56-21XX and 56-22XX Series

DOPSM2097X012

10

Section 6: Installation and  

Start-Up Procedures

October 2016

Section 6: Installation and Start-Up Procedures

Failure to follow these instructions or to properly install and maintain this equipment could 
result in an explosion, fire and/or chemical contamination causing property damage and 
personal injury or death.

TESCOM regulators must be installed, operated and maintained in accordance with federal, state 
and local codes, rules and regulations . 
If the regulator vents gas or a leak develops in the system, service to the unit may be required . 
Failure to correct trouble could result in a hazardous condition . 

Installation, operation and maintenance procedures performed by unqualified personnel may 

result in improper adjustment and unsafe operation . Either condition may result in equipment 

damage or personal injury. Call a qualified personnel when installing, operating, and maintaining 

the 56-21XX and 56-22XX Series regulator .

 

Personal injury, equipment damage or leakage due to escaping fluid may result if needle 

valves are used to isolate the pressure reducing regulator. It is strongly recommended that 

block valves be used to properly isolate the regulator from system. 

Personal injury, equipment damage or leakage due to escaping accumulated fluid or bursting of 

pressure-containing parts may result if this regulator is:

• 

Over-pressured

•  Used with incompatible process fluid
•   Installed where service conditions could exceed the limits given in the specifications section 

and on the appropriate nameplate

• 

 Where conditions exceed any ratings of adjacent piping or piping connections . To avoid such 
injury or damage, provide pressure-relieving or pressure-limiting devices to prevent service 
conditions from exceeding those limits

Confirm with gauges that there is zero pressure in the system prior to installation:

Note: Refer to the Installation Diagram for additional information .

1 . 

Re-tighten fittings on assembly as they may have loosened during shipping.

2 . 

Rotate valve hand knob (B) clockwise until it stops turning. This will close the valve 
which will prevent pressurized flow through the regulator/valve assembly.

3 . 

Close the inlet (C) and outlet (A) block and bleed valves surrounding the regulator and 

pressurize the supply side or inlet side of the system .

4 . 

Install the regulator/valve assembly with the inlet port of regulator (E) connected to 

the supply or inlet piping of the system and connect the outlet port to the downstream 

piping in the system using plumbing supplier specified torque values.

5 . 

Slowly open the inlet block valve (C) to apply pressure to the inlet of the 56-2XXX Series 
assembly regulator (E).

Содержание 56-2100

Страница 1: ...nd Service Manual DOPSM2097X012 October 2016 This manual is available in multiple languages online at www tescom com Do not attempt to select install use or maintain this product until you have read a...

Страница 2: ......

Страница 3: ...fety Installation and Operations Precautions 4 2 1 Regulators and Valves 4 2 2 Installation 6 2 3 Repair Service 6 Section 3 Introduction 7 Section 4 Specifications 8 Section 5 Drawings 8 5 1 Installa...

Страница 4: ...rmation reaches the operator and stays with the product after installation Do not permit untrained personnel to install use or maintain this regulator valve or accessory Improper selection improper in...

Страница 5: ...ressure to the system gradually avoiding a sudden surge of fluid or pressure shock to the equipment in the system 10 Regulators are not shut off devices Install a pressure relief device downstream of...

Страница 6: ...ded for use with all fluids 25 Do not bleed system by loosening fittings unless specified by Instruction Manual 26 Prevent icing of the equipment by removing excess moisture from the gas 27 Always use...

Страница 7: ...siveness and density of chemical fluids the fluid media and full system must be considered by the user when selecting a product This is required to ensure regulator performance user safety flow capabi...

Страница 8: ...mum Inlet Pressure 56 22XX Series 10 000 psig 690 bar MaximumOutletPressure56 21XXSeries 14 800 psig 1034 bar MaximumOutletPressure56 22XXSeries 4000 psig 276 bar Operating Temperature All 0 to 165 F...

Страница 9: ...ctober 2016 5 2 Installation Diagram for 56 22XX Series Letter call outs are referenced in the Installation and Start Up Procedures section of this manual OUTLET BLOCK VALVE INLET BLOCK VALVE 56 22XX...

Страница 10: ...ury equipment damage or leakage due to escaping accumulated fluid or bursting of pressure containing parts may result if this regulator is Over pressured Used with incompatible process fluid Installed...

Страница 11: ...ow through the system 10 Verify the regulator valve assembly s outlet pressure G to determine if there is any leakage If there is any leakage remove the 56 2XXX Series assembly for inspection and repa...

Страница 12: ...one 2 Dubai UAE T 971 4 811 8443 F 971 4 886 5465 mea tescom emerson com www tescom com DOPSM2097X012 TescomCorporation 2015 2016 All RightsReserved Tescom is a business unit of Emerson Process Manage...

Отзывы: