7
Fig.2-6 ECO Mode operation diagram
Note
There is a short interruption time (less than 10ms) when transfer from ECO mode to battery mode,
it must be sure that the interruption has no effect on loads.
2.3.6 Auto-restart Mode
The battery may become exhausted following an extended AC mains failure. The
inverter shuts down when the battery reaches the End of Discharge Voltage (EOD).
The UPS may be programmed to “System Auto Start Mode after EOD”. The system
starts after a delay time when the AC mains input recovers. The mode and the delay
time are programmed by the commissioning engineer.
2.3.7 Frequency Converter Mode
By setting the UPS to Frequency Converter mode, the UPS could present a stable
output of fixed frequency (50 or 60Hz), and the bypass static switch is not available.
2.3.8 Self Aging Mode
If users want to burn in UPS without load, could set the UPS as Self Aging Mode, in
this mode, the current flow through rectifier, inverter, and back to input through
bypass. It needs only 5% loss to burn in UPS with 100% load.
Fig.2-7 self aging operation diagram