26
4.4.1 SW1 position functions
Refer to Table 4-3 for description of SW1 position functions. The factory default setting is Down
for all positions.
Table 4-3: SW1 positions functions
Position
Function
Down(Factory default)
Up
SW1-1
Output Voltage remote
analog programming
Output Voltage
programmed by Front Panel
Output Voltage
programmed by remote
analog voltage
SW1-2
Output Current limit
remote analog programming
Output Current limit
programmed by Front Panel
Output current limit
programmed by remote
analog voltage
SW1-3
Programming range select
(Remote voltage/resistive)
0-5V/(0-5kΩ)
0-10V/(0-10kΩ)
SW1-4
Output Voltage and
Current Monitoring range
0-5V
0-10V
SW1-5 Shut Off logic select
On: High (2-15V) or Open
Off: Low (0-0.6V) or Short
On: Low (0-0.6V) or Short
Off: High (2-15V) or Open
SW1-6 RS232/485 select
RS232 interface
RS485 interface
SW1-7
Output Voltage resistive
programming
Output Voltage
programmed by Front Panel
Output Voltage
programmed by external
resistor
SW1-8
Output Current limit
resistive programming
Output Current limit
programmed by Front Panel
Output Current limit
programmed by external
resistor
SW1-9 Enable/Disable control
Rear panel Enable/Disable
control is not active
Rear pane, Enable/Disable
control is active
4.4.2 Resetting the SW1 switch
Before making any changes to the SW1 switch setting, disable the power supply output by
pressing the front panel OUTPUT button. Ensure that the output voltage falls to zero and OUTPUT
LED is off, and then use any small flat-bladed screwdriver to change the SW1 switch setting.