Theben 2080040 Скачать руководство пользователя страница 9

9

Reset DALI ECGs

The connected DALI ECGs are reset to factory settings.

9.  Start-up

Switch-on behaviour

Every time the power supply is switched on, the presence 

detector runs through two phases that are indicated by the 

LED:

1. Start-up phase (30 s)

 

The red LED flashes at one second intervals and lighting 

is switched on with switch-on dimming value C1.

 

The detector does not respond to push-button com-
mands or to the “theSenda S” user remote control.

 

The lighting is switched off after 30 seconds when the 
room is unoccupied.

2. Operation

 

The red LED is off. The constant light control or switching 
mode are started.

 

The detector is ready for operation.

10. Technical data

Operating voltage

110 – 230 V AC, +10% / -15%

Frequency

50 – 60 Hz

Upstream protection device:

16 A

Power consumption (without DALI-ECG)

< 0.4 W

Type of installation

Ceiling installation; flush/

surface mounted or ceiling 

installation

theRonda S360-110 DALI recommended 

installation height

theRonda P360-110 DALI recommended 

installation height

2.0 – 3.0 m/max. 4 m

2.0 – 3.5 m/max. 15 m

Minimum height

> 1.7 m

Detection area 

horizontal 360°

theRonda S360-110 DALI maximum 

range

Ø 4 m (Mh. 3 m) / 13 m

2

 seated

Ø 9 m (Mh. 15 m) / 64 m

2

 

walking

theRonda P360-110 DALI maximum 

range

Ø 7 m (Mh. 3.5 m) / 38 m

2

 

seated

Ø 25 m (Mh. 10 m) / 491 m

2

 

walking

Setting range brightness setpoint value

10 – 3000 lux

Lighting time delay

10 s – 60 min

Presence switch-on delay

0 s – 30 min

Presence time delay

10 s – 120 min

Lighting standby time

0 s – 60 min / permanently on

Standby dimming value

1 – 25%

Control output lighting

100 mA guaranteed, max. 250 

mA, max. 64 DALI operating 

devices, basic insulation

Connection type

Screw terminals

Max. cable cross-section

Max. 2 x 2.5 mm²

Size of flush-mounted box

Size 1, Ø 55 mm (NIS, PMI)

Protection rating

IP 20 (IP 54 installed)

Ambient temperature

-15 °C ... 50 °C

CE Declaration of Conformity

This device conforms to the 

safety regulations of the EMC 

directive 2014/30/EU and of 

directive 2014/35/EU. 

Dali conformity 

IEC 62386-101, IEC 62386-103

Product overview

Type of 

installation

Channel Operating 

voltage

Colour

Type

Item 

number

Ceiling 

installation

Light

230 V AC

White

theRonda P360-

110 DALI WH

2080040

Ceiling 

installation

Light

230 V AC

White

theRonda S360-

110 DALI WH

2080580

Troubleshooting 

Fault

Cause

Light does not switch 

on and/or off if pre-

sence is detected and 

in darkness

Brightness setpoint value is set too low; detector 

set on semi-automatic; light was switched off 

manually via button or “theSenda S”; person not 

within detection area; obstruction(s) interrupting 

detection; time delay set too short

Light stays on with 

detection of presence 

despite sufficient 

brightness 

Brightness setpoint value is set too high; light was 

briefly switched on manually via button or with 

“theSenda S” (wait 30 min in switching operation); 

detector is in test mode

Light does not switch 

off and/or light swit-

ches on spontaneously 

when no one is present 

Wait for time delay (self-learning);

thermal sources of interference in the detection 

area: fan heaters, incandescent lamps/halogen 

spotlights, moving objects (e.g. curtains hanging in 

open windows) 

Push button does not 

function

Device still in the start-up phase; illuminated 

button was used without neutral conductor; 

push button not fed to the Master

Light cannot be swit-

ched off with the push 

button

Push button not fed to the detector. Check wiring 

to the button

Lighting does not react Short circuit or interruption in the DALI bus. Electri-

cal surge in the DALI bus: Disconnect the detector 

from the supply network for 1 minute (thermal 

fuse).

Device does not 

respond

Short-circuit: disconnect detector from the power 

supply for 5 min (thermal fuse)

Error flashing 

 

(4 x per second)

Error in self-test; 

device not properly functional!

LED is on and flashes 

off briefly 2 x every 3 s

Detector does not recognise DALI ECGs. Check DALI 

connections. At least 1 DALI ECG must be connec-

ted to the detector. Short circuit in DALI bus.

Master/Slave, Master/

Master parallel swit-

ching is not working

Detectors and buttons are not connected to the 

same external conductor. <Terminal S3/P assign-

ment> parameter is not set to "Parallel".

11. Dimensions diagrams

Содержание 2080040

Страница 1: ...ntrol SendoPro theSenda B App optional Installation remote control theSenda P option User remote control theSenda S option 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qual...

Страница 2: ...ic device or after the button is operated semi automatic device Lighting time delay The minimum time delay 10 s 60 min is adjustable It adjusts automatically to the user s behaviour and can incre ase to 30 minutes or reduce back to the set minimum time With settings 2 min or 30 min the time delay remains unchanged at the set value If someone goes into an unoccu pied room only briefly and leaves it...

Страница 3: ...m 452 m2 Ø 24 m 50 m2 Ø 8 m 28 m2 Ø 6 m 3 5 m 452 m2 Ø 24 m 50 m2 Ø 8 m 38 m2 Ø 7 m 4 0 m 452 m2 Ø 24 m 50 m2 Ø 8 m 5 0 m 452 m2 Ø 24 m 50 m2 Ø 8 m 6 0 m 452 m2 Ø 24 m 50 m2 Ø 8 m 10 0 m 491 m2 Ø 25 m 50 m2 Ø 8 m All figures are guidance value Detection areas according to sensNORM IEC 63180 see data sheet Brightness measurement The presence detector measures artificial lighting and day light The i...

Страница 4: ...DALI DA DA L Slave S1 S3 P N P N Light measurement only with the Master Switch up to 10 detectors in parallel Use the same phase for all detectors and buttons Slave theRonda P360 Slave 2080080 Master Master parallel switching Several Masters can be used in parallel switching Each Master controls its lighting group according to its own bright ness measurements Time delays and brightness setpoint va...

Страница 5: ...ription Can be queried Sendo Pro theSenda B App Can be changed Sendo Pro theSenda B App Can be changed theSenda P Standby dim ming value Value range in x IR group address C1 Selection all I II III x Scene 1 C1 Value range in x Scene 2 C1 Value range in x Configuration button Selection enabled disabled x LED display motion Off On x The parameters are sent to the presence detector with the SendoPro ...

Страница 6: ... middle increment 3 Increments 1 to 5 can be selected and sent to the detector with the SendoPro theSenda B App management remote control On the theSenda P installation remote control the sensitivity can be decreased by one increment each time the button is pushed or increased with the button Value range Incre ment Sensitivity 1 Very insensitive 2 Insensitive 3 Standard 4 Sensitive 5 Very sensitiv...

Страница 7: ...ghting is never switched off Never off Manual dimming response With constant lighting control the manual dimming res ponse can be selected with the manual dimming response parameter Value range with SendoPro theSenda B App Constant light control remains active temporarily after manual dimming to the current brightness value as the new setpoint value After the lighting time delay has expired the or...

Страница 8: ...the lighting is switched on The lighting is switched off after 10 seconds when the room is unoccupied Brightness measurement is deactivated detector does not respond to brightness Constant light control is deactivated switching mode Standby function is deactivated The detector reacts as in configuration type fully auto matic device even if semi automatic is set Teach in cannot be activated in test...

Страница 9: ... 101 IEC 62386 103 Product overview Type of installation Channel Operating voltage Colour Type Item number Ceiling installation Light 230 V AC White theRonda P360 110 DALI WH 2080040 Ceiling installation Light 230 V AC White theRonda S360 110 DALI WH 2080580 Troubleshooting Fault Cause Light does not switch on and or off if pre sence is detected and in darkness Brightness setpoint value is set too...

Страница 10: ... de en Cover clip for area restriction Item No 9070921 Details www theben de en theSenda P Item No 9070910 Details www theben de en theSenda S Item No 9070911 Details www theben de en theSenda B App Artikel Nr 9070985 Details www theben de 13 Contact Theben AG Hohenbergstraße 32 72401 Haigerloch GERMANY Tel 49 7474 692 0 Fax 49 7474 692 150 Hotline Tel 49 7474 692 369 hotline theben de www theben ...

Отзывы: