3. Vout resistor programming
---
0~100%, 0~5/0~10kΩ full scale, user select. Accuracy and linearity: +/-1% of rated Vout.
4. Iout resistor programming
---
0~100%, 0~5/0~10kΩfull scale, user select. Accuracy and linearity: +/-1.5% of rated Iout.
5. On/off control
---
By electrical Voltage: 0~0.6V/2~15V or dry contact, user selectable logic.
6. Output current monitor
---
0~5V or 0~10V, user selectable. Accuracy: 1%.
7. Output voltage monitor
---
0~5V or 0~10V, user selectable. Accuracy: 1%.
8. Power supply OK signal
---
4~5V-OK, 0V-Fail. 500ohm series resistance.
9. Parallel operation
---
Possible, up to 4 units in master/slave mode with single wire current balance connection.
10. Series operation
---
Possible (with external diodes), up to 2 units.
11. CV/CC indicator
---
CV: TTL high (4~5V), source current: 10mA, CC: TTL low (0~0.6V), sink current: 10mA.
12. Enable/Disable
---
Dry contact. Open: off, Short: on. Max. voltage at Enable/Disable in: 6V.
13. Local/Remote
analog control
---
By electrical signal or Open/Short: 0~0.6V or short: Remote, 4~5V or open: Local.
14.Local/Remote
Analog status signal.
---
Open collector. Local: Open, Remote: On, Maximum voltage: 30V, maximum sink current: 5mA.
2.6.
PROGRAMMING AND READBACK (RS232/485, Optional IEEE Interface) (At the time of 23℃
±5℃)
1. Vout programming accuracy
---
0.1%+0.05% of rated output voltage
2. Iout programming accuracy
---
0.1%+0.15% of rated output current
3. Vout programming resolution
---
0.012% of full scale
4. Iout programming resolution
---
0.012% of full scale
5. Vout readback accuracy
---
0.1%+0.15% of rated output voltage
6. Iout readback accuracy
---
0.1%+0.35% of rated output current
7. Vout readback resolution
---
0.012% of full scale
8. Iout readback resolution
---
0.012% of full scale
2.7.
PROTECTIVE FUNCTIONS
V
6
8
12.5
20
30
40
60
80
100
150
300
600
1.Foldback protection
--
Output shut-down when power supply change from CV to CC User presetable.
2.Over-voltage protection
--
Inverter shut-down, manual reset by AC input recycle or by OUT button.
3.Over-voltage trip point
V
0.5~7.5 0.5~10 1~15
1~24
2~36
2~44
5~66
5~88 5~110 5~165 5~330 5~660
4.Output under voltage limit
--
Preset by front panel or communication port. Prevents from adjusting Vout bellow limit.
Raises the PS_OK signal in case of output voltage is bellow limit.
5.Over temperature protection
--
User selectable, latched or non latched
2.8.
FRONT PANEL
--
Vout/Iout manual adjust by separate encoders (coarse and fine adjustment).
--
OVP/UVL manual adjust by Vout. Adjust encoder.
--
Address selection by Voltage Adjust encoder. No of addresses: 31.
--
Go to local control.
--
Output on/off
--
AC on/off
--
Front panel Lock
--
Foldback control
--
Baud rate selection: 1200, 2400, 4800, 9600, and 19200.
1.Control functions
--
Re-start modes (automatic restart, safe mode).
--
Vout: 4 digits, accuracy: 0.5% of rated output v/-1count.
2.Display
--
Iout: 4 digits, accuracy: 0.5% of rated output c/-1count.
3.Indications
--
VOLTAGE, CURRENT, ALARM, FINE, PREVIEW, FOLDBACK, LOCAL, OUTPUT ON.
2.9.
ENVIRONMENTAL CONDITIONS
1. Operating temperature
--
0~50℃, 100% load.
2. Storage temperature
--
-20~70℃
3. Operating humidity
%
30~90% RH (no condensation).
4. Storage humidity
%
10~95% RH (no condensation).
5. Altitude
--
Maximum 3000m. Derate output current by 2%/100m above 2000m. Alternatively, derate maximum ambient
temperature by 1℃/100m above 2000m.