5.  Detection area

The square detection area of the presence detector guaran-

tees accurate and simple planning. Square detection areas 

make it possible to cover a whole room with parallel swit-

ching. Note that seated and walking persons are detected in 

differently-sized areas. The recommended installation height 

is 2.0 m – 3.0 m. The sensitivity of the presence detector 

decreases with increasing installation height. At an installa-

tion height of 3 m or higher, walking motions are necessary 

and the detection areas of several detectors should overlap 

in the marginal zones. The detection range is reduced as the 

temperature increases.

Seated persons:

The presence detector reacts very sensitively to the slightest 

movements. The details refer to smallest movements at table 

height (approx. 0.80 m). The detection sensitivity is reduced 

from an installation height of > 3 m. More pronounced move-

ments are required for clear detection.

Walking persons:

Use of the whole detection area. 

o

0

1

2

3

4

1

4

2

3

3

2

1

0

m

seated 

persons

walking 

persons

Instal-

lation 

height

seated persons

walking persons

2.0 m

  9 m

2

3.0 m x 3.0 m

20 m

2

 4.5 m x 4.5 m ± 0.5 m

2.5 m

16 m

2

4.0 m x 4.0 m

36 m

2

 6.0 m x 6.0 m ± 0.5 m

3.0 m

25 m

2

5.0 m x 5.0 m

49 m

2

 7.0 m x 7.0 m ± 1.0 m

3.5 m

---

64 m

2

 8.0 m x 8.0 m ± 1.0 m

Brightness measurement

The presence detector measures artificial light and daylight 

(opening angle for each approx. ± 30°). The installation loca-

tion is the reference point for the lighting level. The bright-

ness measurement can be adapted to the conditions in a 

room with the room correction factor. The light measurement 

area maps a rectangle of about 2 x 3.5 m at table height.

Direct light influences the light measurement. Avoid placing 

floor lamps or suspended lighting directly below the detector. 

 

L

With deactivated constant lighting control (reg. off), the 
brightness measurement is switched off.

Fenster

Innen

2m

Suitable lamps

The presence detector is designed for the operation of fluo

-

rescent lamps, compact fluorescent lamps, halogen/incande

-

scent lamps and LEDs. 

6.  Installation

Flush-mounted fitting

The presence detector is flush-mounted using a size 1 stan

-

dard flush-mounting installation socket.

Ceiling installation

A ceiling installation box 73A is available for a simplified 

ceiling installation of the presence detector (see accessories). 

This also ensures cord grip and contact protection. The instal-

lation diameter is 72 mm (drill diameter 73 mm).

Surface-mounted installation

A back box 110A, protection rating IP40, is available for sur-

face mounted installation (see accessories).

Содержание 2070525

Страница 1: ...Safety Danger of death through electric shock or fire Installation should only be carried out by a quali fied electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qualified electrician in accordance with the technical regulations applying to electricity Comply with the country specific safe...

Страница 2: ...s to the standby brightness if the room brightness falls below the brightness setpoint value When the room is entered again the detector returns to the programmed brightness setpoint value either automatically fully automatic device or after the button is operated semi automatic device In switching operation the standby function is also available Instead of the brightness setpoint value the switch...

Страница 3: ... 0 m 0 5 m 3 0 m 25 m2 5 0 m x 5 0 m 49 m2 7 0 m x 7 0 m 1 0 m 3 5 m 64 m2 8 0 m x 8 0 m 1 0 m Brightness measurement The presence detector measures artificial light and daylight opening angle for each approx 30 The installation loca tion is the reference point for the lighting level The bright ness measurement can be adapted to the conditions in a room with the room correction factor The light me...

Страница 4: ...ments Delay times and brightness setpoint values are set individually on each Master Presence continues to be detected by all detectors L N L P S Master EVG DALI 1 DA DA L S Master EVG DALI 2 DA DA N P N One Master with individual brightness measurement per lighting group Set potentiometer and DIP switch individually for each Master Switch up to 10 detectors in parallel Use the phase with the same...

Страница 5: ...ith the potentiometer the desired basic brightness in standby operation can be set The setting range is between 1 and 25 of the lamp output The factory presetting is at 10 1 3 5 10 15 20 25 By using the management remote control the standby set tings can be set in finer increments DIP switch Fully semi automatic device auto man auto man Description of the function semi automatic or fully automatic...

Страница 6: ...ness is measured below the presence detector If the prevailing brightness is below the setpoint value the light is switched on when a presence is detected in configuration type fully automatic device Value range Lux values with SendoPro 868 A management remote control In the installation remote control theSenda P the following values are available The currently measured brightness value lux can be...

Страница 7: ...lighting switches on and off automa tically due to presence absence and brightness auto Semi automatic Switching on always has to be done manually Switching off is done automatically by the presence detector due to presence or brightness man Detection sensitivity The detector has 5 sensitivity increments The basic setting is the middle increment 3 By selecting the test presence operating mode the ...

Страница 8: ...here is no motion the red LED switches off and the lighting is switched off after 10 s Brightness measurement deactivated detector does not react to brightness The detector reacts as in configuration type fully auto matic device even if semi automatic is set Detector stays permanently in the test phase Setting the presence test mode via remote control The detector goes directly into test mode when...

Страница 9: ...detector Check wiring to the button Device does not respond Short circuit or several phases in parallel swit ching Disconnect detector from the power supply for 5 min thermal fuse Error flashing 4 x per second Error in self test Device not properly functional Guarantee Theben HTS presence detectors are manufactured with the utmost care and using state of the art technology and are quality tested T...

Страница 10: ...eben de SendoPro 868 A Item No 9070675 Details www theben de theSenda S Item No 9070911 Details www theben de theSenda P Item No 9070910 Details www theben de 13 Contact Theben HTS AG Im Langhag 7b 8307 Effretikon SWITZERLAND Phone 41 52 355 17 00 Fax 41 52 355 17 01 Hotline Phone 41 52 355 17 27 hotline theben hts ch Addresses telephone numbers etc www theben hts ch ...

Отзывы: