thePrema S360 DALI

           

 Mechanical safety lock

Light channel A 

The lighting is controlled by presence and brightness. Artificial 

lighting is switched on and regulated at a constant brightness 

level via a DALI interface in the event of too little daylight and 

when the room is occupied.

The lighting is switched off via the DALI interface if there is 

sufficient daylight or if the room is unoccupied. 

Constant lighting control (DIP2: reg.on)

Constant lighting control compensates variations in daylight 

with controlled artificial light. The overall brightness will be 

kept constant at the desired brightness level. A setpoint in lux 

will be preset during start-up. This value will be applied whe-

never the light is switched on by the detector. Depending on 

"school" or "office" configuration type, the presence detector 

behaves differently after manual dimming via button:

 

"School" configuration type for applications in class

-

rooms and meeting rooms:

 

y

Manual dimming stops constant lighting control.

 

y

Lighting remains at dimmed level when room is occupied 

(no brightness influence).

 

y

Switching off and on returns to standard operation.

 

"Office" configuration type for applications in small and 
large offices:

 

y

Constant lighting control remains active after manual dim-

ming to new brightness setpoint value.

 

y

The new brightness setpoint value only applies if the room 

is occupied.

 

y

Switching off and on returns to standard operation with the 

originally set brightness setpoint value.

Switching operation (DIP2: reg.off)

If constant lighting control is switched off, the lighting is 

controlled depending on presence only. During start-up, the 

switch-on dimming value is preset. When switching on, the 

lighting dims to the set value, regardless of the daylight. By 

using the button, the intensity of artificial light can be chan

-

ged for the duration of the presence.

Standby (orientation light)

The standby function acts as an orientation light. After the 

time delay expires, the lighting is set to the standby bright-

ness (1 - 25 % of the lamp output). The standby time can be 

set between 0 s and 60 min or permanently. The lighting is 

switched off if the brightness level in the room exceeds the 

brightness setpoint value. The lighting automatically returns 

to the standby brightness if the room brightness falls below 

the brightness setpoint value. When the room is entered 

again, the detector returns to the programmed brightness 

setpoint value, either automatically (fully automatic device) or 

after the button is operated (semi-automatic device).

In switching operation, the standby function is also available. 

Instead of the brightness setpoint value, the switch-on dim-

ming value is relevant.

Time delay

The minimum time delay (10 s - 60 min) is adjustable. It 

adjusts automatically to the user's behaviour and can incre-

ase independently to max. 30 minutes or reduce back to the 

set minimum time. With settings ≤ 2 min or ≥ 30 min, the time 

delay remains unchanged at the set value. If someone goes 

into an unoccupied room only briefly and leaves it within 30 

seconds, then the light will be switched off prematurely after 

2 minutes (short-term presence).

Button control

The lighting can be manually switched or dimmed at any time 

via a button. A short press of the button switches the light 

on or off, a longer press of the button dims the lighting up or 

down. The dimming direction changes each time the button is 

pressed.

The light is forced off after a preset time delay if the room 

was (previously) vacated. If artificial lighting is switched off 

manually, the lighting remains switched off as long as the 

room is occupied. The lighting switches again automatically 

after the time delay has expired.

Adjusting the brightness setpoint value via button

During operation, the brightness setpoint value can be set by 

using the button. Release or blocking can be set on the DIP 

switch, see chapter 8. Settings. The setting is done as follows:

 

†

Dim to the desired setpoint value by using the button

 

†

Release the button

 

†

Hold the button for > 15 seconds, until the lighting flashes. 

(During this time, the lighting dims to maximum or mini-

mum value). New set point value is stored permanently!

During switching operation (DIP2: reg.off), the switch-on dim-

ming value is set instead of the brightness setpoint value. 

Fully or semi-automatic device

Lighting control via the presence detector operates fully 

automatically for increased comfort or semi-automatically 

for greater energy savings. The lighting switches on and off 

automatically as „fully automatic device“. As „semi-automatic 

device“, the lighting must always be switched on manually. 

The lighting is switched off automatically.

Exceptionally easy configuration of the energy-saving beha-

viour

By selecting “eco” for optimal switching behaviour or “eco 

plus” for maximum energy saving, users can adjust the pre-

sence detector to their requirements very easily.

Содержание 2070525

Страница 1: ...Safety Danger of death through electric shock or fire Installation should only be carried out by a quali fied electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qualified electrician in accordance with the technical regulations applying to electricity Comply with the country specific safe...

Страница 2: ...s to the standby brightness if the room brightness falls below the brightness setpoint value When the room is entered again the detector returns to the programmed brightness setpoint value either automatically fully automatic device or after the button is operated semi automatic device In switching operation the standby function is also available Instead of the brightness setpoint value the switch...

Страница 3: ... 0 m 0 5 m 3 0 m 25 m2 5 0 m x 5 0 m 49 m2 7 0 m x 7 0 m 1 0 m 3 5 m 64 m2 8 0 m x 8 0 m 1 0 m Brightness measurement The presence detector measures artificial light and daylight opening angle for each approx 30 The installation loca tion is the reference point for the lighting level The bright ness measurement can be adapted to the conditions in a room with the room correction factor The light me...

Страница 4: ...ments Delay times and brightness setpoint values are set individually on each Master Presence continues to be detected by all detectors L N L P S Master EVG DALI 1 DA DA L S Master EVG DALI 2 DA DA N P N One Master with individual brightness measurement per lighting group Set potentiometer and DIP switch individually for each Master Switch up to 10 detectors in parallel Use the phase with the same...

Страница 5: ...ith the potentiometer the desired basic brightness in standby operation can be set The setting range is between 1 and 25 of the lamp output The factory presetting is at 10 1 3 5 10 15 20 25 By using the management remote control the standby set tings can be set in finer increments DIP switch Fully semi automatic device auto man auto man Description of the function semi automatic or fully automatic...

Страница 6: ...ness is measured below the presence detector If the prevailing brightness is below the setpoint value the light is switched on when a presence is detected in configuration type fully automatic device Value range Lux values with SendoPro 868 A management remote control In the installation remote control theSenda P the following values are available The currently measured brightness value lux can be...

Страница 7: ...lighting switches on and off automa tically due to presence absence and brightness auto Semi automatic Switching on always has to be done manually Switching off is done automatically by the presence detector due to presence or brightness man Detection sensitivity The detector has 5 sensitivity increments The basic setting is the middle increment 3 By selecting the test presence operating mode the ...

Страница 8: ...here is no motion the red LED switches off and the lighting is switched off after 10 s Brightness measurement deactivated detector does not react to brightness The detector reacts as in configuration type fully auto matic device even if semi automatic is set Detector stays permanently in the test phase Setting the presence test mode via remote control The detector goes directly into test mode when...

Страница 9: ...detector Check wiring to the button Device does not respond Short circuit or several phases in parallel swit ching Disconnect detector from the power supply for 5 min thermal fuse Error flashing 4 x per second Error in self test Device not properly functional Guarantee Theben HTS presence detectors are manufactured with the utmost care and using state of the art technology and are quality tested T...

Страница 10: ...eben de SendoPro 868 A Item No 9070675 Details www theben de theSenda S Item No 9070911 Details www theben de theSenda P Item No 9070910 Details www theben de 13 Contact Theben HTS AG Im Langhag 7b 8307 Effretikon SWITZERLAND Phone 41 52 355 17 00 Fax 41 52 355 17 01 Hotline Phone 41 52 355 17 27 hotline theben hts ch Addresses telephone numbers etc www theben hts ch ...