8
2.2.5 USER OPTIONS Menu items
From this menu the user selects some important parameters and apply them.
Submenu item
Function
1 MODE: ONLINE
4 Operating modes can be selected using up and down buttons.
ONLINE
: normal operating mode.
PARALLEL
: Symmetric parallel operation mode of 2 UPS’s.
HOT STANDBY
: 1 UPS is master and 1 UPS is redundant operating mode.
REDUNDANT
: 2 UPS’s redundant operating mode.
→
Press ENTER for 3 seconds to save the selected mode.
2 UPS No : 001
By using PLUS and MINUS keys you can change number 0 to 3.
In parallel operation select different numbers for each UPS. If you select the
same number DUBL UPS NUMBER message tells the fault.
→
press ENTER for 3 seconds and then the selection is valid
3 BYP.PROTECT ON
By using
↔
key you can change on and off options.
ON
: if the bypass source is out of tolerance, UPS turns off load power in
case of a fault or overload..
OFF
: UPS turn off load power only during bypass moves. If bypass period
is completed UPS continues to supply the load.
→
press ENTER for 3 seconds and then the selection is valid
4 RESTART:ON/OFF
By using
↔
key you can change on and off options.
ON
: during mains failure at the and of battery discharge UPS shut-
downs,after mains restored UPS starts again.
(battery trip out is on every time)
OFF
: after mains restoration UPS doesn’t start again.
(battery trip out is off)
→
press ENTER for 3 seconds and then the selection is valid
5 REMOTE : ENABLE
By using
↔
key you can change enable and disable options.
Enable
: remote battery test, shutdown and bypass functions are enabled
disable
: these functions are disabled
→
press ENTER for 3 seconds and then the selection is valid
6
CENTER-EDGE
LANGUAGE
Turkish – English is selected.
7 BOOST TIME
Quick charge period of 1-15 hours is configured. Boost is disabled if 0 is
entered while boost charge.
8 BOOST
Manual – automatic modes are selected using
↔
key. Normal charge mode
operates in manual selection. In automatic mode, if the line is off, at each
time input line voltage is restored the boost charge starts automatically.
9 DIREK START: ON
ON: UPS at the beginning starts automatically.
OFF: The inverter is in standby.
The inverter starts and the output forms when ENTER is pressed. Until this
moment the load is supplied from the by-pass.
10 XFER MOD: CURRENT
CURRENT : Switches into bypass without delay when the current is zero
DELAY : If the UPS is not synchron, switching into bypass takes place with
15 ms. Delay.
11 RELAY COMMON
12 RL4 COMMON
Alarms : COMMON,RL4, BATT. LOW, OUTPUT H
İ
GH, OVERLOAD, L
İ
NE
FAILURE, OVER TEMP., OVER CURRENT, OUTPUT LOW, BATTERY
H
İ
GH, BATT. FAULT, BY-PASS BAD, BOOST CHARGE, MANUEL BYP,
ROT. PHASE, OUTP. OFF, UPS FAILURE.
RL4 relay can be defined for any desired alarm.
13 RL5 COMMON
Alarms : COMMON,RL4, BATT. LOW, OUTPUT H
İ
GH, OVERLOAD, L
İ
NE
FAILURE, OVER TEMP., OVER CURRENT, OUTPUT LOW, BATTERY
H
İ
GH, BATT. FAULT, BY-PASS BAD, BOOST CHARGE, MANUEL BYP,
ROT. PHASE, OUTP. OFF, UPS FAILURE.
RL5 relay can be defined for any desired alarm.