Pr.20: High Current Protection Value
:
Determines the maximum operating current
value of load.
Default:
3.0A,
Min:
0.1A,
Max:
5.0A
Pr.21: High Current Protection Delay Time
: Determines delay open time. Delay time
for activating the output. If any current exceeds high current protect value, Relay output
switches open at the end of delay time.
Default:
3sec,
Min:
1sec,
Max:
10000sec.
Pr.26: Low Current Protection Delay Time
: Determines delay open time. Delay time
for activating the output. If any current over the low current protect value, Relay output
switches open at the end of delay time.
Default:
3sec,
Min:
1sec,
Max:
10000sec.
Pr.22: High Current Protection Reset Time:
Determines delay close time.If all current
below the high current protect value as a hysteresis current, relay output switches close
at the end of the reset time.
Default:
10sec,
Min:
1sec,
Max:
10000sec.
Pr.27: Low Current Protection Reset Time:
Determines delay close time.If all current
below the low current protect value as a hysteresis current, relay output switches close
at the end of the reset time.
Default:
10sec,
Min:
1sec,
Max:
10000sec.
Pr.23: High Current Protection Hysteresis:
Required hysteresis current for high
current warning is programmed.
Default:
0.5A,
Min:
0.1A,
Max:
3.0A
Pr.28: Low Current Protection Hysteresis:
Required hysteresis current for low voltage
warning is programmed.
Default:
0.5A,
Min:
0.1A,
Max:
3.0A
Pr.24: High Current Protection Enable/Disable:
Determines Enable or Disable the
high current protection.
lir.
Default:
Enable,
Min:
Disable,
Max:
Enable
Pr.29: Low Current Protection Enable/Disable:
Determines Enable or Disable the low
current protection.
Default:
Enable,
Min:
Disable,
Max:
Enable
-11-
Figure-51
A
Pr.25: Low Current Protection Value
:
Determines the minimum operating current
value of load.
Default:
0.1A,
Min:
0.1A,
Max:
5.0A
Figure-58
Figure-59
V
Figure-69
Figure-68
Figure-66
Figure-65
Figure-64
Figure-63
Figure-62
Figure-61
Pr.37: Current Fuses Enable/Disable:
If any phase current exceeds 1.5 times of high
current protect value, or ,if any phase current decrease 0.5 times of low voltage protect
value, the relay switches off instantly. At position disable, current fuses function is
cancelled.
Default:
Disable,
Min:
Disable,
Max:
Enable
-12-
Pr.30: Current Asymmetry Protection Value
:
Determines the controlled current
asymmetry.
Asymmetry Ratio Adjusment:
Device calculates a value by dividing
difference between highest and lowest phase value to highest phase value.
Default:
%30,
Min:
%5,
Max:
%50
Pr.31: Current Asymmetry Protection Delay Time
: Determines delay open time.
Delay time for activating the output. If calculated asymmetry value below the current
asymmetry protect value, Relay output switches open at the end of delay time.
Default:
3sec,
Min:
1sec,
Max:
10000sec.
Pr.32: Current Asymmetry Protection Reset Time:
Determines delay close time.
If calculated asymmetry value over the current asymmetry protect value as a hysteresis
current, relay output switches close at the end of the reset time.
Default:
10sec,
Min:
1sec,
Max:
10000sec.
Pr.33: Current Asymmetry Protection Hysteresis:
Required hysteresis current for
current asymmetry warning is programmed.
Default:
%3,
Min:
%1,
Max:
%20
Pr.34: Current Asymmetry Protection Enable/Disable:
Determines Enable or Disable
the current asymmetry protection.
Default:
Disable,
Min:
Disable,
Max:
Enable
Pr.38: Demurrage Protection Enable/Disable:
Determines Enable or Disable the
demurrage protection.
Default:
Enable,
Min:
Disable,
Max:
Enable
Pr.35: Current Auto Reset Enable/Disable
:
If auto reset enable and system into error,
if all current are over/below the protect value as hysteresis value ,relay output switches
on at the end of the Reset time. If Auto reset is disable, after all current are over/below
hysteresis value, relay output switches manually. (Using ESC button).
Default:
Enable,
Min:
Disable,
Max:
Enable
Figure-67
Pr.36: Current Transformer Ratio
: If a current transformer which has a ratio of
100/5A is used between the system and device; Current transformer ratio is entered
as = 100/5 = 20. If the current transformer is not used between the system and device,
current transformer ratio is entered as ”1”
Default:
1,
Min:
1,
Max:
2000
Figure-72
Pr.39: Demurrage Protection Time
:
Demurrage time is used to prevent from faulty
switching caused by motor Demurrage current. In this period, demurrage is controlled
by device.
Default:
10,
Min:
1,
Max:
100