9
Reset DALI ECGs
The connected DALI ECGs are reset to factory settings.
9. Start-up
Switch-on behaviour
Every time the power supply is switched on, the presence
detector runs through two phases that are indicated by the
LED:
1. Start-up phase (30 s)
•
The red LED flashes at one second intervals and lighting
is switched on with switch-on dimming value C1.
•
The detector does not respond to push-button com-
mands or to the “theSenda S” user remote control.
•
The lighting is switched off after 30 seconds when the
room is unoccupied.
2. Operation
•
The red LED is off. The constant light control or switching
mode are started.
•
The detector is ready for operation.
10. Technical data
Operating voltage
110 – 230 V AC, +10% / -15%
Frequency
50 – 60 Hz
Upstream protection device:
16 A
Power consumption (without DALI-ECG)
< 0.4 W
Type of installation
Ceiling installation; flush/
surface mounted or ceiling
installation
theRonda S360-110 DALI recommended
installation height
theRonda P360-110 DALI recommended
installation height
2.0 – 3.0 m/max. 4 m
2.0 – 3.5 m/max. 15 m
Minimum height
> 1.7 m
Detection area
horizontal 360°
theRonda S360-110 DALI maximum
range
Ø 4 m (Mh. 3 m) / 13 m
2
seated
Ø 9 m (Mh. 15 m) / 64 m
2
walking
theRonda P360-110 DALI maximum
range
Ø 7 m (Mh. 3.5 m) / 38 m
2
seated
Ø 25 m (Mh. 10 m) / 491 m
2
walking
Setting range brightness setpoint value
10 – 3000 lux
Lighting time delay
10 s – 60 min
Presence switch-on delay
0 s – 30 min
Presence time delay
10 s – 120 min
Lighting standby time
0 s – 60 min / permanently on
Standby dimming value
1 – 25%
Control output lighting
100 mA guaranteed, max. 250
mA, max. 64 DALI operating
devices, basic insulation
Connection type
Screw terminals
Max. cable cross-section
Max. 2 x 2.5 mm²
Size of flush-mounted box
Size 1, Ø 55 mm (NIS, PMI)
Protection rating
IP 20 (IP 54 installed)
Ambient temperature
-15 °C ... 50 °C
CE Declaration of Conformity
This device conforms to the
safety regulations of the EMC
directive 2014/30/EU and of
directive 2014/35/EU.
Dali conformity
IEC 62386-101, IEC 62386-103
Product overview
Type of
installation
Channel Operating
voltage
Colour
Type
Item
number
Ceiling
installation
Light
230 V AC
White
theRonda P360-
110 DALI WH
2080040
Ceiling
installation
Light
230 V AC
White
theRonda S360-
110 DALI WH
2080580
Troubleshooting
Fault
Cause
Light does not switch
on and/or off if pre-
sence is detected and
in darkness
Brightness setpoint value is set too low; detector
set on semi-automatic; light was switched off
manually via button or “theSenda S”; person not
within detection area; obstruction(s) interrupting
detection; time delay set too short
Light stays on with
detection of presence
despite sufficient
brightness
Brightness setpoint value is set too high; light was
briefly switched on manually via button or with
“theSenda S” (wait 30 min in switching operation);
detector is in test mode
Light does not switch
off and/or light swit-
ches on spontaneously
when no one is present
Wait for time delay (self-learning);
thermal sources of interference in the detection
area: fan heaters, incandescent lamps/halogen
spotlights, moving objects (e.g. curtains hanging in
open windows)
Push button does not
function
Device still in the start-up phase; illuminated
button was used without neutral conductor;
push button not fed to the Master
Light cannot be swit-
ched off with the push
button
Push button not fed to the detector. Check wiring
to the button
Lighting does not react Short circuit or interruption in the DALI bus. Electri-
cal surge in the DALI bus: Disconnect the detector
from the supply network for 1 minute (thermal
fuse).
Device does not
respond
Short-circuit: disconnect detector from the power
supply for 5 min (thermal fuse)
Error flashing
(4 x per second)
Error in self-test;
device not properly functional!
LED is on and flashes
off briefly 2 x every 3 s
Detector does not recognise DALI ECGs. Check DALI
connections. At least 1 DALI ECG must be connec-
ted to the detector. Short circuit in DALI bus.
Master/Slave, Master/
Master parallel swit-
ching is not working
Detectors and buttons are not connected to the
same external conductor. <Terminal S3/P assign-
ment> parameter is not set to "Parallel".
11. Dimensions diagrams