6 Commissioning
63
tour data can be printed out by a Testo printer via infrared (0554 0549). A
cockpit unit can save several different tours with time marks.
A maximum of 50 Saveris cockpit units can be integrated into a testo
Saveris measurement data monitoring system.
The Saveris cockpit unit can display the measurement data of 2 groups
each comprising 4 radio data loggers (max. 32 channels). The data are
transferred every 15 minutes. Alarm events are forwarded immediately
to the Saveris cockpit unit.
The Saveris cockpit unit is only used to display the measurement data,
not for permanent storage. It is therefore important to ensure that the
mobile radio data loggers come into radio contact with a Saveris
extender or the Saveris base on a regular basis, depending on the
measuring cycle, in order to enable the measurement data to be
transferred.
The reading output can be configured via the testo Saveris software.
The integration of a Saveris cockpit unit involves two steps:
1
Register Saveris cockpit unit on the Saveris base.
2
Mount Saveris cockpit unit and supply with power.
6.9.8.1
Registering Saveris cockpit unit
You can register a maximum of 50 Saveris cockpit units on the Saveris
base.
1
On the Saveris base, use the
[▼]
key to switch to the
Info System
menu.
2
Press
[Enter]
to call up the
Login
function.
The status bar on the display
indicates that the Saveris base is
ready to detect the Saveris cockpit
unit.