background image

EEI

0.20

Energy-saving Pipeline Canned 
Motor Pump

APUMP-HE Series

Installation and 
Operation Manual

 

TFC Group LLP

Содержание Tower APUMP-HE Series

Страница 1: ...EEI 0 20 Energy saving Pipeline Canned Motor Pump APUMP HE Series Installation and Operation Manual TFC Group LLP ...

Страница 2: ...talled in a place that is damp or may be splashed by water 14 Ventilation must be ensured in summer or high ambient temperature conditions to avoid condensation that may cause electrical malfunctions 06 For convenient access of maintaince a shut off valve shall be installed on each side of the pump 15 If there is a risk of frost damage install a frost protection thermostat or drain down the system...

Страница 3: ...d cool place under room temperature Warning Before installation you must carefully read the installation and operation manual The installation and use of the equipment must comply with local regulation and applicable operation standards Warning Those who have weak physical strength react slowly or lack experience and knowledge including children can use this motor pump only under the monitoring an...

Страница 4: ...or and differential pressure controller capable of automatically continuously adjusting motor performance to meet the actual needs of the system This pump is equipped with control panel on the front for easy operation by users stable and variable flow heat supply 2 2 Advantages Easy installation and start up motor pump needs no adjustment and can be readily started and will adjust automatically to ...

Страница 5: ...ion IP 44 3 6 Inlet Pressure Liquid Temperature 85 90 110 Inlet Pressure 0 05bar 0 28bar 1bar 0 5m head 2 8m head 3 7 Pumping Liquid The pumping liquid includes thin clean non corrosive and non explosive liquid which shall not contain any solid particles fiber or mineral oil and the pump must definitely not be used to pump inflammable liquid such as rapeseed oil and gasoline If the pump is used in a ...

Страница 6: ...alling the motor pump in the pipeline the two gaskets supplied must be installed at the inlet and outlet During the installation the motor pump shaft must be horizontal Installation When installing APUMP HE series circulation pump the arrow on the motor 4 Installation 05 APUMP HE ...

Страница 7: ...inlet and outlet and release the pressure 2 Unscrew and remove the four socket head screws that fasten the pump body 3 Rotate the motor to the required position and align the four screw holes 4 Install the four socket head screws again and fasten them clockwise making sure they are fully tightened Changing Position of Junction Box APUMP HE 5 Open the valves at the inlet and outlet ...

Страница 8: ...both sides of motor pump must be closed before removing the socket head screws 4 4 Thermal Insulation of Motor Pump Body Limiting the heat loss of motor pump body and pipeline Motor pump body and pipeline should be thermally insulated to reduce their heat loss Do not insulate or cover the junction box and control panel Caution Note 07 APUMP HE ...

Страница 9: ...5 Electrical Connection 08 APUMP HE ...

Страница 10: ...um contact gap in both poles Check if the supply voltage and frequency are the same as parameters indicated on the nameplate of the motor pump Connect the motor pump and power supply with the plug supplied together with the pump After the power is supplied the indicator lamp on the control panel is ON APUMP HE series circulation motor pump needs no protection from external motor 09 APUMP HE ...

Страница 11: ...The motor pump settings are indicated with different indication lamp areas three three 10 Button Times Indication Lamp Area 0 1 2 AUTO Initial setting MIN MAX Descriptions Self adaptive AUTO Constant Speed Curve Velocity Min Constant Curve Velocity Max Speed 6 3 By pressing the button once at 2 seconds interval the motor pump setting mode will change to the next in sequence A cycle is constituted ...

Страница 12: ...motor pump can memorize its last setting in AUTO mode and continue adjusting the performance automatically AUTO Self Adaptive Mode mode can adjust the performance of motor pump based It may take several minutes or even hours to reach the optimal operation mode after motor pump setting is changed from the optimal setting the Recommended above mention to one of the other optional setting If the opti...

Страница 13: ... Min Velocity Max Highest to Lowest Pressure Curve It runs on the constant curve in a constant velocity In the Velocity Min mode the pump is set to work on the lowest curveunder all working conditions Functions Setting Pump Characteristics Curve 9 Performance Curve 9 1 Every setting of the motor pump has corresponding performance curve Q H curve However AUTO Self Adaptive Mode mode covers just one...

Страница 14: ...s guarantee curve If a specific performance is needed then separate measuring shall be conducted Velocity Max Min curves have all been marked The applicable Kinetic viscosity of the curve υ 0 474 mm s 0 474CcST Curve conditions Test liquid air free water Applicable density of curve ρ 983 2 kg m and liquid temperature 60 9 3 Performance Curve APUMP HE APUMP HE ...

Страница 15: ...er 6 7 8 Highest Liquid Temperature Certification Mark Rotation Direction 9 Protection Grade 10 Insulation class 11 Energy Index 12 Frequency Hz 13 Voltage v Power Watt Electricity ampere Minimum power input in minimum pattern Minimum flow in minimum pattern Maximum system load bearing Mpa 14 Minimum power input in maximum pattern Minimum flow in maximum pattern APUMP HE ...

Страница 16: ... 60Hz PE The pump needs no external protection IP 44 H Max 95 1 0 MPa Liquid Temperature 85 90 110 The sound pressure level of pump is lower than 42dB A 0 40 TF110 The maximum surface temperature is not higher than 125 2 110 Minimum Inlet Pressure 0 005 MPa 0 028 MPa 0 100 MPa 110 110 110 110 90 70 Max To prevent condensation in the junction box and rotor the temperature of pumping liquid of the m...

Страница 17: ...16 11 2 Installation Dimensions Material of Pump Body 45 Product Model Power W Cast Iron Plastic Copper SS Dimension mm L1 65 L2 B1 B2 H1 H2 G 130 82 1301031301 APUMP HE APUMP HE ...

Страница 18: ...l or voltage control opens Connect the circuit breaker Failure of motor pump Return to factory maintenance Under voltage Check whether power supply is in specified range PCB component failure or motor failure Return to factory maintenance Flicker one time High voltage Check whether power supply is in specified range Flicker six time No water in the pump Open the valve and supply water to the pump Fl...

Отзывы: