background image

6

 

Deactivation of the brightness measurement (the 
brightness has no effect). The light channels only switch 
after presence/absence. Possible with the „SendoPro, 
theSenda B/App“ management remote control (measu-
ring off) or the “theSenda P” installation remote control 
(button  ).

Room correction factor mid, brightness measure-

ment value mid

The room correction factor is a measurement for the diffe-

rence of the brightness measurement on the ceiling and the 

work area. The brightness value on the ceiling is influenced 

by the installation location, the incidence of light, the position 

of the sun, the weather conditions, as well as the reflection 

properties of the room and the furniture.

With the room correction factor, the measured brightness 

value of the channel C1 light is adjusted to the conditions in 

the room and in this way can be matched to the lux meter 

value 

 measured at the surface beneath the presence 

detector.

Room correction factor =  Brightness value at the ceiling 

 

Brightness value on the work  

 

 surface

We recommend the following procedure:

 

The lux meter is placed on the work surface below the 

sensor and the measured lux value is entered via the 

„SendoPro, theSenda B/App“ management remote control, 

<brightness measurement value mid> parameter.

 

The room correction factor is calculated from this 

automatically. Values between 0.05 and 2.0 are permitted. 

Calculated or entered values outside the permitted range 

will automatically be set to the appropriate limit value.

 

The calculated room correction factor will be applied 

immediately. For monitoring purposes, the room correction 

factor can be queried via the <room correction factor mid> 

parameter.

 

L

The standard value is 0.3 and is suitable for most appli-
cations. Changes are only sensible in strongly deviating 
situations.

Detection sensitivity

The detector has 5 sensitivity increments. The basic setting is 

the middle increment (3). 

Increments 1 to 5 can be selected and sent to the detector 

with the „SendoPro, theSenda B/App“ management remote 

control. On the “theSenda P” installation remote control, the 

sensitivity can be decreased by one increment each time the 
button 

-

 is pushed or increased with the 

 button.

Value range

Incre-

ment

Sensitivity

1

Very insensitive

2

Insensitive

3

Standard

4

Sensitive

5

Very sensitive

By selecting the test presence operating mode, the set sensi-

tivity increment is not changed. 

Lighting time delay

Value range

Adjustable values with SendoPro, theSenda B/App 

management remote control

10 s – 60 min

In the “theSenda P” installation remote control, the 

following values are available

10 s (button 

),  

30 s, 60 s, 2 min,  

10 min, 20 min,  
60 min (button 

)

Short presence 

If someone goes into an unoccupied room only briefly and 

leaves it within 30 seconds, then the lighting will be switched 

off prematurely after 2 minutes (short-term presence). The 

short-term presence can be used for the fully automatic and 

semi-automatic configuration types.

The time delay is applied according to the set time delay.

Off

Short-term presence is active.

On

Energy saving mode eco/eco plus

The selection of “eco” stands for optimum switching behavi-

our, while “eco plus” stands for maximum energy saving.

Value range (with SendoPro, theSenda B/App)

“eco”

The time delay adjusts to the user behaviour by self-learning. 

It does not drop below the set value.

“eco plus” The set time delay remains unchanged (no self-learning 

effect). Faster response to brightness detection than with 

“eco”.

Presence switch-on delay

The contact of the external DALI relay closes when some-

one is present regardless of the brightness and after the set 

switch-on delay has elapsed. Buttons and the configuration 

type (fully automatic device/semi-automatic device) do not 

affect the relay contact.

Value range (with SendoPro, theSenda B/app)

No switch-on delay

0 s

Switch-on delay

10 s – 30 min

Presence time delay

The relay contact of the external DALI relay only opens once 

the set time delay has elapsed in periods of absence.

Содержание 2080040

Страница 1: ...ntrol SendoPro theSenda B App optional Installation remote control theSenda P option User remote control theSenda S option 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qual...

Страница 2: ...ic device or after the button is operated semi automatic device Lighting time delay The minimum time delay 10 s 60 min is adjustable It adjusts automatically to the user s behaviour and can incre ase to 30 minutes or reduce back to the set minimum time With settings 2 min or 30 min the time delay remains unchanged at the set value If someone goes into an unoccu pied room only briefly and leaves it...

Страница 3: ...m 452 m2 Ø 24 m 50 m2 Ø 8 m 28 m2 Ø 6 m 3 5 m 452 m2 Ø 24 m 50 m2 Ø 8 m 38 m2 Ø 7 m 4 0 m 452 m2 Ø 24 m 50 m2 Ø 8 m 5 0 m 452 m2 Ø 24 m 50 m2 Ø 8 m 6 0 m 452 m2 Ø 24 m 50 m2 Ø 8 m 10 0 m 491 m2 Ø 25 m 50 m2 Ø 8 m All figures are guidance value Detection areas according to sensNORM IEC 63180 see data sheet Brightness measurement The presence detector measures artificial lighting and day light The i...

Страница 4: ...DALI DA DA L Slave S1 S3 P N P N Light measurement only with the Master Switch up to 10 detectors in parallel Use the same phase for all detectors and buttons Slave theRonda P360 Slave 2080080 Master Master parallel switching Several Masters can be used in parallel switching Each Master controls its lighting group according to its own bright ness measurements Time delays and brightness setpoint va...

Страница 5: ...ription Can be queried Sendo Pro theSenda B App Can be changed Sendo Pro theSenda B App Can be changed theSenda P Standby dim ming value Value range in x IR group address C1 Selection all I II III x Scene 1 C1 Value range in x Scene 2 C1 Value range in x Configuration button Selection enabled disabled x LED display motion Off On x The parameters are sent to the presence detector with the SendoPro ...

Страница 6: ... middle increment 3 Increments 1 to 5 can be selected and sent to the detector with the SendoPro theSenda B App management remote control On the theSenda P installation remote control the sensitivity can be decreased by one increment each time the button is pushed or increased with the button Value range Incre ment Sensitivity 1 Very insensitive 2 Insensitive 3 Standard 4 Sensitive 5 Very sensitiv...

Страница 7: ...ghting is never switched off Never off Manual dimming response With constant lighting control the manual dimming res ponse can be selected with the manual dimming response parameter Value range with SendoPro theSenda B App Constant light control remains active temporarily after manual dimming to the current brightness value as the new setpoint value After the lighting time delay has expired the or...

Страница 8: ...the lighting is switched on The lighting is switched off after 10 seconds when the room is unoccupied Brightness measurement is deactivated detector does not respond to brightness Constant light control is deactivated switching mode Standby function is deactivated The detector reacts as in configuration type fully auto matic device even if semi automatic is set Teach in cannot be activated in test...

Страница 9: ... 101 IEC 62386 103 Product overview Type of installation Channel Operating voltage Colour Type Item number Ceiling installation Light 230 V AC White theRonda P360 110 DALI WH 2080040 Ceiling installation Light 230 V AC White theRonda S360 110 DALI WH 2080580 Troubleshooting Fault Cause Light does not switch on and or off if pre sence is detected and in darkness Brightness setpoint value is set too...

Страница 10: ... de en Cover clip for area restriction Item No 9070921 Details www theben de en theSenda P Item No 9070910 Details www theben de en theSenda S Item No 9070911 Details www theben de en theSenda B App Artikel Nr 9070985 Details www theben de 13 Contact Theben AG Hohenbergstraße 32 72401 Haigerloch GERMANY Tel 49 7474 692 0 Fax 49 7474 692 150 Hotline Tel 49 7474 692 369 hotline theben de www theben ...