Theben 2080040 Скачать руководство пользователя страница 4

4

Surface-mounted installation

A back box 110A is available for surface mounted installation 

(see accessories).

7.  Connection

The presence detectors can be combined as master in 

individual switching, master-master in parallel switching or 

master-slave parallel switching. Several push buttons can be 

connected to one control input. Illuminated push buttons can 

only be used with neutral conductor connection. 

Up to 50 DALI operating devices can be connected to each 

master device. We recommend distributing the DALI operating 

devices equally over the 3 phases.

L

All detectors and buttons must be connected to the same 
phase.

L

Connect at least 1 Dali operating device per master.

Individual switching

In individual switching, the presence detector, as Master, 

detects presence and brightness and controls lighting.

L

L

N

Master

EV

G

DALI

DA+  DA-

S1

N

Master/Slave parallel switching

If the detection area covered by one presence detector is 

insuffi cient (larger rooms), then up to 10 detectors can be 

operated in parallel by connecting the P terminals. In the 

process, presence detection is performed by all detectors 

together. The Master measures the brightness, operates the 

buttons and controls the lighting. All other detectors are used 

as Slaves. They only provide presence information.

L

N

L

Master

EV

G

DALI

DA+  DA-

L

Slave

S1

S3/P

N

P

N

Light measurement only with the Master

Switch up to 10 detectors in parallel

Use the same phase for all detectors and buttons

Slave: theRonda P360 Slave (2080080)

Master/Master parallel switching

Several Masters can be used in parallel switching. Each 

Master controls its lighting group according to its own bright-

ness measurements. Time delays and brightness setpoint 

values are set individually on each master. Presence continues 

to be detected by all detectors. 

L

N

L

Master 1

EV

G

DALI 1 

DALI 2 

DA+ DA–

Master 2

EV

G

DA+ DA–

S3/P

S1

N

L

S3/P

S1

N

One master with individual brightness measurement per 
lighting group

Switch up to 10 detectors in parallel

Use the same phase for all detectors and buttons

Integrating an external DALI relay

No more than 1 external DALI relay can be connected 
on one single DALI line. The Dali relay must comply with 
Standard IEC 62386-208 (device type 7).

The detector automatically detects the DALI relay.

Switch-on delay and time delay can be set using the 
remote control.

Master

DALI

DA+ DA–

S1 

EVG

N

L

N

L

EVG

DALI

Relay

8.  Settings

The presence detectors are supplied with basic settings ready 

for operation. The specifi cations are guidance values. The 

optional „SendoPro, theSenda B/App“ management remote 

control or the “theSenda P” installation remote control are 

available for start-up support. They enable remote setting. 

The „SendoPro, theSenda B/App“ can be used to query, adjust 

and optimise parameters. Parameters can only be adjusted 

Содержание 2080040

Страница 1: ...ntrol SendoPro theSenda B App optional Installation remote control theSenda P option User remote control theSenda S option 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qual...

Страница 2: ...ic device or after the button is operated semi automatic device Lighting time delay The minimum time delay 10 s 60 min is adjustable It adjusts automatically to the user s behaviour and can incre ase to 30 minutes or reduce back to the set minimum time With settings 2 min or 30 min the time delay remains unchanged at the set value If someone goes into an unoccu pied room only briefly and leaves it...

Страница 3: ...m 452 m2 Ø 24 m 50 m2 Ø 8 m 28 m2 Ø 6 m 3 5 m 452 m2 Ø 24 m 50 m2 Ø 8 m 38 m2 Ø 7 m 4 0 m 452 m2 Ø 24 m 50 m2 Ø 8 m 5 0 m 452 m2 Ø 24 m 50 m2 Ø 8 m 6 0 m 452 m2 Ø 24 m 50 m2 Ø 8 m 10 0 m 491 m2 Ø 25 m 50 m2 Ø 8 m All figures are guidance value Detection areas according to sensNORM IEC 63180 see data sheet Brightness measurement The presence detector measures artificial lighting and day light The i...

Страница 4: ...DALI DA DA L Slave S1 S3 P N P N Light measurement only with the Master Switch up to 10 detectors in parallel Use the same phase for all detectors and buttons Slave theRonda P360 Slave 2080080 Master Master parallel switching Several Masters can be used in parallel switching Each Master controls its lighting group according to its own bright ness measurements Time delays and brightness setpoint va...

Страница 5: ...ription Can be queried Sendo Pro theSenda B App Can be changed Sendo Pro theSenda B App Can be changed theSenda P Standby dim ming value Value range in x IR group address C1 Selection all I II III x Scene 1 C1 Value range in x Scene 2 C1 Value range in x Configuration button Selection enabled disabled x LED display motion Off On x The parameters are sent to the presence detector with the SendoPro ...

Страница 6: ... middle increment 3 Increments 1 to 5 can be selected and sent to the detector with the SendoPro theSenda B App management remote control On the theSenda P installation remote control the sensitivity can be decreased by one increment each time the button is pushed or increased with the button Value range Incre ment Sensitivity 1 Very insensitive 2 Insensitive 3 Standard 4 Sensitive 5 Very sensitiv...

Страница 7: ...ghting is never switched off Never off Manual dimming response With constant lighting control the manual dimming res ponse can be selected with the manual dimming response parameter Value range with SendoPro theSenda B App Constant light control remains active temporarily after manual dimming to the current brightness value as the new setpoint value After the lighting time delay has expired the or...

Страница 8: ...the lighting is switched on The lighting is switched off after 10 seconds when the room is unoccupied Brightness measurement is deactivated detector does not respond to brightness Constant light control is deactivated switching mode Standby function is deactivated The detector reacts as in configuration type fully auto matic device even if semi automatic is set Teach in cannot be activated in test...

Страница 9: ... 101 IEC 62386 103 Product overview Type of installation Channel Operating voltage Colour Type Item number Ceiling installation Light 230 V AC White theRonda P360 110 DALI WH 2080040 Ceiling installation Light 230 V AC White theRonda S360 110 DALI WH 2080580 Troubleshooting Fault Cause Light does not switch on and or off if pre sence is detected and in darkness Brightness setpoint value is set too...

Страница 10: ... de en Cover clip for area restriction Item No 9070921 Details www theben de en theSenda P Item No 9070910 Details www theben de en theSenda S Item No 9070911 Details www theben de en theSenda B App Artikel Nr 9070985 Details www theben de 13 Contact Theben AG Hohenbergstraße 32 72401 Haigerloch GERMANY Tel 49 7474 692 0 Fax 49 7474 692 150 Hotline Tel 49 7474 692 369 hotline theben de www theben ...

Отзывы: