recommend that the unit is initially powered on battery only for no longer
than 24 hours.
1.6 Installing Multiple Units
The following diagram illustrates how to wire multiple units together:
If the first unit is opened it will self-activate and a tamper will be signalled to the
control panel. If the second unit is opened both units will self-activate and a
tamper will be signalled to the control panel.
If more than one unit is connected to an installation, the current demand may
exceed the rated current output of the control panel. This can be avoided by
selecting Low Current (LC) or SCB mode on one or more of the connected units.
Low Current Mode
Low current mode* allows the sounder current draw from the control panel to be
reduced whilst maintaining significant alarm volume. To select low current mode,
ensure the SAB/SCB jumper is in the SAB position and move the LC jumper to the
Low Current on position. Details on current draw can be found in the technical
specification (
).
* Not available on all models
SCB Mode
In SCB mode the unit draws the majority of its sounding current from the built-in