background image

 

Tech-Tip 93 

Released: 6/19/2019 

Tech Tips 

Step 2 

Complete a thorough daily inspection of the unit, 

including running all boom functions through 

their full range of motion before beginning any 

dielectric testing. Daily inspection criteria can be 

found in the unit specific operators and 

maintenance manuals. 

 

The fiberglass booms must be clean, dry and in 

good physical condition.  Check carefully for any 

bird’s nests, material buildup, or hydraulic leaks 

in the boom or control areas. Check under the 

boom tip covers and look down each boom from 

both ends checking for a blockage or any signs 

of a leak.  A bird’s nest, blockage, or leak in the 

boom could ignite and cause a fire during the 

dielectric test. 

 

If a blockage or leak is found it must be repaired 

and the unit cleaned prior to continuing with the 

dielectric test. 

 

Record all unit info and weather conditions on 

the dielectric test sheet prior to starting the test.  

The test sheets are included in the Manual and 

can be copied as needed.

 

Содержание L13I

Страница 1: ...9 2019 Tech Tips Service Call AC Dielectric Testing of a Category C Telescopic Aerial Device Tools Required AC Dielectric Tester Insulating Outrigger Pads Safety equipment to create a dielectric test...

Страница 2: ...epair procedures are performed Do Not Perform Maintenance Unless You are trained and qualified to perform maintenance on this machine You read understand and obey o manufacturer s instructions and saf...

Страница 3: ...anyone unassociated with the procedure out of the testing area If a barrier is not available use a spotter s The AC Dielectric Tester voltage source should also be contained within this area The test...

Страница 4: ...er the unit is insulated or non insulated If the unit is insulated the qualification voltage and rating of the unit will be shown Verify that the boom is designed as insulated before proceeding with t...

Страница 5: ...for any bird s nests material buildup or hydraulic leaks in the boom or control areas Check under the boom tip covers and look down each boom from both ends checking for a blockage or any signs of a l...

Страница 6: ...lace the transmission in neutral and turn on the PTO Set the unit up for operation by deploying the outriggers onto insulating platforms pads centered under the outrigger foot reference Figure 1 Once...

Страница 7: ...om 5 Platform bracket to boom tip bracket 6 Jib bracket if equipped to platform bracket 7 Verify that the jumpers make good contact by removing paint if needed at the attachment location prior to atta...

Страница 8: ...Tech Tip 93 8 Released 6 19 2019 Tech Tips Figure 2...

Страница 9: ...he boom tip This may be attached at the same location as the jumpers that were installed at the boom tip See Figure 3 Keep the test machine directly below or away from the truck if possible Follow the...

Страница 10: ...e lower and upper booms both at 45 degrees Extend the upper boom to the minimum extension decal if equipped Visually check that all jumpers voltage source from the AC Dielectric Tester and return are...

Страница 11: ...l connections If the current meter value stays below the Max Leakage continue the test until complete record readings return the voltage control to 0 turn off and unplug the dielectric machine If the...

Страница 12: ...or after a major component such as a boom is replaced Periodic testing is done once a year to verify dielectric integrity of the unit For a Category C AC Qualification test the reading should be no hi...

Страница 13: ...below rotation 1 Lower boom insert 3 Upper boom to knuckle 4 Knuckle to lower boom 5 Platform bracket to boom tip bracket 6 Jib bracket if equipped to platform bracket 7 See Figure 2 to identify jumpe...

Страница 14: ...lectric Tester to the knuckle side of the lower boom and install jumpers between components in the following locations as shown in Figure 4 below Lower boom to knuckle 1 Lower boom link to knuckle 2 T...

Страница 15: ...heet Monitor the volt and current meters to verify that the test is working correctly If the current meter value stays below the Max Leakage continue test until complete record readings return the vol...

Страница 16: ...below For a Chassis Insulating System Lower Boom Insert Qualification test the reading should be no higher than 3000 A for 3 minutes at 50 KV For a Chassis Insulating System Lower Boom Insert Periodi...

Страница 17: ...from the following locations indicated in Figure 4 Lower boom to knuckle 1 Lower boom link to knuckle 2 Turntable above rotation to pedestal below rotation 3 Lower boom link to turntable 4 Remove the...

Страница 18: ...Tip 93 18 Released 6 19 2019 Tech Tips Step 15 Attach the voltage source from the AC Dielectric Tester to the control handle using a spring with the cable going over the top of the platform as shown b...

Страница 19: ...19 Released 6 19 2019 Tech Tips Step 16 Reach under the upper control cover and attach the current meter return to a fitting that is attached to the upper control valve as shown below Cover removed f...

Страница 20: ...listed on the test sheet Monitor the volt and current meters to verify that the test is working correctly If the current meter value stays below the Max Leakage continue the test until it is complete...

Страница 21: ...hould be no higher than 400 A for 3 minutes at 40 KV A Microamp Step 19 Once testing is complete lower the platform to the ground mount position Remove the spring from the control handle and current m...

Отзывы: