1.  General information

 

Passive infrared presence detector with 2 lighting chan-

nels for ceiling installation (false ceiling), flush mounting 
in standard box and surface mounting

 

Circular detection area 360°, up to Ø 24 m (452 m

2

)

 

Restriction of detection area with cover clips

 

2 mixed light measurements

 

Settings via potentiometer or remote control

 

Fully or semi-automatic operation, switchable

 

Brightness setpoint value adjustable, teach-in function

 

Reduction of time delay when present briefly (short-term 

presence)

 

Pulse function for staircase light timer switch

 

Configurable time delay

 

Configurable detection sensitivity

 

Ready for immediate use due to factory presetting

 

Test mode for checking function and detection area

 

Extension of detection area via master/slave or master/
master switching

 

Optional accessories

Surface-mount frame 100A WH (9070819)

 

theSenda S user remote control (9070911) (theSenda S 
for short), theSenda P service remote control (9070910) 
(theSenda P for short), theSenda B app remote control 
(9070985) and the corresponding “theSenda Plug” app 
(iOS/Android) (theSenda B/app for short)

2.   Safety

Assembly and installation should only be carried 

out by a qualified electrician, somebody who has 

completed appropriate professional training and 

has the knowledge and experience necessary to be 

able to recognise and avoid the potential dangers 

posed by electricity.

Before installation/disassembly, disconnect the 

power supply and ensure that the parts are no 

longer live.

Prior to commissioning and using the product, read 

and observe all the operating instructions.

The presence detector conforms to EN 60669-2-1 if correctly 

installed.

3.  Proper use

 

Presence detector for presence and brightness-depen-
dent lighting control 

 

Suitable for ceiling installation (false ceilings), flush 
mounting in standard box or surface mounting in inte

-

riors (offices, meeting rooms, classrooms, warehouses, 

sports halls, garages, etc.)

4.  Installation

Installation instructions

As the detector reacts to variations in temperature, avoid the 

following situations:

 

†

Do not point the presence detector at objects with highly 

reflective surfaces such as mirrors, etc.

 

†

Do not install the presence detector near heat sources such 

as heating vents, air conditioners, lamps, etc.

 

†

Do not point the presence detector at objects that move in 

the wind such as curtains, large plants, etc.

 

†

Pay attention to the direction of motion during the test run.

 

 

L

Prior to installation, you may need to make settings at the 
potentiometers.

 

L

Observe the recommended installation height of 2 – 5 m.

 

L

Ensure that there are no obstructions as infrared rays 
cannot pass through solid objects. 

 

L

Light measurement L1 is assigned to lighting channel 1 
and light measurement L2 is assigned to lighting channel 
2. This must be taken into consideration when installing 

the detector.  

Example

: If light measurement L1 is directed towards the 

window, lighting channel 1 (terminal connection ↑1) 

must also be provided at the window. 

L2

L1

L1

L2

1

2

 

†

Place the bezel frame on the housing so that the notches 

line up. 

 

†

Turn the cover ring clockwise briefly until it clicks into place.

Содержание 1040200

Страница 1: ...ect the power supply and ensure that the parts are no longer live Prior to commissioning and using the product read and observe all the operating instructions The presence detector conforms to EN 60669 2 1 if correctly installed 3 Proper use Presence detector for presence and brightness depen dent lighting control Suitable for ceiling installation false ceilings flush mounting in standard box or s...

Страница 2: ...crew Fixing plate Detector Secured screws Turn anticlockwise and remove Decorative ring Detector Installation frame LA box with a minimum depth of 40 mm provides the opti mum installation conditions Surface mounting Strip the cable to 6 8 mm Assemble and connect the device as shown in the figure LIP 54 protection 6 8 mm 30 35 mm Decorative frame Turn left to take off Non dropping screw Detector Se...

Страница 3: ...nually switch on off the ligh ting at any time Switching on manually Pressing the button briefly switches the light on While move ment is detected the light will stay on for at least 30 min Afterwards it will go out if the brightness is sufficient If no more movements are detected the light switches off after the set time delay Switching off manually If the light is switched on it can be switched ...

Страница 4: ... passed 10 sec LIf the walking test is carried out using the slave device the walking test must also be activated on the master device LTest mode can also be activated via the theSenda P remote control and the theSenda B app 7 Parameters and control commands via remote control The following parameters can be checked or changed via the remote control for support during start up as well as servicing...

Страница 5: ... press the lighting channel 2 button and then the button with the desired lux value Room correction factor A room correction factor B The room correction factor is a measurement for the diffe rence of the brightness measurement on the ceiling and the work area The brightness value on the ceiling is influenced by the installation location the incidence of light the position of the sun etc theSenda ...

Страница 6: ...a S Group addresses for the remote control theSenda S group address I is assigned to lighting channel 1 and group address II to lighting channel 2 theSenda B here any group addresses can be assigned to any lighting channel buttons A lighting channel can only be switched on or off if the group address of the lighting channel matches the corresponding button on the remote control The selection of th...

Страница 7: ...light B switching light all on off theSenda Plug theSenda B theSenda P theSenda S Test Presence mode The Test Presence mode is used to check the presence detection and wiring Select ON in the app The presence detector only reacts to movements brightness measurement is switched off After the detector has detected a movement it switches the connected light on At the same time the red LED lights up b...

Страница 8: ...rly The presence detector is in presence test mode or LED motion display is activated The LED detects movements Troubleshooting Fault Cause Light does not switch on or off if presence is detected and in darkness Lux value is set too low detector set to semi automatic light was switched off manually via button or remote control person not within detec tion area obstruction s interrupting detection ...

Страница 9: ... 40 IP 54 surface mounting Protection class II subject to designated installation Cleaning and service Only use a dry soft cloth to clean the device surface Do not use any cleaning agents or solvents Disposal Dispose of device in environmentally sound manner electronic waste Dimensional drawings 10 Contact Theben AG Hohenbergstr 32 72401 Haigerloch GERMANY Phone 49 7474 692 0 Fax 49 7474 692 150 H...

Отзывы: