IPsecure Interface KNX
Device technology
15
2.4
Mounting and installation
The device is a modular installation device for quick installation in distribution boards on 35 mm mounting rails to
DIN EN 60 715.
The installation position can be selected as required.
The connection to the bus is implemented using the supplied bus connection terminal. The terminal assignment is
located on the housing.
The device is ready for operation after connecting the bus voltage and the auxiliary voltage.
Accessibility to the device for the purpose of operation, testing, visual inspection, maintenance and repair must be
provided compliant to DIN VDE 0100-520.
Prerequisites for commissioning
In order to commission the device, a PC with ETS (ETS 5 version 5.7.4 or higher) and a supply voltage of 12 to 30 V
DC are required. Alternatively, the device can be powered via PoE (Power over Ethernet) to IEEE 802.3af class 1.
The device is ready for operation after connection to the bus voltage and auxiliary voltage.
Mounting and commissioning may only be carried out by electrical specialists. The appropriate standards,
directives, regulations and specifications for the appropriate country should be observed when planning and
setting up electrical installations and security systems for intrusion and fire detection.
•
Protect the device from damp, dirt and damage during transport, storage and operation.
•
Only operate the device within the specified technical data!
•
The device should only be operated in an enclosed housing (distribution board)!
•
The voltage supply to the device must be switched off before mounting work is performed.
Danger
To avoid dangerous touch voltages which originate through feedback from differing phase conductors, all poles
must be disconnected when extending or modifying the electrical connections.
Supplied state
All physical tunneling connection addresses are set to 15.15.100 in the supplied state. In other words, only one
tunnel is visible to the outside. The tunneling connection addresses set in ETS will be adopted only after the first
download.
The IP address is set to automatic IP assignment (DHCP/AutoIP).
Assignment of the physical address
The physical addresses and parameters are assigned and programmed in ETS.
The device features a
Programming
button for assignment of the physical address. The red
Programming
LED
lights up after the button has been pressed. It goes off as soon as ETS has assigned the physical address or the
Programming
button is pressed again.