7-13
(2) Number of water level electrode bars setting
: Number of Water Level Electrode Bars
Function
Seletcts the number of electrode bars for measuring the water level
Adjustable
range
4: 4 electrode bars (4P)
5: 5 electrode bars (5P)
Initial setting
4: 4 electrode bars (4P)
(If you specify the other value upon placing an order, the specified value
is preset in the parameter.)
Remarks
Setting this to “4 electrode bars” causes the system to ignore the input of
the electrode bars 1E4 and 2E4.
(3) 5P-electrode bar pattern setting
: 5P-Electrode Bar Pattern
Function
Seletcts the pattern for assigning a monitoring task to each electrode
when the “Number of Water Level Electrode Bars” setting is set to “5
electrode bars.”
Adjustable
range
0: Standard
1: Special
Initial setting
0: Standard (If you specify the other value upon placing an order, the
specified value is preset in the parameter.)
Remarks
This setting is ignored when 4 electrode bars are selected in P101.
(4) Solenoid valve type setting
: Solenoid Valve Type
Function
Seletcts the type of the solenoid valve connected to the control panel.
Adjustable
range
0: Normally open type
1: Normally closed type
Initial setting
0: Normally open type
(If you specify the other value upon placing an order, the specified value
is preset in the parameter.)
Remarks -
5P-electrode bar patterns
Setting: 0
Setting: 1
Full water level
Full water level
Low water level
Low water level
Dry-run recovery
Dry-run recovery
Dry-run prevention Dry-run prevention
Ground Ground