7-11
(4) Inspection mode setting
: Inspection mode setting
Function
Enters/Exits the inspection mode.
* The inspection mode setting is not retained when the power is shut off.
Setting range
: In inspection mode
: In normal mode
Initial setting
: In normal mode
Remarks
For the inspection mode, refer to “8.2 Inspection mode.”
(5) Energy-saving operation setting
: Energy-saving operation setting
Function
Enables/Disables the energy-saving operation.
The energy-saving operation enables variable control of pump-stop
period depending on the operation conditions of the unit in automatic
mode.
Adjustable
range
: Enables the energy-saving operation
: Disables the energy-saving operation
Initial setting
: Enables the energy-saving operation
Remarks
If the energy-saving operation is disabled, the pump-stop check period is
set to 60 seconds.
7.5.4 Extended
parameters
The following are extended parameters for setting or adjusting various functions of the water supply unit.
Note
Extended parameters can be changed only when the operation mode is set to
“Stop.” Therefore, make the settings before starting the operation of the water
supply unit.
(1) External relay output pattern setting
: External relay output pattern setting
Function
Seletcts a pattern of the signals to be output from the relays M1, M2, and
B1 to B5.
For the patterns, see Table 7-5-4.
Adjustable
range
0 to 4
Initial setting
0 (This can be preset to a value that is specified when an order is placed.)
Remarks
The common terminal for M1 and M2 is MC, and the common terminal for
B1 to B5 is BC.