5.5.2 Temperature settings in DHW circuit
1) A short pressing buttons + / - causes the activation of the D.H.W. settings mode. The value of D.H.W. temperature is flashing on the
left side of the display.
2) Buttons + / - enable to change the value of D.H.W. setting.
Completion of the operation changes mode is done automatically after 5 seconds of inactivity or after pressing the reset.
NOTICE:
1. In the case of system boilers, reducing the setting DHW results in stopping the water heating in the tank (below the value indicated
on the display by symbol ”MIN”). In the left field of display you can see the symbol „—„. To switch on again the function of heating water
in the tank it is necessary to increase the setting to the minimum value or higher.
2. When the controller is in STAND BY mode, service function mode, or in state of emergency blockade then the setting of C.H. and
D.H.W. cannot be changed.
5.6. Controller configuration – boiler parameters setting
It is possible to change the following parameters of the boiler through the procedure of programming:
Name
Values
Factory default values
Remarks
P01
Start power
0
÷
99 (100 steps from min to max )
see Table 4.3.2.1
-
P02
Max power for DHW
0
÷
99 (100 steps from min to max )
-
P03
Max power for CH
0
÷
99 (100 steps from min to max )
-
P04
Minimum speed limit
1000
÷
2000 [rotations/min] (1 step =
100 rotations/min)
-
P05
Maximum speed limit
2500
÷
9500 [rotations/min] (1 step =
100 rotations/min)
-
P06
Type of boiler selection
1
÷
2 (1 – system boiler, 2 – combi
boiler)
Depending on boiler type
Parameter is visible when
the CM clamp is removed
P07
Type of CH circuit
1 – closed
1
Boiler adapted for closed central
heating system
P08
Type of heating
0 / 1 (0 – standard heating, 1 – floor
heating)
0
-
P09
Type of CH pressure
transducer
0 / 1 (0 – type: 0,5 ÷ 3,5 V; Uz=18V,
1 – type: 0,5 ÷ 2,5 V; z=5V;
1
Transducer connection:
0 – socket M10
1 – socketM12
P10
"Anti-legionella” mode
0 / 1 (0 – manual mode, 1 – automatic
mode)
0
important only in case of boilers
with water tanks
P11
The number of pulses per
rotation
1/2/3/4 [pulses / rotation]
2
-
P12
Type of pump
0 / 1 (0 – standard, 1 – with PWM
signal)
Depending on boiler type
-
P13
∆
T for pump with PWM signal
5
÷
25 °C
6
Parameter is visible when P12=1
and P15=0 and P07=1
P14
Min pump flow
15
÷
99%
50
Parameter is visible for P12=1 and
P07=1
P15
ECO mode
0 / 1 (1 – ON, 0 – OFF)
0
Parameter is visible for P12=1 and
P07=1
P16
a time when a boiler is
working with max CH power
which is set by parameter P17
0÷5 min
0
P17
value of max CH power when
a boiler works for a specified
by parameter P16 period
0÷25%
10
Parameter is visible when P16 > 0
P18
Max speed limit for modulating
pump in CH mode
25
÷
99 %
99
Parameter is visible when P12=1
P19
Max speed limit for modulating
pump in DHW mode (if P6=1)
25
÷
99 %
99
Parameter is visible when P12=1
and P6=1
P20
Hysteresis for the condition of
switching off at work in CH
circuit
0
÷
10
5
P21
CH temperature during
heating the DHW in tank (if
P6=1)
70
÷
89
75
Parameter is visible when P6=1
P22
The value of the parallel
displacement of the heating
curve of weather regulator
0
÷
20
0
Parameter visible for P26=1 or 2
P23
Fan type selection
0 ÷ 1 (0 – FIME, HONEYWELL
FPE4200A; 1 – SIT NG40)
1
P24
Startup power maintaining
time during work in CH circuit
2
÷
30 sec
20
reset
2
1