10
Operation
The Transmitter
Plug into a 120 V AC circuit for locating circuit breakers. Use plug adapter, alligator clips,
and receptacle blade for setups other than 120 V outlets and other tracing applications.
Throughout this manual you will be instructed to use a
“separate or earth ground.” A
“separate or earth ground” must be used for many applications.
A separate ground
simply means connecting the transmitter to a ground that is physically separated from the
area of the wire to be traced. Conduit, outlet boxes, and wire trays carrying the trace line do
not create a separate ground path. For further details, see “Using a Separate Ground” in the
“Tracing the Path of a Hidden Wire (Live Circuit)” section of this manual.
Electric shock hazard:
Contact with live circuits can result in severe injury or death. Use
only the plug and adapters provided with the 2011 when tracing
circuits.
Failure to observe this warning will result in severe injury or death.
Electric shock hazard:
Do not connect to voltage greater than 600 V AC/DC. Check circuit voltage before
•
plugging in transmitter.
Connect ground or neutral first when using clip leads or adapters. Current flows
•
through both the hot and ground or neutral transmitter lead.
Failure to observe these warnings could result in severe injury or death.