene number 63 Fourth of the 8 possible scene numbers Status after download Off On See above Permit teach in No Yes See above Channel reacts to No scene number Scene number1 Scene number 5 Scene number 63 Fifth of the 8 possible scene numbers Status after download Off On See ...

Страница 35: ...cene number1 Scene number 7 Scene number 63 Seventh of the 8 possible scene numbers Status after download Off On See above Permit teach in No Yes See above Channel reacts to No scene number Scene number1 Scene number 8 Scene number 63 Last of the 8 possible scene numbers Status after download Off On See above Permit teach in No Yes See above Updated Apr 15 Subject to changes Page 35 of 50 ...

Страница 36: ...cription Reported status Not inverted Channel switched on feedback object sends a 1 inverted Channel switched on feedback object sends a 0 Transmit feedback cyclically No yes Send at regular intervals Time for cyclical transmission of feedback 2 minutes 3 minutes 5 minutes 10 minutes 15 minutes 20 minutes 30 minutes 45 minutes 60 minutes At what interval Updated Apr 15 Subject to changes Page 36 o...

Страница 37: ...cyclically No yes Send at regular intervals Time for cyclical transmission 2 minutes 3 minutes 5 minutes 10 minutes 15 minutes 20 minutes 30 minutes 45 minutes 60 minutes At what interval Counter for time period before next service Service interval 0 2000 x10 h 0 2000 Default value 100 Desired timescale between 2 services Example 10 10 x 10 h 100 hours Reporting of time to service when changing 0 ...

Страница 38: ...n Designation Values Description Time for cyclical transmission time to service and service 2 minutes 3 minutes 5 minutes 10 minutes 15 minutes 20 minutes 30 minutes 45 minutes 60 minutes At what interval Updated Apr 15 Subject to changes Page 38 of 50 ...

Страница 39: ...al link with the channel object AND link The Logic input in AND gate object appears e g object 1 OR link override The Logic input in OR gate object appears e g object 1 XOR link The Logic input in XOR gate object appears e g object 1 Disable object affects logic object No The disable object only affects the channel object e g object 0 If required the logic object can activate the channel function ...

Страница 40: ...h button interface 2 push buttons are connected to a TA 2 push button interface and they control 2 channels of the RMG 4 U 6 1 1 Devices RMG 4 U 4930223 TA 2 4969202 6 1 2 Overview Figure 1 6 1 3 Objects and links Table 20 No TA 2 No RMG 4 U Comment Object name Object name 0 Channel 1 switching 0 RMG 4 U channel C1 Switch object 3 Channel 2 switching 10 RMG 4 U channel C2 switch object Updated Apr...

Страница 41: ... Switch push button Object type Switching 1 bit Response to rising edge BY Response to falling edge none Channel 2 See channel 1 Table 22 RMG 4 U Parameter page Parameter Setting RMG 4 U channel C1 Configuration options Channel function Switching ON OFF Activation of function via Switch object Contact characteristics Type of contact NO contact RMG 4 U channel C2 See channel C1 Updated Apr 15 Subje...

Страница 42: ...p in a hall is controlled by channel C1 The lamps have to be replaced after 20 000 hours service The time period to the service and the service status are shown on the VARIA 826 S display 6 2 1 Devices RMG 4 U 4930223 VARIA 826 S 8269210 8269211 6 2 2 Overview Figure 2 Updated Apr 15 Subject to changes Page 42 of 50 ...

Страница 43: ...ect 0 Switch object Any KNX sensor Push button time switch twilight switch etc sends the switch command to RMG 4 U Table 24 No RMG 4 U No VARIA Comment Object name Object name 6 Time to next service 39 Counter value 0 65535 Time in hours 7 Service required 41 Switching ON OFF 1 Time has elapsed Updated Apr 15 Subject to changes Page 43 of 50 ...

Страница 44: ...e when changing 0 100 h 0 no report 100 Report service cyclically yes Table 26 VARIA Parameter page Parameter Setting Selection of display pages Show page 1 for display objects yes Display objects page 1 Fade in operating instructions on page 1 No Page heading Lamp maintenance Page 1 line 1 Line format 16 bit counter value object type Text for line 1 Service in Unit for display object h Value rang...

Страница 45: ...ce and it controls a channel of the RMG 4 U A lamp shall flash in the event of an error channel 1 relay output 6 3 1 Devices RMG 4 U 4930223 TA 2 4969202 6 3 2 Overview Figure 3 6 3 3 Objects and links Table 27 No TA 2 No RMG 4 U Comment Object name Object name 0 Channel 1 switching 0 RMG 4 U channel C1 Switch object Updated Apr 15 Subject to changes Page 45 of 50 ...

Страница 46: ...ponse to rising edge On Response to falling edge Off Table 29 RMG 4 U Parameter page Parameter Setting General Type of basic module RMG 4 U RMG 4 U channel C1 Configuration options Channel function Flashing Activation of function via Switch object Contact characteristics Type of contact NO contact Flashing ON phase Hours 0 Minutes 0 Seconds 1 OFF phase Hours 0 Minutes 0 Seconds 1 How often should ...

Страница 47: ...is allocated to the appropriate scene number when a scene is saved The previously saved status is restored when a scene number is called up This allows a MIX system to be easily associated with each chosen user scene Table 30 Permitted scene numbers Series Appliance Supported scene numbers MIX order no 4910xxx SME 2 S JME 4 S RME 4 S C load 1 8 MIX2 order no 4930xxx RMG 4 I RME 4 I RMG 4 U RME 4 U...

Страница 48: ...5 5 85 133 7 06 6 86 134 8 07 7 87 135 9 08 8 88 136 10 09 9 89 137 11 0A 10 8A 138 12 0B 11 8B 139 13 0C 12 8C 140 14 0D 13 8D 141 15 0E 14 8E 142 16 0F 15 8F 143 17 10 16 90 144 18 11 17 91 145 19 12 18 92 146 20 13 19 93 147 21 14 20 94 148 22 15 21 95 149 23 16 22 96 150 24 17 23 97 151 25 18 24 98 152 26 19 25 99 153 27 1A 26 9A 154 28 1B 27 9B 155 29 1C 28 9C 156 30 1D 29 9D 157 31 1E 30 9E ...

Страница 49: ...173 47 2E 46 AE 174 48 2F 47 AF 175 49 30 48 B0 176 50 31 49 B1 177 51 32 50 B2 178 52 33 51 B3 179 53 34 52 B4 180 54 35 53 B5 181 55 36 54 B6 182 56 37 55 B7 183 57 38 56 B8 184 58 39 57 B9 185 59 3A 58 BA 186 60 3B 59 BB 187 61 3C 60 BC 188 62 3D 61 BD 189 63 3E 62 BE 190 64 3F 63 BF 191 Examples central or channel related Calling status of scene 5 Send 04 to the relevant scene object Save curr...

Страница 50: ...possible scene numbers in a channel Status after download parameter The scenes are programmed into the device after the download has been completed Later changes via teach in telegrams are possible if required and they can be permitted or blocked via a parameter 7 2 Conversion of percentages to hexadecimal and decimal values Percentage value 0 10 20 30 40 50 60 70 80 90 100 Hexadecimal 00 1a 33 4D...

Отзывы: