17
Alarm
code
Description
What to do
18
Table charts not
available..
The operating
condition selection is
missing
•Please, select the operating mode in use and
confirm it.
20
Group
Alarm.Configuration
errore
•Please, select the operating mode in use and
confirm it.
6
Page
22, 23,
24, 32
Boom length sensor 1
reading lower than the
minimum value
• Verify that the wiring and the connectors are not in
short circuit
If the alarm persists, please, contact Technical
Assistance:
Verify the length transducer integrity
7
Page
22, 23,
24, 32
Boom length sensor 1
reading higher than
the maximum value
• Verify that the cable or the connector wiring is not
open
If the alarm persists, please, contact Technical
Assistance :
• Verify the length transducer integrity
NOTE: The code of the alarms can change in case of particular functions or client
needs