ACKF01_GB_00
TEXA S.p.A. 109/122
When the vacuum phase is completed, the unit performs a
connection leak test:
The Display shows:
F l u s h i n g
L e a k t e s t .
S e c . x x x x
m B . x x x x
Default leak check time is
240 seconds
, but it can be shorted by
pressing
UP
or
DOWN
.
You can also cancel and completely quit
the program by pressing the
Stop
button.
LEAKAGE WARNING!
If a leak is detected the following message appears with also the
current vacuum value. Verify connection to system and/or components.
L e a k a g e !
E N T E R t o c o n t i n u e
m B . x x x x
Press
Stop
to cancel and quit the program for fixing a major problem
(Important leak). Or press
Enter
to continue if you could solve
immediately the issue. (Tightness of one connection).
If no leakage has been detected, the system is ready for flushing.
The Display shows:
O p e n o n l y H P v a l v e
C l o s e L P v a l v e
E N T E R t o c o n f i r m .
Press
Enter
to confirm.
Now the refrigerant flushing phase is starting.
The refrigerant flows into the system, and arrives inside the flushing canister.
The Display shows:
F l u s h i n g
A / C s y s t e m
F i l l i n g p h a s e
Q u a n t i t y g . x x x x x