If the bezel frame is mounted as shown in the figure, the 
alignment of the light measurement can also be identified 
when it is installed. The arrow marking shows where light 
measurement L2 is.

 

 

†

Disconnect the power source prior to installation.

Installation in false ceiling (ceiling installation)

 

†

Create a ceiling opening of approx. Ø 68 mm.

 

†

Strip the cable to 6 – 8 mm.

 

†

Assemble and connect the device as shown in the figure.

 

Ø = 68

6 - 8 mm

30 - 35 mm

Screws

Flush mounting

 

†

Remove the ceiling installation box from the detector.

 

†

Strip the cable to 6 – 8 mm.

 

†

Assemble and connect the device as shown in the figure.

 

6 - 8 mm

20 - 30 mm

Decorative

frame

Turn left to

take off

Non-dropping

screw

Fixing plate

Detector

Secured 

screws

Turn anticlockwise 

and remove

Decorative 

ring

Detector

Installation 

frame

 

L

A box with a minimum depth of 40 mm provides the opti

-

mum installation conditions. 

Surface mounting

 

†

Strip the cable to 6 – 8 mm.

 

†

Assemble and connect the device as shown in the figure.

 

L

IP 54 protection. 

6 - 8 mm

30 - 35 mm

Decorative

frame

Turn left to

take off

Non-dropping

screw

Detector

Secured 

screws

Turn anticlockwise 

and remove

Decorative 

ring

Detector

Surface-mount 

frame 9070819

Detection area

A

S

T

Installation 

height (A)

Walking persons

 

frontal (r)

Walking persons

 

across (t)

Seated persons 

(s)

2.5 m

28 m

2

Ø 6 m

452 m

2

Ø 24 m

28 m

2

Ø 6 m

All figures are guidance values.

 

Limiting the detection area

 

†

Use

 the enclosed cover clip to adjust the detector to the 

desired detection area.

 

†

Remove the required section of the clip using scissors.

 

†

Then place it on the lens.

Содержание 1040200

Страница 1: ...ect the power supply and ensure that the parts are no longer live Prior to commissioning and using the product read and observe all the operating instructions The presence detector conforms to EN 60669 2 1 if correctly installed 3 Proper use Presence detector for presence and brightness depen dent lighting control Suitable for ceiling installation false ceilings flush mounting in standard box or s...

Страница 2: ...crew Fixing plate Detector Secured screws Turn anticlockwise and remove Decorative ring Detector Installation frame LA box with a minimum depth of 40 mm provides the opti mum installation conditions Surface mounting Strip the cable to 6 8 mm Assemble and connect the device as shown in the figure LIP 54 protection 6 8 mm 30 35 mm Decorative frame Turn left to take off Non dropping screw Detector Se...

Страница 3: ...nually switch on off the ligh ting at any time Switching on manually Pressing the button briefly switches the light on While move ment is detected the light will stay on for at least 30 min Afterwards it will go out if the brightness is sufficient If no more movements are detected the light switches off after the set time delay Switching off manually If the light is switched on it can be switched ...

Страница 4: ... passed 10 sec LIf the walking test is carried out using the slave device the walking test must also be activated on the master device LTest mode can also be activated via the theSenda P remote control and the theSenda B app 7 Parameters and control commands via remote control The following parameters can be checked or changed via the remote control for support during start up as well as servicing...

Страница 5: ... press the lighting channel 2 button and then the button with the desired lux value Room correction factor A room correction factor B The room correction factor is a measurement for the diffe rence of the brightness measurement on the ceiling and the work area The brightness value on the ceiling is influenced by the installation location the incidence of light the position of the sun etc theSenda ...

Страница 6: ...a S Group addresses for the remote control theSenda S group address I is assigned to lighting channel 1 and group address II to lighting channel 2 theSenda B here any group addresses can be assigned to any lighting channel buttons A lighting channel can only be switched on or off if the group address of the lighting channel matches the corresponding button on the remote control The selection of th...

Страница 7: ...light B switching light all on off theSenda Plug theSenda B theSenda P theSenda S Test Presence mode The Test Presence mode is used to check the presence detection and wiring Select ON in the app The presence detector only reacts to movements brightness measurement is switched off After the detector has detected a movement it switches the connected light on At the same time the red LED lights up b...

Страница 8: ...rly The presence detector is in presence test mode or LED motion display is activated The LED detects movements Troubleshooting Fault Cause Light does not switch on or off if presence is detected and in darkness Lux value is set too low detector set to semi automatic light was switched off manually via button or remote control person not within detec tion area obstruction s interrupting detection ...

Страница 9: ... 40 IP 54 surface mounting Protection class II subject to designated installation Cleaning and service Only use a dry soft cloth to clean the device surface Do not use any cleaning agents or solvents Disposal Dispose of device in environmentally sound manner electronic waste Dimensional drawings 10 Contact Theben AG Hohenbergstr 32 72401 Haigerloch GERMANY Phone 49 7474 692 0 Fax 49 7474 692 150 H...

Отзывы: