background image

©Copyright Task Force Tips LLC  2020 

LIY-301 March 26, 2020 Rev00

3

1.0 MEANING OF SAFETY SIGNAL WORDS

A safety related message is identi

fi

 ed by a safety alert symbol and a signal word to indicate the level of risk involved with a particular 

hazard. Per ANSI Z535.6, the de

fi

 nitions of the four signal words are as follows:

DANGER

DANGER indicates a hazardous situation which, if not avoided, will result in death or serious 
injury.

WARNING

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious
injury.

CAUTION

CAUTION indicates a potentially hazardous situation which, if not avoided, could result in minor 
or moderate injury.

NOTICE

NOTICE is used to address practices not related to physical injury.

2.0  SAFETY

DANGER

An inadequate supply of pressure and/or 

fl

 ow will cause an ine

 ective stream and can result 

in injury or death. Choose operating conditions to deliver adequate 

fi

 re suppression. See 

fl

 ow 

graphs.

WARNING

The stream exiting a nozzle is very powerful and capable of causing injury and property damage. 
Make sure the nozzle is securely attached and pointing in a safe direction before water is turned 
on. Do not direct water stream to cause injury or damage to persons or property.

WARNING

Equipment may be damaged if frozen while containing signi

fi

 cant amounts of water. Such damage 

may be di

  cult to detect visually. Subsequent pressurization can lead to injury or death. Any time 

the equipment is subject to possible damage due to freezing, it must be tested and approved for 
use by quali

fi

 ed personnel before being considered safe for use.

WARNING

This equipment is intended for use by trained personnel for 

fi

 re

fi

 ghting. Use of this equipment for 

other purposes may involve hazards not addressed by this manual. Seek appropriate guidance 
and training to reduce risk of injury.

CAUTION

The electric drives are current limited but may still produce enough force to cause injury. To avoid 
injury from a moving monitor:

• Be aware that the monitor may be remotely operated
• Keep hands and 

fi

 ngers away from pinch points on the monitor

• Never operate the manual override while electric controls are in operation

NOTICE

To prevent mechanical damage, do not drop or throw equipment.

3.0  GENERAL INFORMATION

TFT’s Tornado RC compact industrial monitor is designed for both 

fi

 re and industrial applications. This industrial version is certi

fi

 ed 

to ingress protection IP66/67 to limit penetration of dust and moisture into the electronics, ball races and gears. Models can be 
remotely operated and are capable of 

fl

 owing up to 500 gpm (2000 l/min). Heavy duty seals and O-rings help mitigate contamination 

in applications like mining and road construction.

The Tornado RC compact industrial monitor features include:

• High performance seals in both the vertical and horizontal axis minimize penetration of dust and moisture in bearing races
• Override knobs replaced with protective caps and O-rings to minimize penetration of dust and moisture into the worm gear area
• 340° maximum total rotation for the horizontal axis
• Horizontal axis has in

fi

 nitely adjustable travel stops

Содержание TORNADO RC

Страница 1: ... member companies of FEMSA that provide emergency response equipment and services want responders to know and understand the following 1 Firefighting and Emergency Response are inherently dangerous activities requiring proper training in their hazards and the use of extreme caution at all times 2 It is your responsibility to read and understand any user s instructions including purpose and limitat...

Страница 2: ... INSTALLATION SAFE OPERATION AND MAINTENANCE DANGER Understand manual before use Operation of this device without understanding the manual and receiving proper training is a misuse of this equipment Obtain safety information at www tft com serial number TASK FORCE TIPS LLC MADE IN USA tft com 3701 Innovation Way IN 46383 9327 USA 800 348 2686 219 462 6161 Fax 219 464 7155 SECTION 4 1 Monitor Mount...

Страница 3: ...ect to possible damage due to freezing it must be tested and approved for use by qualified personnel before being considered safe for use WARNING This equipment is intended for use by trained personnel for firefighting Use of this equipment for other purposes may involve hazards not addressed by this manual Seek appropriate guidance and training to reduce risk of injury CAUTION The electric drives...

Страница 4: ...ction Force 500 gpm 200 psi 400 lbs 180 kg Horizontal Travel Range 340 170 left and right Vertical Travel Range 135 45 to 90 Maximum Torque Elevation 35 ft lbs 50N m Maximum Torque Horizontal 35 ft lbs 50N m Operating temperature range of fluid 33 to 120 F 1 to 50 C Storage temperature range 40 to 150 F 40 to 65 C Speed Elevation 25 deg sec Speed Horizontal 25 deg sec Mechanical Ingress Protection...

Страница 5: ... B Inlet Pressure Nozzle A Inlet Pressure Maximum Nozzle Inlet Pressure Maximum Monitor Inlet Pressure Monitor Loss Nozzle C Inlet Pressure Figure 3 2 3 Nozzle A flows 250 gpm 950 l min at 100 psi 7 bar K factor 25 Nozzle B flows 500 gpm 1900 l min at 100 psi 7 bar K factor 50 Nozzle C flows 750 gpm 2900 l min at 100 psi 7 bar K factor 75 3 3 USE WITH SALT WATER Use with salt water is permissible ...

Страница 6: ...r and bending forces due to nozzle reaction Nozzle reaction can be as high as 400 lbs 180 kg For flanged connections the use of flat flanges without raised faces is recommended Use a ring gasket as defined in ASME 16 21 or ISO 7483 Tighten flange bolts in an alternating sequence as shown below Tighten sequentially each bolt or stud three times to 30 then 60 and finally 100 of the specified torque ...

Страница 7: ...octite 242 blue to the screw threads and tighten set screws to lock the travel stop position 7 Repeat for the other side INSTALL ADJUSTMENT DISC ON THIS SIDE OF STOP BOLT TO REDUCE DOWNWARD TRAVEL BY 13 FOR EACH DISC INSTALLED STOP BOLT INSTALL ADJUSTMENT DISC ON THIS SIDE OF STOP BOLT TO REDUCE UPWARD TRAVEL BY 13 FOR EACH DISC INSTALLED STRAIGHT AHEAD REFERENCE MARK SET SCREW RIGHT TRAVEL STOP L...

Страница 8: ...ded that the monitor be parked in a position such that the monitor s nozzle rests against a bracket or support surface If a support surface is not available run the elevation against one of its travel stops to take some of the backlash out of the gear drive This will minimize bouncing of the nozzle when the apparatus is traveling Always be sure the monitor is properly parked before moving the truc...

Страница 9: ... and Task Force Tips 5 and 10 inch Stream Straightener friction loss 0 0 3 0 6 0 9 1 2 1 5 1 8 2 1 2 4 0 200 400 600 800 1000 1200 1400 1600 1800 0 3 6 9 12 15 18 21 24 27 30 33 0 100 200 300 400 500 LOSS bar FLOW l min LOSS psi FLOW gpm TORNADO MONITOR 19 psi LOSS AT 500 gpm TORNADO MONITOR 7 psi LOSS AT 300 gpm 5 OR 10 STREAM STRAIGHTENER 3 psi LOSS AT 500 gpm Figure 7 2 7 2 1 STREAM STRAIGHTENE...

Страница 10: ...ch 26 2020 Rev00 10 8 0 EXPLODED VIEW AND PARTS LISTS 8 1 INDUSTRIAL TORNADO RC MONITOR 32 5 23 8 7 15 16 11 14 9 10 30 29 20 27 1 3 4 12 37 2 34 35 36 28 31 26 6 19 24 22 17 2 30 6 8 10 11 12 18 18 21 21 21 27 29 31 32 32 32 35 9 33 26 21 16 25 13 ...

Страница 11: ... THREAD ADAPTER 1 5 M 1 15 VO 145 O RING 145 1 16 VT25 20BH312 87721 3 6 5 2 17 Y5801 T1 TORNADO ELECTRICAL 1 18 Y4954 GEAR MOTOR MONITOR 2 19 Y2130 CONTROL BOX BRACKET 1 20 Y2132 CONTROL BOX SUPPORT 1 21 VT25 28SH625 1 4 28 X 5 8 SOCKET HEAD CAP SCREW 12 22 VW687E259 50 FLAT WASHER 1 4 1 23 Y5250 HOSE 3 8 ID PUSH LOK 1 24 Y5250 HOSE 3 8 ID PUSH LOK 1 25 VFSP2M SS 1 4 NPT PLUG HEX SOCKET 1 26 Y291...

Страница 12: ... 8 7 5 1 6 2 3 4 ITEM NO PART NUMBER DESCRIPTION QTY 1 Y4617 MOTOR SOCKET 1 2 VO 038 O RING 038 1 3 Y4600 KIT GEAR MOTOR W CRIMPED TERMINALS 1 4 Y4616 ENCLOSURE 1 5 Y5213 CONDUIT FITTING 1 6 VO 018 O RING 018 1 7 Y4620 CUP SEAL 1 0625 X 5625 X 1 4 1 8 VT06S32SH312 6 32 X 5 16 SHCS WITH SILICONE HEAD SEAL 4 ...

Страница 13: ...BOARD COMMUNICATIONS RS 485 SERIAL 1 5 Y5100 BOARD MOTOR CONTROL 12 24 VDC 3 6 Y5891 RADIO 900 MHZ 1 7 Y5893 RADIO ADAPTER 2 4 GHZ 1 8 VTM4 0 7PH6 M4 0 7 X 6MM PHILLIPS PAN HEADSCREW 4 9 Y5213 CONDUIT FITTING 2 10 VO 018 O RING 018 2 11 Y5205 STRAIN RELIEF PG11 1 12 Y5245 STRAIN RELIEF PG9 1 13 Y5897 ANTENNA 900 920 MHZ SYSTEMS 1 14 Y5898 ANTENNA 2 4 GHZ SYSTEMS 1 15 Y5248 HEX PLUG PG9 WITH ASSEMB...

Страница 14: ...not allow the exclusion or limitation of incidental or consequential damages so the above may not apply to you TFT shall have no obligation under this limited warranty if the equipment is or has been misused or neglected including failure to provide reasonable maintenance or if there have been accidents to the equipment or if it has been repaired or altered by someone else THIS IS A LIMITED EXPRES...

Страница 15: ...rive parts Clean out debris or replace damaged parts Lack of lubricant Grease see section 10 1 10 3 REPAIR Factory service is available with repair time seldom exceeding one day in our facility Factory serviced equipment is repaired by experienced technicians wet tested to original specifications and promptly returned Repair charges for non warranty items are minimal Any returns should include a n...

Страница 16: ...veling elements rotate freely 10 Nozzle is securely attached BEFORE BEING PLACED BACK IN SERVICE appliances must be inspected to this list 1 All valves open and close smoothly and fully 2 The waterway is clear of obstructions 3 There is no damage to any thread or other type connection 4 The pressure setting of the relief valve if any is set correctly 5 All locks and hold down devices work properly...