background image

3

5.  Connection

 

!

Use the same phase for all detectors and buttons.

 

!

Several buttons can be connected to one control input. 
Illuminated buttons can only be used with a neutral 
conductor connection.

 

!

Secure device with an upstream type B or type C 10 A 
circuit breaker (EN 60898-1).

Individual switching

In individual switching, the presence detector detects pre

-

sence and brightness and controls lighting.

S1

1

2

1

2

S2

Master

Master/slave parallel switching

If the detection area covered by a single presence detector 

is insufficient (in large rooms), then several detectors can 

be operated in parallel by connecting the P terminals. In the 

process, presence detection is performed by all detectors 

together. The master measures the brightness, processes the 

button information and controls the lighting. Slaves are used 
as further detectors. They only provide presence information.

S1

P

N

L

1

2

1

2

S2

P

N

L

Master 1

Slave

1040200

 

L

Use the same phase for all detectors.

 

L

A maximum of 10 devices can be operated in parallel.

Master/master parallel switching

Several masters can be used in a parallel switching configu

-

ration. Every master controls its lighting group according to 

its own brightness measurement. Delay times and brightness 

setpoint values are set individually on each master. Presence 

continues to be detected by all detectors.

S1

P

N

L

1

2

1

2

S2

S1

1

2

1

2

S2

P

N

L

Master 1

Master 2

 

L

Use the same phase for all detectors.

 

L

A maximum of 10 devices can be operated in parallel.

Button input

The button can be used to manually switch on/off the ligh

-

ting at any time. 

Switching on manually

Pressing the button briefly switches the light on. While move

-

ment is detected, the light will stay on for at least 30 min. 

Afterwards, it will go out if the brightness is sufficient. If no 

more movements are detected, the light switches off after the 

set time delay.

Switching off manually

If the light is switched on, it can be switched off by briefly 

pressing the button. As long as people are present, the ligh

-

ting remains switched off. If no more movements are detec

-

ted, the lighting switches on again automatically after the 

time delay has passed.

Fully or semi-automatic

Lighting control via the presence detector operates fully auto

-

matically or semi-automatically. As a “fully automatic device”, 

the lighting is switched on and off automatically (depending 

on the parameters set). As a “semi-automatic device”, the 

detector has to be activated via a connected button. It is then 

controlled and switched off depending on movement and 

brightness. The remote control is used to make the settings.

Switch-on behaviour

When the power supply is switched on or the device is 

restarted using the remote control, the presence detector 

runs through two phases that are shown by an LED and the 

connected lamp:

1. Warm-up phase (1 min)

 

The red LED flashes and the light switch contact is 

closed (light on).

 

The detector does not respond to button commands and 
remote control commands.

2. Operation

 

The detector is on standby (LED off) and the light switch 

contact opens when no one is present (light off).

6.  Settings via potentiometer

The presence detector has 3 potentiometers (under the cover) 

for setting the time delay (TIME) and brightness switching 

value (LUX).

Teach-in

Pulse

Test

Содержание 1040200

Страница 1: ...ect the power supply and ensure that the parts are no longer live Prior to commissioning and using the product read and observe all the operating instructions The presence detector conforms to EN 60669 2 1 if correctly installed 3 Proper use Presence detector for presence and brightness depen dent lighting control Suitable for ceiling installation false ceilings flush mounting in standard box or s...

Страница 2: ...crew Fixing plate Detector Secured screws Turn anticlockwise and remove Decorative ring Detector Installation frame LA box with a minimum depth of 40 mm provides the opti mum installation conditions Surface mounting Strip the cable to 6 8 mm Assemble and connect the device as shown in the figure LIP 54 protection 6 8 mm 30 35 mm Decorative frame Turn left to take off Non dropping screw Detector Se...

Страница 3: ...nually switch on off the ligh ting at any time Switching on manually Pressing the button briefly switches the light on While move ment is detected the light will stay on for at least 30 min Afterwards it will go out if the brightness is sufficient If no more movements are detected the light switches off after the set time delay Switching off manually If the light is switched on it can be switched ...

Страница 4: ... passed 10 sec LIf the walking test is carried out using the slave device the walking test must also be activated on the master device LTest mode can also be activated via the theSenda P remote control and the theSenda B app 7 Parameters and control commands via remote control The following parameters can be checked or changed via the remote control for support during start up as well as servicing...

Страница 5: ... press the lighting channel 2 button and then the button with the desired lux value Room correction factor A room correction factor B The room correction factor is a measurement for the diffe rence of the brightness measurement on the ceiling and the work area The brightness value on the ceiling is influenced by the installation location the incidence of light the position of the sun etc theSenda ...

Страница 6: ...a S Group addresses for the remote control theSenda S group address I is assigned to lighting channel 1 and group address II to lighting channel 2 theSenda B here any group addresses can be assigned to any lighting channel buttons A lighting channel can only be switched on or off if the group address of the lighting channel matches the corresponding button on the remote control The selection of th...

Страница 7: ...light B switching light all on off theSenda Plug theSenda B theSenda P theSenda S Test Presence mode The Test Presence mode is used to check the presence detection and wiring Select ON in the app The presence detector only reacts to movements brightness measurement is switched off After the detector has detected a movement it switches the connected light on At the same time the red LED lights up b...

Страница 8: ...rly The presence detector is in presence test mode or LED motion display is activated The LED detects movements Troubleshooting Fault Cause Light does not switch on or off if presence is detected and in darkness Lux value is set too low detector set to semi automatic light was switched off manually via button or remote control person not within detec tion area obstruction s interrupting detection ...

Страница 9: ... 40 IP 54 surface mounting Protection class II subject to designated installation Cleaning and service Only use a dry soft cloth to clean the device surface Do not use any cleaning agents or solvents Disposal Dispose of device in environmentally sound manner electronic waste Dimensional drawings 10 Contact Theben AG Hohenbergstr 32 72401 Haigerloch GERMANY Phone 49 7474 692 0 Fax 49 7474 692 150 H...

Отзывы: