Texmate Tiger 380 Series Скачать руководство пользователя страница 5

5

2 February, 2005   Code Sheet V4.01d (NZ1001)

CALIBRATION MODE

CALIBRATION MODES FOR INPUT AND OUTPUT

0 No function

1 On Demand TARE from the PROGRAM button

2 On Demand Single-point Calibration from the PRO-

GRAM button (requires single input source)

3 On Demand 2-point Calibration from the PROGRAM

button (requires dual input source)

4 On Demand Primary Input Compensation Mode from

the PROGRAM button

5 On Demand Manual Loader Mode (no increase /

decrease with HOLD active)

6 -
7 -

Note:

When in the TARE mode, a decimal point appears at the right
of the display indicating that the tare value is NOT zero.

FIRST DIGIT

SECOND DIGIT

0 Manual Calibration

(requires NO input source)

1 2-point Calibration (requires dual input source)

2 Calibrate Thermocouple (requires K type thermocouple

input source)

3 Calibrate RTD (requires RTD 385 input source)

4

Note: For future development

5 Calibrate Analog Output mA/V (Single analog out requires

multimeter connected to pins 2 and 3 on Terminal 4)

6 -
7 -

0 Serial Communications Properties

1 Set Auto Zero Maintenance for 3rd digit

2 Set Averaging Samples & Averaging Window for 3rd digit

3 Totalizer Settings Mode

4 Setup 32-point Linearization Tables

5 Scale Analog Output LOW/HIGH Scale Range Settings

6 -

7 -

OBJECT FOR 2nd DIGIT

0

Result

1

Channel 1

2

Channel 2

3

Channel 3

4

Channel 4

5

Channel 5

6

Channel 6

7

Channel 7

THIRD DIGIT

This is the default 3rd digit box. If not point-
ing to another 3rd digit box, all 2nd digit
settings should be regarded as pointing to
here. It is identified on Pages 6 and 7 by
the following box:

0

-

1

CH1

2

CH2

3

CH3

0

-

1

CH1

2

CH2

3

CH3

4

CH4

5

CH5

6

CH6

7

CH7

0

-

1

CH1

2

CH2

3

CH3

4

CH4

5

CH5

6

CH6

7

CH7

0

-

1

Total 1

2

Total 2

3

Total 3

4

Total 4

5

Total 5

6

Total 6

0

-

1

Port  1

2

Port  2

3

Port  3

Converting °F to °C

See User Notes on Page 21 for a procedure.

See 

CH1 Thermocouple

Calibration

on Page 21

for a procedure.

See 

CH1 RTD

Calibration

on Page 22

for a procedure.

CHANNELS 5, 6, 7

Not available thru front panel controls.

Can only be setup via serial port using
Texmate’s Meter Configuration Utility
program, or accessed via a macro.

See Page 6 for a
breakdown of the
sub-menu

See Page 6 for a
breakdown of the
sub-menu

See Page 7 for a
breakdown of the
sub-menu

2

1

3

+

Single
Analog
Output
(AIC or
AIV)

Analog Output TERMINAL 4

2

1

3

+

+

Dual
Analog
Output
(ADV)

0 Functions Activated

by Pressing the
PROGRAM Button

1 Calibration

Procedures

2 Related Calibration

Functions

3 -

Using the Calibration Mode

1) Press the 

and 

buttons at the same time.

The controller enters the brightness menu [BRI].

Press the 

button again to enter the Calibration

Mode.

2) With [CAL] [XXX] toggling on the display, set the

1st, 2nd, and 3rd digits to their required settings.

3) Press the 

button to enter the selected sub-

menu and select the required calibration settings
from the sub-menus displayed.

4) Press the 

button repeatedly to return to the

operational display (bypassing Codes 1 to 9).

Note:

Once the 3-digit settings have been entered for
an on-demand function [CAL] [0XX], pressing

the 

button saves the selected on-demand

setting and moves to Code 1.

When in the operational display, press the 
button for 4 seconds to activate the selected
on-demand function and display the relevant
sub-menu settings (except [01X] which has no
sub-menu).

DEFAULT 3rd Digit

0

-

1

Analog Output 1

2

Analog Output 2

3

Analog Output 3

4

Analog Output 4

5

Analog Output 5

6

Analog Output 6

7

Analog Output 7

Note: Settings 3-7
not available at
present

0

-

1

Analog Output 1

2

Analog Output 2

3

Analog Output 3

4

Analog Output 4

5

Analog Output 5

6

Analog Output 6

7

Analog Output 7

Note: Settings 3-7
not available at
present

Note: Port 3 only
available on certain
input modules 

Содержание Tiger 380 Series

Страница 1: ...isplay text editing Configuration data copying Downloading macros to the meter Tamper proof settings Tiger 380 Series controllers except the DI 802 have tamper proof lockout switches to prevent users...

Страница 2: ...e holding both buttons press the Prog button then release all three buttons Press and hold the and buttons Programming Tip The Model and Software Code Version check ing procedure can be performed at a...

Страница 3: ...n the controller is powered up Macros can be installed in the controller at the factory during initial programming or by the cus tomer at some later date Macros are written and compiled using the Tige...

Страница 4: ...put pins on the rear of the con troller Display test pin Hold pin Lock pin The Setpoint and Relay Control Settings diagram on Pages 12 to 14 shows the three digit configuration settings that are appli...

Страница 5: ...Port 2 3 Port 3 Converting F to C See User Notes on Page 21 for a procedure See CH1 Thermocouple Calibration on Page 21 for a procedure See CH1 RTD Calibration on Page 22 for a procedure CHANNELS 5 6...

Страница 6: ...t input module data sheet for setup procedures Use buttons to set CAL_LO Use buttons to set CAL_HI 0 Manual Calibration requires NO input source 1 2 point Calibration requires dual input source 2 Cali...

Страница 7: ...signal channel must be selected in the 3rd digit when configuring a lin earization table using the auto setup mode 0 1 CH1 2 CH2 3 CH3 4 CH4 5 CH5 6 CH6 7 CH7 THIRD DIGIT THIRD DIGIT THIRD DIGIT Use...

Страница 8: ...NDARY display is the bargraph display Note 3 These functions are only available on selected input modules Note 4 If Code 1 s display modes have been entered second digit set to 5 6 or 7 the display wi...

Страница 9: ...r 2 2 Output Register 3 3 Output Register 4 4 Output Register 5 5 Output Register 6 6 Output Register 7 7 Smart Input Module Register 1 Code Setup See Note 6 THIRD DIGIT FIRST DIGIT SECOND DIGIT CODE...

Страница 10: ...1 Frequency 999 99 Hz range from 0 01 Hz 2 Frequency 99 999 kHz range from 1 Hz 1 s gate 3 Frequency 500 kHz range from 10 Hz 0 1 s gate 4 Pulse 50 0000 s 100 s resolution 5 Period 999 99 ms 10 s reso...

Страница 11: ...ear FIFO Buffer 3 Reset Buffer Number to 0 Note Setting Code 8 to 3XX resets the data log buffer to 0 Once reset Code 8 must be set back to the required data log buffer setting DATE TIME STAMP OPTIONS...

Страница 12: ...Relay Reset 4 Relay Latched Off 5 Mode Hysteresis Deviation PID SP Flashing SP Tracking 6 Timer Modes OFF Normal Delay Repeat ON Pulse ON 1 Shot ON Repeat OFF Pulse OFF 1 Shot OFF Note In PID Mode al...

Страница 13: ...o 6553 5 65 535 secs On_t 0 1 0 001 to 6553 5 65 535 secs Off time oFF_t 0 1 0 001 to 6553 5 65 535 secs Off time oFF_t 0 1 0 001 to 6553 5 65 535 secs Minimum off time M_of 0 1 to 6553 5 secs Set Up...

Страница 14: ...ct reset trigger from 1 of 4 relay operating edges Reset Trigger Select register to be reset Reset Destination Register Select Reg in reset mode Reset Mode Copy contents of selected register SP1 to SP...

Страница 15: ...ble CONST This mode stores a user defined constant into the selected destination regis ter In most cases this number will be zero but it can be any number I S C This mode stores the current input valu...

Страница 16: ...nual Calibration 2 point Calibration INPUT INPUT 111 ZERO SPAN INPUT INPUT 112 ZERO SPAN INPUT INPUT 113 ZERO SPAN INPUT INPUT 114 ZERO SPAN INPUT INPUT 025 SPAN 035 ZERO SPAN 045 CHANNEL 055 CHANNEL...

Страница 17: ...Analog Output 152 CAL LOW CAL HIGH OUTPUT OUTPUT SOURCE SOURCE 1st DIGIT 2nd DIGIT 3rd DIGIT SUB SETTINGS TC TYPE UNITS TC TYPE UNITS TC TYPE UNITS 121 ZERO SPAN INPUT INPUT Calibrate RTD 122 ZERO SPA...

Страница 18: ...IGIT CODE 4 PRESCALER 1st DIGIT 2nd DIGIT 3rd DIGIT CODE 5 SMART INPUT MODULE SETTINGS 1st DIGIT 2nd DIGIT 3rd DIGIT CODE 6 SMART INPUT MODULE SETTINGS 1st DIGIT 2nd DIGIT 3rd DIGIT CODE 7 1st DIGIT 2...

Страница 19: ...ING SPAN PB INT DER ARW MCT SP TRACKING SPAN PB INT DER ARW MCT SP TRACKING TIMER MODE SETTINGS SPC_1 _ _ 6 SPC_2 SPC_3 SPC_4 SPC_5 SPC_6 _ _ 6 _ _ 6 _ _ 6 _ _ 6 _ _ 6 SPC SETTING NORMALLY OFF PULSED...

Страница 20: ...setpoint with the contents of a selected source register Setpoint Control Settings XX7 Select the contents of one register to be copied into another register by a setpoint The 38 named registers that...

Страница 21: ...he Calibration mode CAL set to 111 and fine tune the thermocouple calibration over the required temperature range Fine Tune Calibration over Specific Temperature Range Follow Steps 1 to 5 for setting...

Страница 22: ...ls 2 and 3 using the following settings CH2 Code 4 210 for type 385 CAL 132 to calibrate type 385 Code 4 2X0 to select specific RTD CAL 112 to fine tune selected RTD CH3 Code 5 X31 for type 385 CAL 13...

Отзывы: