background image

Texmate, Inc. Tel. (760) 598-9899  •  www.texmate.com

Page 18

Apr-18-2016  DI-60A 320 DS (NZ302)_UL April 2016

FRONT PANEL ANNUNCIATORS

0  ON when Setpoints are ON (relay 

energized)

1  ON when Setpoints are OFF (relay 

de-energized)

2  Always OFF. 

See Note 1

3  LED SP1 ON indicates RISING 

signal trend.

  LED SP2 ON indicates FALLING 

signal trend.

 DISPLAY FUNCTIONS

SELECT DATA SOURCE FOR

0  Primary Display

1  Second Display. See Note 2
2  Third Display. See Note 2
3 Peak/Valley
4  Analog Output 1
5  Analog Output 2
6  Totalizer 1
7  Totalizer 2

CODE 1 – DISPLAY CONFIGURATION

0 Result

1  Channel 1
2  Channel 2
3  Channel 3
4  Channel 4
5  Default Display
6  Total 1
7  Total 2

0 Result

1  Channel 1
2  Channel 2
3  Channel 3
4  Channel 4
5  Default Display
6  Total 1
7  Total 2

SELECT DISPLAY FORMAT FOR

SELECT TEXT CHARACTER FOR

FIRST DIGIT

SECOND DIGIT

THIRD DIGIT

See diagram below

See diagram below

See diagram below

Select Data Source

Select Display Format

Select Last Digit Text Character

[TOT_1]

[TOT_2]

[TARE]

[VALLEY]

Select Data Source

Display Format Mode

Program the three digits to the required 
display function mode

0  Normal Display Mode (i.e. operational display 

shows selected register) updates every 0.5 
seconds

1  Manual Loader Mode (Direct Display). 

See Note*

2  Update at sample rate selected in Code 2
3 -
4 -

5  Select data source as per 3rd digit. 

See Note 4

6  Select display format as per 3rd digit. 

See Note 4

7  Select text character as per 3rd digit. 

See Note 4

Note*:

For the Manual Loader Mode (Direct Display) to work, with Code 1 set to [X54] the data source for 

the analog output (1 or 2) must be set to [diSP].
Operating range upper and lower limits can be set for the manual loader mode.
The setpoint activation values for setpoint 5 becomes the upper limit and setpoint 6 becomes the 

lower limit.
When either the direct display or on demand manual loader mode is programmed into the meter, the 

values for setpoint 5 and setpoint 6 are activated as upper and lower limits.

 

See Analog Output Supplement for further details.

Note 1:

LED annunciators are always off, except when the meter is in single channel VOLTAGE or CURRENT 

mode and Code 3 = [X6X], or Code 7 = [X6X] in which case the LEDs indicate which 32-point table 

has been selected from the rear pins (SP1 = Table 1, SP2 = Table 2, SP3 = Table 3, SP4 = Table 4).

LAST DIGIT ROUNDING

0  No rounding

1  Rounding by 2’s
2  Rounding by 5’s
3  Rounding by 10’s

Note:

Selecting 1, 2, or 3 

in the 2nd digit of 

this mode config-

ures the display of 

the selected channel 

as a clock.

DISPLAY UNITS

0 Decimal

1  24-hour clock mode
  Hours: Minutes: 

Seconds (6-digit ver-
sion only)

2  12-hour clock mode 

(12:30 am is displayed 
as 12:30A. 12:30 pm is 
displayed as 12:30P)

3  24-hour clock mode
  Days: Hours:Minutes 

(6-digit version only)

4 -
5 -
6 -
7 Octal

DECIMAL POINT PLACEMENT
0  No decimal point

1   XX.XX.XX
2  X.XXXXX
3   X.XXXX
4  

X.XXX

5  

X.XX

6  

X.X

7  Decimal Point set from the 

rear (X.XXXX to XXXXX)

  See Note 3.
  Also See Note 4.

FIRST DIGIT

SECOND DIGIT

THIRD DIGIT

Note 2:

These options are only for use with meters that have more than one display. With bargraph meters 

the PRIMARY display is the digital display, and the SECONDARY display is the bargraph display. 

Note 3:

These functions are only available on selected input modules.

Note 4:

If Code 1's display modes have been entered (second digit set to 5, 6, or 7), the display will cycle 

between Code 1 and the display functions mode each time the PROGRAM button is pressed. To 

leave the cycle, the Code 1 digits must be reset to any relevant function between [X00] to [X20]. 

This takes you into Code 2.

Initial Setup Procedures

[CodE_1] - Display Configuration continued

Use the     buttons to cycle through the 
Registers Menu and Registers (1 to 244) 
to select data source for displays, peak 
and valley, totalizers and analog output 
(also see page 36).

[RESULT]

[CH1]

[CH2]

[CH3]

[CH4]

[PEAK]

[DISP]

[  1]

[ 10]

[100]

[200]

[244]

Use the   button to cycle through the 
menu, and the   button to cycle back.

Select Last Digit Text Character

P

P

Содержание DI-60AE

Страница 1: ...dback and PID output Scalable from 1 count to full scale Dual independent totalizers to integrate input signals 6 super smart independently programmable setpoints with 8 selectable functions including...

Страница 2: ...smart setpoints with fully configurable hysteresis on and off delays one shot pulse and repeat timers latching dual PID setpoint tracking resetting of registers initiat ing of logging and printing Sig...

Страница 3: ...ngle Analog Output Fully scalable from 4 to 20mA or 0 to 20mA or reverse and selectable for 0 to 10VDC or reverse 2 Dual Analog Output Fully scalable from 0 to 10VDC or reverse Outputs continued Analo...

Страница 4: ...ta source for OUTPUT PROCESSING Select data source for Setpoint 1 2 3 4 5 6 Analog output 1 2 Data logging Select data source for DISPLAY PROCESSING Select data source for Display 1 Default Display Ch...

Страница 5: ...Page 5 Apr 18 2016 DI 60A 320 DS NZ302 _UL April 2016 Texmate Inc Tel 760 598 9899 www texmate com THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 6: ...total 2 Once into the viewing routine pressing the button moves through each displayed parameter See Display with Faceplate and Bezel diagram Annunciator LEDs The annunciator LEDs can be programmed to...

Страница 7: ...have to be connected to the COMMON pin pin 11 The LOCK pin can also be configured in Code 9 to carry out the following functions see Meter Programming Codes on Page 9 Reset channel 1 XX1 Reset channel...

Страница 8: ...indicates that the buttons must be pressed at the same time The only exception to this rule is when carrying out the Model and Software Code Version Check Programming procedures are graphic based with...

Страница 9: ...P The Setpoint and Relay Control Settings diagram on Pages 34 and 35 shows the three digit config uration settings that are applied individually to each setpoint See Page 33 for an example proce dure...

Страница 10: ...lowing selected on demand modes On Demand Modes Tare Single point calibration Two point calibration Primary input compensation Manual loader manual offset Print View Mode SP_1 SP_3 SP_5 PEAK TOT_1 CH3...

Страница 11: ...eventing them from being reprogrammed Any codes that have not been blanked out are still visible and can be reprogrammed Turning code blanking OFF means all meter programming codes are visible when yo...

Страница 12: ...Display Operational Display Example OR Press at same time Press at same time Press at same time Press at same time Enter Brightness Mode Adjust brightness to 7 Save brightness setting Exit Brightness...

Страница 13: ...odule Note This function is not available on all input modules 5 Calibrate Analog Output requires multimeter con nected to pins 16 and 17 6 7 0 Serial Communications Properties 1 Set Auto Zero Mainten...

Страница 14: ...m 1 to 255 samples The averaging window can be set to between 1 and 65535 counts See the calibration modes diagram on Page 13 showing a breakdown of 1st 2nd and 3rd digits See Input Signal Sampling Sh...

Страница 15: ...the HIGH input signal Select the No Function Calibration Mode 000 Save Calibration Mode 000 setting and enter Code 1 Exit code 1 and return to operational display 5 1 Adjust display to desired readin...

Страница 16: ...6 To Step 7 OR From Step 6 OR OR Press 1 Press 1 Press 1 Press 1 Press 1 Press at same time Press at same time Press at same time Press at same time Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 St...

Страница 17: ...Functions Mode The display functions mode is configured by changing the 2nd and 3rd digits in Code 1 Selecting X5X enters the Data Source sub menu Selecting X6X enters the Display Format sub menu Sele...

Страница 18: ...eter the values for setpoint 5 and setpoint 6 are activated as upper and lower limits See Analog Output Supplement for further details Note 1 LED annunciators are always off except when the meter is i...

Страница 19: ...CONFIGURE DATA SOURCE Go to Source selection Go to the next selection Example Procedure Configure the Primary Display with the display diSP as the data source by setting Code 1 to X50 See diagram at t...

Страница 20: ...ons setting Enter Brightness Mode Pass Brightness and Calibration Modes and enter Code 1 Save entered value Save Code setting 0 No rounding 1 Rounding by 2 s 2 Rounding by 5 s 3 Rounding by 10 s Confi...

Страница 21: ...Operational Display Operational Display Example Press 2 Press at same time Press at same time Press 1 OR Step 4 Press at same time Press at same time Step 6 Prog SP1 SP2 SP4 SP3 SP5 SP6 Prog SP1 SP2...

Страница 22: ...nciators Procedure Prog SP1 SP2 SP4 SP3 SP5 SP6 Prog SP1 SP2 SP4 SP3 SP5 SP6 Prog SP1 SP2 SP4 SP3 SP5 SP6 Prog SP1 SP2 SP4 SP3 SP5 SP6 X X Prog SP1 SP2 SP4 SP3 SP5 SP6 CONFIGURE UPDATE AT SAMPLE RATE...

Страница 23: ...pe of TC 2 RTD 3 wire 3rd digit selects type of RTD 3 RTD 2 or 4 wire 3rd digit selects type of RTD 4 Frequency 5 Period 6 Counter 7 Smart Input Module CODE 2 CHANNEL 1 MEASUREMENT TASK AND SAMPLING R...

Страница 24: ...ith or without a Day Month Year or Hours Minutes Seconds time stamp Time stamp settings are configured in Code 8 Post processing functions refer to functions that occur to the input after it has been...

Страница 25: ...surement task and 32 point linearization for CH2 is config ured in the 1st and 2nd digits of Code 4 The diagram opposite lists the available configuration selections in Code 4 Example Procedure Config...

Страница 26: ...t X Not relevant Save CH3 setting Exit Code 6 Return to Operational Display Enter Brightness Mode FOR THERMOCOUPLE 0 Type J 1 Type K 2 Type R 3 Type S 4 Type T 5 Type B 6 Type N 7 Select user defined...

Страница 27: ...Time Clock and Timer 3rd digit selects type 5 6 7 Smart Input Module 3rd digit selects register FOR SMART INPUT MODULE 0 Output Register 1 1 Output Register 2 2 Output Register 3 3 Output Register 4...

Страница 28: ...sult using Table 2 See Note 5 3 32 point Linearization on Result using Table 3 See Note 5 4 32 point Linearization on Result using Table 4 See Note 5 5 125 point Linearization on Result Tables 1 to 4...

Страница 29: ...S LOG OR PRINT TRIGGER 0 No trigger 1 Trigger on Demand from PROGRAM Button 2 Trigger on Demand from F1 Button 3 Trigger on Demand from F2 Button 4 Trigger on Demand from HOLD Pin 5 Trigger on Demand...

Страница 30: ...y output modules support a combination of 4 5 A Form A and 9 10 A Form C relays providing 12 configuration options A solid state relay SSR output module supports 300 V 210 mA DC SSRs A 22 opto isolate...

Страница 31: ...can be programmed in relay latching modes Setpoint Reset Trigger Setpoints can be programmed to reset selected registers or be manually reset They can also trigger a data print or a data log DUAL PID...

Страница 32: ...N Pulsed OFF Modes These are delay modes were the relay is normally on and pulses off when the setpoint activates 1 Shot OFF mode Programmable Minimum OFF time SP ON SP OFF 1 Shot OFF Mode Prog Min OF...

Страница 33: ...ly cycle thru SPC_1 Save SP1 control settings Operational Display Operational Display Exit SPC_2 and return to operational display Save SP1 activation value setting Select CH1 as the SP1 activation so...

Страница 34: ...setpoint value with RISING INPUT SIGNAL INITIAL START UP INHIBIT SP Activation Source 0 Activate Setpoint Source from Selected Register 1 Select Source for Setpoint Note X1X is a register selection pr...

Страница 35: ...o XX0 DOM 0 0 to 6553 5 secs Minimum on time M_on 0 0 to 6553 5 secs On time on _t 0 0 0 001 to 6553 5 65 535 secs DOB 0 0 to 6553 5 secs Off time oFF_t 0 0 0 001 to 6553 5 65 535 secs DOB 0 0 0 001 t...

Страница 36: ...t hold the button down while cycling through the decades and release it when oFF or tArE appears Registers that Should Not be Used The following registers are contained within the selectable 1 to 244...

Страница 37: ...r HI Voltage Fuse for LO Voltage Isolated Feed Back Isolated Switching Power Supply Controller 5 VDC 18 VDC ISO 5 VDC 5 VDC 5 VDC GND 24 VDC GND LC Filter 1 2 3 4 5 6 7 8 9 10 RELAY MODULES NO3 COM 1...

Страница 38: ...29 27 26 25 Options 4A 4A Order Code OR11 OR12 OR23 OR14 4A 4A 4A 4A 10A OR15 OR16 SP2 SP4 SP1 SP3 9A 9A 9A 9A 9A 9A 9A 9A SP3 SP1 SP4 SP2 Relay Modules with up to two 4 5A Form A Relays and up to tw...

Страница 39: ...and process control applications Modular construction ensures you don t have to pay for unnecessary hardware Simply order the input and output options to suit your application Input Signal Conditioni...

Страница 40: ...20V 2V SPAN Increase Decrease ON OFF 24V Exc Input Signal Conditioner Main PCB Shown with optional Input Signal Conditioning Module Ordered Separately Hi Volt Order Code PS1 Lo Volt Order Code PS2 ID0...

Страница 41: ...oisy components Shielding cables for input output leads is recommended with shield connection to earth ground near the meter preferred 4 A circuit breaker or disconnect switch is required to disconnec...

Страница 42: ...3 Code 3 Channel 1 Post Processing and Serial Mode Functions 24 Code 4 Channel 2 Measurement Task and Sampling Rate 25 Code 5 Channel 3 Functions 26 Code 6 Channel 4 Functions 27 Code 7 Result Process...

Страница 43: ...d Not Be Selected 36 Resetting and Incrementing Using Setpoints 36 Relay Logic Output Modules 38 Serial Communication Configuration 24 Pinouts 38 Setpoint Programming Mode 30 35 Data Logging 31 Data P...

Страница 44: ...xmate com Texmate has facilities in Japan Taiwan and Thailand Case Dimensions Clear Lockable NEMA 4X Splash Proof Cover P N OP N4 96x48 The 96x48mm case is particularly suitable for mounting in mosaic...

Отзывы: