IPsecure Interface KNX
Device technology
17
Resetting to factory settings can also be performed directly on the device. This is not a security risk, because the
device will no longer be part of the system afterward.
•
Press the Programming button when the KNX bus is not connected
•
Hold the Programming button down and plug on the bus terminal. The Programming LED flashes (2 Hz)
•
Press the button, hold it for at least 5 s and then release it. The Programming LED goes out, and the device
reboots with the factory settings
The Interface can be reprogrammed if ETS connects with the device after reset and if the device’s FDSK is still
known to ETS. ETS will report that the device was reset in this case.
See chapter
, for more information about the FDSK (Factory Default Setup Key).
Cleaning
Disconnect the device from the electrical power supply before cleaning. If devices become dirty, they can be
cleaned using a dry cloth or a cloth dampened with a soapy solution. Never use corrosive agents or solutions.
Maintenance
In the event of damage, e.g. during transport and/or storage, repairs are not allowed to be made.
Please keep the device’s firmware up to date; see chapter