13.1 - Voltage Settings:
-7-
Pr.1:
High Voltage Protection Value
Pr.2:
High Voltage Protection Delay time
Pr.3:
High Voltage Protection Reset time
Pr.4:
High Voltage Protection Hysteresis
Pr.5:
High Voltage Protection Enable/Disable
Pr.6:
Low Voltage Protection Value
Pr.7:
Low Voltage Protection Delay time
Pr.8:
Low Voltage Protection Reset time
Pr.9:
Low Voltage Protection Hysteresis
Pr.10:
Low Voltage Protection Enable/Disable
Pr.11:
Voltage Asymmetry Protection Value
Pr.12:
Voltage Asymmetry Protection Delay
T
ime
Pr.13:
Voltage Asymmetry Protection Reset
T
ime
Pr.14:
Voltage Asymmetry Protection Hysteresis
Pr.15:
Voltage Asymmetry Protection Enable/Disable
Pr.16:
Voltage Auto Reset Enable/Disable
Pr.17:
Voltage Transformer Ratio
Pr.18:
Voltage Fuses Enable/Disable
Pr.19:
Voltage Protection Type
Figure-33
Figure-32
Set
Esc
V
Figure-42
Figure-43
Figure-34
Figure-35
Figure-36
Figure-37
Figure-38
Figure-39
V
V
Figure-40
V
Figure-41
Press Menu button and enter password (Default Password =0000)
to enter program list. The figure-26 is displayed when you enter
password and press the Menu button. You enter Voltage set when
you press Menu button. If you enter voltage set menu, the figure-32
displayed. This menu have 19 different voltage set value. When you
press the up button to see the other voltage set values on the display,
the next data is displayed. The figure-32 is displayed when you press
the up button after the Pr.19 is displayed. By using up-down buttons
select the program. Press Menu to enter required program.
By up-down buttons, you can set the program. Press Menu to record
your settings, if you press ESC button, you cannot record your settings.
Figure-26
Figure-48
Figure-47
Figure-46
Figure-45
Figure-49
Figure-44
Figure-50
Figure-38
Figure-36
Figure-35
V
V
Figure-32
Pr.1 : High Voltage Protection Value
:
Determines the maximum operating voltage
value of load.
Default
:
250V,
Min:
1V,
Max:
300V
Pr.6: Low Voltage Protection Value
:
Determines the minimum operating voltage
value
of load.
Default:
170V,
Min:
1V,
Max:
300V
Figure-33
Pr.2: High Voltage Protection Delay Time
: Determines delay open time. Delay time for
activating the output. If any voltage exceeds high voltage protect value, Relay output
switches open at the end of delay time.
Default:
3sec,
Min:
1sec,
Max:
10000sec.
Pr.7: Low Voltage Protection Delay Time
: Determines delay open time. Delay time for
activating the output. If any voltage over the low voltage protect value, Relay output
switches open at the end of delay time.
Default:
3sec,
Min:
1sec,
Max:
10000sec.
Figure-34
Pr.3: High Voltage Protection Reset Time:
Determines delay close time. If all voltage
below the high voltage protect value as a hysteresis voltage , relay output switches close
at the end of the reset time.
Default:
3sec,
Min:
1sec,
Max:
10000sec.
Pr.8: Low Voltage Protection Reset Time:
Determines delay close time.If all voltage
below the low voltage protect value as a hysteresis voltage , relay output switches close
at the end of the reset time.
Default:
3sec,
Min:
1sec,
Max:
10000sec.
Pr.4: High Voltage Protection Hysteresis:
Required hysteresis voltage for high voltage
warning is programmed.
Default:
5V,
Min:
1V,
Max:
200V
Pr.9: Low Voltage Protection Hysteresis:
Required hysteresis voltage for low voltage
warning is programmed.
Default:
5V,
Min:
1V,
Max:
200V
Pr.5: High Voltage Protection Enable/Disable:
Determines Enable or Disable the high
voltage protection.
Default:
Enable,
Min:
Disable,
Max:
Enable
Pr.10: Low Voltage Protection Enable/Disable:
Determines Enable or Disable the low
voltage protection.
Default:
Enable,
Min:
Disable,
Max:
Enable
Figure-37
V
Figure-39
Figure-40
V
Figure-41
-8-