Alarm
code
Description
What to do
13
Page
27
Pressure reading of
the main cylinder (rod
side) lower than the
minimum.
•Verify that the wiring and the connectors are not in
short circuit
If the alarm persists, please, contact Technical
Assistance :
•Verify the pressure transducer integrity
23
Page
28
Pressure reading
pressure of the main
cylinder (rod side)
higher than the
maximum.
• Verify that the cable or the connector wiring are
not open
If the alarm persists, please, contact Technical
Assistance :
•Verify the pressure transducer integrity
E01
RADIUS
MIN
The boom’s angle has
overtaken the
maximum value
• Lower the boom
E02
RADIUS
MAX
This message appears
when the boom is
positioned in a way
that, referring to the
load charts, there isn’t
any load charts table
applicable
•Lift or close the crane boom until a load chart table
can be applied.
11
Page
29, 30,
31
Boom length sensor
total reading lower
than the minimum
value
• Verify that the wiring and the connectors are not in
short circuit
If the alarm persists, please, contact Technical
Assistance:
Verify the length transducer integrity
21
Page
29, 30,
31
Boom length sensor
total reading higher
than the maximum
value
• Verify that the cable or the connector wiring is not
open
If the alarm persists, please, contact Technical
Assistance :
• Verify the length transducer integrity