Current SET menu is include set of high/low current protection,current transformer
ratio and demurrage setings.
Figure-27
Pr.20 is displayed when you press the “SET” button and press
“Up” button. You will see Pr.36
(Figure-67).It is using for
setting current transformer ratio. You can increase/decrease
value to use Up/Down Button. You can use “SET” button to save.
The figure-67 is displayed when you press the SET button.
Press “Up” button until you see the Pr.25
(figure-56).
A
Figure-51
A
Pr36 It is using for setting current transformer ratio. You
can increase/decrease value to use Up/Down Button. You can
use “SET” button to save. The figure-67
is displayed
when you press the SET button. Press “Up” button until you
see the Pr.25
(figure-56).
Figure-67
Pr.25 is using for setting low current protection. It is deleted
from screen when you press the “SET” button. You can
increase/decrease value to use Up/Down Button. You can use
“SET” button to save. The figure-56
is displayed when you
press the SET button. Press “Up”button until you see the
Pr.20
(figure-51)
A
A
Figure-56
Pr.40 is using for setting demurrage time. It is deleted from
screen when you press the “SET” button. You can
increase/decrease value to use Up/Down Button. You can use
“SET” button to save. The figure-71 is displayed when you
press the SET button. Press twice “ESC” button for back to
home screen.
Figure-71
All settings are made. Press ESC to exit. The figure-27 is displayed on screen.
Press the ESC key again.
Figure-27
-21-
Şekil-70
Pr.39 is using for setting demurrage time. It is deleted from
screen when you press the “SET” button. You can
increase/decrease value to use Up/Down Button. You can use
“SET” button to save. The figure-70
is displayed when
you press the SET button. Press “Up”button until you see the
Pr.40
(figure-71)
.
Figure-70
You have exited the menu. The “Home Screen” is displayed on screen.
The device will control according to the set values.
A
A
V
L1
L2
L3
V
V
A
Home Screen
Parameter
Minimum
Value
Default
Value
Unit
Maximum
Value
Parameter
Number
Menu
300
5.0
5.0
70.0
70.0
%50
300
200
Enable
3.0
Enable
3.0
Enable
20.0
20.0
Enable
Enable
Enable
247
38400
9999
Enable
Enable
120
-
20
-
-
%20
Enable
Enable
2000
Enable
Enable
200
Enable
%10
Enable
Enable
%30
10000
10000
10000
10000
10000
10000
100
10.0
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
999
Enable
L-L
1
0.1
0.1
45.0
45.0
%5
1
1
Disable
0.1
Disable
0.1
Disable
0.1
0.1
Disable
Disable
Disable
1
1200
0000
Disable
Disable
1
-
1
-
-
%1
Disable
Disable
1
Disable
Disable
1
Disable
%1
Disable
Disable
%5
1
1
1
1
1
1
1
1.0
1
1
1
1
1
1
1
1
1
1
1
Disable
L-n
250
3.0
0.1
51.0
49.0
%30
170
5
Enable
0.5
Enable
0.5
Enable
0.5
0.5
Disable
Disable
Disable
1
9600
0000
Disable
Disable
15
-
1
-
-
%3
Disable
Enable
1
Disable
Enable
5
Enable
%2
Enable
Enable
%20
3
3
3
3
3
3
10
3.0
3
3
3
10
10
3
3
10
3
3
1
Disable
L-n
Volt
Amper
Amper
Hertz
Hertz
-
Volt
Volt
-
Amper
-
Amper
-
Hertz
-
Hertz
-
-
-
bps
-
-
-
Minute
-
Round
-
-
-
-
-
-
-
-
Volt
-
-
-
-
-
Second
Saniye
Second
Second
Second
Second
Second
-
Second
Second
Second
Second
Second
Second
Second
Second
Second
Second
-
-
-
Pr.1
Pr.20
Pr.25
Pr.41
Pr.46
Pr.30
Pr.6
Pr.4
Pr.5
Pr.23
Pr.24
Pr.28
Pr.29
Pr.44
Pr.45
Pr.49
Pr.50
Pr.51
Pr.52
Pr.53
Pr.54
Pr.55
Pr.56
Pr.57
Pr.58
Pr.59
Pr.60
Pr.61
Pr.33
Pr.34
Pr.35
Pr.36
Pr.37
Pr.38
Pr.9
Pr.10
Pr.14
Pr.15
Pr.16
Pr.11
Pr.2
Pr.21
Pr.26
Pr.42
Pr.47
Pr.31
Pr.39
Pr.40
Pr.7
Pr.12
Pr.3
Pr.22
Pr.27
Pr.43
Pr.48
Pr.32
Pr.8
Pr.13
Pr.17
Pr.18
Pr.19
High Voltage Value
High Current Value
Low Current Value
High Frequency Value
Low Frequency Value
Current Asymmetry Value
Low Voltage Value
Voltage Asymmetry Value
High Voltage Reset Time
High Current Reset Time
Low Current Reset Time
High Frequency Reset Time
Low Frequency Reset Time
Current Asymmetry Reset Time
Low Voltage Reset Time
Voltage Asymmetry Reset Time
High Voltage Hysteresis
High Voltage Protection
High Current Hysteresis
High Current Protection
Low Current Hysteresis
Low Current Protection
High Frequency Hysteresis
High Frequency Protection
Low Frequency Hysteresis
Low Frequency Protection
Frequency Auto Reset
ModBus ID
ModBus BaudRate
Password Change
Password Protection
Phase Sequence
Demand Time
Demand Delete
C.T. Cable Turn Number
Serial Number
Version
Current Asymmetry Hysteresis
Current Asymmetry Protection
Current Auto Reset
Current Transformer Ratio
Current Fuse
Demurrage Protection
Demurrage Time
Demurrage Protection Factor
Low Voltage Hysteresis
Low Voltage Protection
Voltage Asymmetry Hysteresis
Voltage Asymmetry Protection
Voltage Auto Reset
Voltage Transformer Ratio
Voltage Fuse
Voltage Protection Type
High Voltage Delay Time
High Current Delay Time
Low Current Delay Time
High Frequency Delay Time
Low Frequency Delay Time
Current Asymmetry Delay Time
Low Voltage Delay Time
Voltage Asymmetry Delay Time
-22-
25 - Parameters Table: