Switch-off delay time
● Transfer areas
approx. 5min.
● Working areas
approx. 10min.
● In the range between 2 - 15min the switch-off delay varies according to
its self-learning behavior. The set values <2min or >15min remain fixed.
● «Pulse»: staircase lighting timer control (0.5sec. “on” / 10sec. “off”)
DIP switch
Light measurement: adaptive or fixed hysteresis
●
: the light measurement is in adaptive mode.
● : if the lighting is continuously
overridden by a superordinate logic, the
adaptive mode can be deactivated.
4.2 Settings for analog output 0-10V
(compact office 24V Lux only)
Linear or logarithmic output of brightness
●
„0-10V lin“: linear output of brightness
●
„0-10V log“: logarithmic output of brightness; improved resolution at low
lux values
0-10V lin
fix
auto
0-10V log
fix
auto