IV. UPS INSTALLATION
4.1
Introduction
WARNING!!!
•
Do not apply electrical power to the UPS equipment before the arrival of authorized service personnel.
•
The UPS equipment should be installed by a qualified service personnel.
•
The connection of the batteries and the maintenance should be done by the qualified service personnel.
•
Do not make short- circuit to the batteries poles. Because of the high short-circuit current, it has the danger
of electrical shock or burn.
•
Eye protection should be worn to prevent injury from accidental electrical arcs. Remove rings, watches and
all metal objects. Only use tools with insulated handles. Wear rubber gloves.
This chapter contains location installation information of the UPS and the batteries. All the establishments
have their own specialties and needs. So in this part the installation procedure is not being explain step by
step. Instead general procedure and the applications are explained for the technical personnel.
.
4.2 Unpacking
The UPS is packed and enclosed in a structural cardboard carton to protect it from damage.
1) Inspect for damage that may have occurred during the shipment If any damage is noted, call the shipper
immediately and retain the shipping carton and the UPS.
2) Carefully open the carton and take the UPS out.
3) Retain the carton and packing material for future use.
Unit package contents:
1) A user manual and Guarantee certificate.
2) Battery cabinet and/or shelf (Optional)
3) Battery connection cables.
4) Battery Circuit Breaker (Optional)
4.3 Equipment Positioning
1) The equipment’s installation place must be an easy serving place.
2) Install the UPS in a protected area with adequate air flow and free of excessive dust.
3) You must therefore allow for a minimum gap of 250 mm behind the unit to allow adequate air flow
4) Select a suitable place (temperature is between 0
°
C and 40
°
C) and the relative humidity (%90 max)
5) It is recommended to air-conditioned the room (24
°
C)
6) Temperature is a major factor in determining the battery life and capacity. Battery manufacturers
quote figures for an operating temperature of 20
°
C. On a normal installation the battery temperature
is maintained between 15
°
C and 25
°
C. Keep batteries away from main heat sources or main air inlets
etc.
7) In case of an operating the UPS in a dusty place, clean the air with a suitable air filtration system.
8) Keep out of your equipment from the explosive and flammable items.
9) Avoid direct sunlight, rain, and high humidity.
WARNING!!!
Check the capacity of the forklift if it is available for lifting.
DO NOT MOVE THE BATTERY CABINET WHILE THE BATTERIES ARE INSTALLED.