4
Setting the brightness switching value (LUX 1/LUX 2)
You can set different brightness values with the brightness
potentiometer (factory setting
500 lx).
S
et the potentiometer to the desired switch-on brightness
10 – 3000 lux ( = light measurement off).
Teach-in function (teaching the brightness switching value)
At the desired brightness, set the potentiometer to
.
▻ The LED flashes for 20 s.
Move away from the detector so the light measurement will
not be influenced.
▻ When the LED stops flashing, the currently measured
brightness value will be accepted as the new brightness
setpoint value.
Leave the potentiometer at position
.
Setting the time delay (TIME)
If the detector detects
no further movement, it switches off
after the set time delay. If you want to change the preset time
(factory setting 10 min):
Set the potentiometer to the desired time
(e.g. 10 s – 60 min).
Pulse function
If you wish to use the pulse function (e.g. for a staircase light
timer switch):
Set the potentiometer to
(0.5 s on, 9.5 s off).
Test detection area (test mode or walking test)
The test mode is used to test the detection area and to
restrict it if necessary.
Set the TIME potentiometer to
test
.
▻ The presence detector only reacts to movements;
brightness measurement is switched off.
▻ After the detector has detected a movement, it switches
the connected light on. At the same time, the red LED
lights up briefly each time a movement is detected. If
no movement is detected, the light switches off after
the time delay of 10 s has passed.
10 sec
L
If the walking test is carried out using the slave device, the
walking test must also be activated on the master device.
L
Test mode can also be activated via the theSenda P
remote control and the theSenda B/app.
7. Parameters and control commands via
remote control
The following parameters can be checked or changed via
the remote control for support during start-up as well as
servicing:
Parameters
Parameter
theSenda B/
app
check
Can be chan-
ged by
theSenda B/
app
Can be
changed by
theSenda P
Brightness setpoint
value A
X
X
X
Brightness setpoint
value B
X
X
X
Room correction factor
A
X
X
Room correction factor
B
X
X
Brightness measure
-
ment value A
X
Brightness measure
-
ment value B
X
Time delay A+B
X
X
Short-term presence
A+B
X
Configuration type A+B
X
X
Detection sensitivity
increment 3 (standard)
X
X
X
IR group address A
X
IR group address B
X
Scene 1 A
X
Scene 2 A
X
Scene 1 B
X
Scene 2 B
X
LED motion display
X
A corresponds to lighting channel 1 and B to lighting channel 2
L
The parameters are sent to the detector by infrared. Chan
-
ged parameters are applied and used. The red status LED
flashes briefly to confirm that the device has received and
understood the infrared commands.
To check the parameters:
press the
button and follow the instructions in the app.
Control commands
The following control commands can be triggered with the
remote control:
Control command
Can be trigge-
red by
theSenda B/app
Can be
triggered by
theSenda P
Can be
triggered by
theSenda S
Teach-in channel A
X
Teach-in channel B
X
Teach-in channel A+B
X
X
Switching light A
X
X
Switching light B
X
X
Switching light (all)
X
X
Presence test
X
X
Restart
X
X
Factory settings
X